Once a project is classed as a high-rise building in the Saudi Building Code, the fire requirements step up: sprinklers throughout, voice evacuation, a fire command center, smokeproof exit stairs, and standby and emergency power. Section 403 of SBC 201 gathers these requirements in one place and points each one to its detailed section.
This article lays out Section 403 as written in the official public-access text of the 2024 edition, with the section number for each item, so owners, consultants and contractors know what will be checked. AZEIDK supports this stage through its engineering design and calculations service, and supplies and installs the fire fighting systems required.
Key takeaways
- SBC 201 defines a high-rise building as one with an occupied floor located a significant height above the lowest level of fire department vehicle access; Sections 403.2 to 403.6 then apply.
- Sprinklers throughout to Section 903.3.1.1, with a secondary water supply where Section 403.3.3 requires it.
- Automatic smoke detection, fire alarm, emergency voice/alarm communication, standpipes, emergency responder radio coverage and a fire command center are required.
- Every interior exit stairway is a smokeproof enclosure, separated by fire barriers of not less than 2 hours.
- Standby and emergency power, luminous egress path markings and a fire service access elevator are required.
What is a high-rise building in the Saudi Building Code?
Chapter 2 of SBC 201 defines a high-rise building as a building with an occupied floor located a significant height above the lowest level of fire department vehicle access. The test is not the number of storeys or the total tower height, but the height of the highest occupied floor measured from where fire vehicles can reach.
The public summary text does not state the numeric threshold in the definition, so confirm it in the full adopted edition or with Civil Defense at design stage. Section 403.1 applies Sections 403.2 to 403.6 to high-rise buildings, with the exceptions it lists.
Construction: fire resistance and structure
- Reduced fire-resistance ratings (403.2.1): the reductions in Sections 403.2.1.1 and 403.2.1.2 are allowed in buildings with sprinkler control valves fitted with supervisory and water-flow initiating devices on every floor. Floor-by-floor valve supervision is therefore a condition of the reduction, not just an operating detail.
- Integrity of exit stair and elevator enclosures (403.2.2): specific structural requirements apply.
- Sprayed fire-resistant materials (403.2.3): bond strength throughout the building must meet the section.
Sprinklers and standpipes
Section 403.3 requires an automatic sprinkler system throughout to Section 903.3.1.1, with a secondary water supply where Section 403.3.3 requires it; only the spaces listed in the Section 403.3 exceptions are exempt. Section 403.4.3 requires standpipes per Section 905.3, and Section 905.3.1 requires Class III standpipes throughout where any of its height conditions apply.
Tall buildings also see high pressure on lower floors, typically handled with pressure zones and pressure reducing valves; see high-rise building fire pumps and fire pressure reducing valves.
Detection, alarm and emergency systems
| System | SBC 201 section | Detailed reference |
|---|---|---|
| Automatic smoke detection | 403.4.1 | 907.2.13.1 |
| Fire alarm system | 403.4.2 | 907.2.13 |
| Standpipe system | 403.4.3 | 905.3 |
| Emergency voice/alarm communication | 403.4.4 | 907.5.2.2 |
| Two-way emergency responder radio coverage | 403.4.5 | SBC 801 Section 510 |
| Fire command center | 403.4.6 | 911, location approved by the fire code official |
| Post-fire smoke removal | 403.4.7 | Natural or mechanical ventilation by the listed methods |
| Standby and emergency power | 403.4.8 | 2702 and 3003 |
Section 907.2.13 adds a fire department communication system (907.2.13.2) alongside smoke detection and voice evacuation, with its listed exceptions. In practice, sounders and strobes alone are not enough. For alarm triggers in other buildings, see when a fire alarm is mandatory under SBC 801. Smoke removal under Section 403.4.7 is for post-fire salvage and overhaul, not smoke control during evacuation.
Means of egress
- Stair separation (403.5.1): the separation between interior exit stairways is set by the section and measured in a straight line between the nearest points of the stair enclosures.
- Additional stair (403.5.2): buildings other than Group R-2 that meet the section’s conditions need one extra interior exit stairway beyond the minimum in Section 1006.3, and the remaining stairs must still have enough capacity with one stair removed.
- Stair doors (403.5.3): doors may be locked from the stair side under the section’s conditions, including that locked doors can be opened simultaneously.
- Smokeproof enclosures (403.5.4): every interior exit stairway is a smokeproof enclosure under Sections 1023.12 and 909.20, separated from the building by fire barriers of not less than 2 hours, using natural ventilation, mechanical ventilation or stair pressurization. See smoke control and stair pressurization.
- Luminous egress path markings (403.5.5): provided per Section 1025.
Elevators
Section 403.6 requires elevators to follow Chapter 30 and Sections 403.6.1 and 403.6.2: the first covers the fire service access elevator, and the second allows passenger elevators installed per Section 3008 to be used for occupant self-evacuation.
How owners and consultants should prepare
- Decide at concept stage whether the building is high-rise, measuring the highest occupied floor from the lowest fire vehicle access level, and confirm the adopted threshold.
- Turn Section 403 into a checklist and assign each item to a system and a responsible party.
- Coordinate systems: sprinklers with valve supervision, alarm with voice evacuation, smoke control with elevators.
- Plan integrated acceptance tests before handover.
For residential towers specifically, see fire safety in high-rise residential towers. For choosing the fire fighting system itself, see the fire fighting system selection guide.
Frequently asked questions
How does the Saudi Building Code define a high-rise building?
A building with an occupied floor a significant height above the lowest level of fire department vehicle access; confirm the adopted threshold in the full code edition and with Civil Defense.
Are sprinklers required throughout a high-rise?
Yes. Section 403.3 requires sprinklers throughout to Section 903.3.1.1, except the spaces it exempts.
Is a conventional sounder alarm enough?
No. A high-rise needs emergency voice/alarm communication to Section 907.5.2.2 and a fire department communication system.
What is a fire command center?
The main location where the status of detection, alarm and control systems is shown and from which they can be controlled manually, required by Section 911.
What rating do high-rise stair enclosures need?
Each interior exit stairway is a smokeproof enclosure separated by fire barriers of not less than 2 hours under Section 909.20.
How does AZEIDK help on a high-rise project?
With design and calculations, and with supply, installation, testing and maintenance of fire fighting and fire alarm systems.
Could your project be a high-rise? Send the drawings to AZEIDK to check the Section 403 requirements and related systems before submission. Contact AZEIDK
Related guides
- Cinema Fire Safety: Voice Evacuation, Smoke Control and Alarms for Dark Auditoriums
- Fire Extinguishers in Schools: Right Type for Each Space, Quantity, Mounting and Inspection
- Aramco iktva vs the Local Content Certificate: What Fire and Security Suppliers Need to Know
- CCTV Maintenance SLA: Response Time, Repair Time and Recording Availability