Foam Bladder Tank Comparison: WATEX, FIRETECH, Falcon Gold and SFFECO by Approval, Capacity and Pressure

Foam Bladder Tank Comparison: WATEX, FIRETECH, Falcon Gold and SFFECO by Approval, Capacity and Pressure

When a Saudi project needs a foam bladder tank, the question that usually follows is which brand to specify. AZEIDK supplies four: WATEX, FIRETECH, Falcon Gold and SFFECO. This comparison puts their published data side by side (approval, capacity range, working pressure, vessel and bladder materials, options) so the choice follows the project specification rather than the name on the tank.

If you first need the basics of how a bladder tank works and how it is sized, start with our guide to foam proportioning and bladder tanks, then come back here. All four tanks sit within AZEIDK’s special fire suppression systems scope.

Key points

  • WATEX and FIRETECH: bladder tanks with a ratio controller, UL listed under Proportioners, Foam Concentrate, with the UL file numbers published on the product pages.
  • FIRETECH publishes the widest capacity range (100 to 20,000 L), a flow range of 75 to 36,000 L/min and a twin-vessel (main and reserve) option.
  • Falcon Gold: roughly 189 to 12,000 L at 175 psi with a long options list; the product page does not quote a UL listing, so ask for approval documents if the specification requires one.
  • SFFECO: models SFD-U2 to SFD-U8-BTRFC, vertical and horizontal; capacity and pressure come from the model datasheet at quotation stage.
  • All four work the same way: fire water pressure squeezes the bladder and pushes concentrate to the ratio controller, with no foam pump and no power supply.
In this article
  1. Foam bladder tank comparison table
  2. WATEX: UL listed tank and ratio controller
  3. FIRETECH: widest capacity range and a reserve tank option
  4. Falcon Gold: a long options list, built to order
  5. SFFECO: SFD-U models, vertical and horizontal
  6. How to choose between the four
  7. Common comparison mistakes
  8. Frequently asked questions
  9. Summary

Foam bladder tank comparison table

The data below comes from AZEIDK’s product pages, which in turn quote the manufacturers’ catalogues and UL records. Where a cell says “not stated”, the page simply does not give that item; it does not mean the product lacks it.

ItemWATEXFIRETECHFalcon GoldSFFECO
Published approvalUL, certificate EX29807 to UL 162UL, file EX15733Not stated on the product pageNot stated on the product page
CapacityVertical 200 to 7,500 L; horizontal 1,000 to 15,000 L100 to 20,000 LAbout 189 to 12,000 L (50 to 3,200 gal)Per model datasheet
Rated pressure175 psi12.06 bar (175 psi)175 psi (about 12 bar)Per datasheet
Test pressure18.5 kg/cm² (1.5 x rated)18 bar1.5 x working pressurePer datasheet
Design codeASME Section VIII Div. 1ASME Section VIII Div. 1ASME Section VIIINot stated
Vessel materialSA-516 Gr. 70Carbon steel, or stainless 304/L or 316/LCarbon steelStainless steel or metal alloy, by application
BladderFabric-reinforced nitrile (Buna-N), replaceable on site through the manholeNylon-reinforced nitrile, UL listed for AFFF 1%, 3% and AR-AFFF 3×3%Nylon-reinforced Buna-NNot stated
OrientationVertical and horizontalVertical and horizontalVertical and horizontalVertical and horizontal
Ratio controller65 to 200 NB, models WTX-BT and WTX-SSRatio-flow controller within the listingOptional, pre-piped to the tankWorks with a ratio controller

WATEX: UL listed tank and ratio controller

The WATEX foam bladder tank page cites UL certificate EX29807 in the foam concentrate proportioner category under UL 162, covering the ratio-flow controller with ASME horizontal tanks of 264 to 3,963 gallons and vertical tanks of 53 to 1,982 gallons. Minimum working pressure is 30 psi, operating temperature 2 to 65 °C, finish fire red RAL 3000, and the manufacturer gives a five-year warranty. Sizing and ratio controller selection are covered in our WATEX foam bladder tanks guide.

FIRETECH: widest capacity range and a reserve tank option

The FIRETECH foam bladder tank page cites UL file EX15733 for the ratio-flow controller with bladder tank, with ASME vertical tanks of 25 to 3,963 gallons and horizontal tanks of 53 to 5,300 gallons in the listing. From the datasheet: 100 to 20,000 litres, a flow range of 75 to 36,000 L/min, coal tar epoxy lining and a fire red polyurethane finish. Options include the ASME U stamp, CE marking and a twin-vessel main and reserve arrangement with switchover, which some consultants ask for where protection cannot be down during refilling.

Falcon Gold: a long options list, built to order

The Falcon Gold foam bladder tank page describes a carbon steel ASME Section VIII vessel rated at 175 psi, a nylon-reinforced Buna-N bladder, a perforated PVC centre tube, brass trim valves with Teflon seats and about 10% extra volume for thermal expansion of the concentrate. Options include a pre-piped proportioner, sight glass, access ladder, stainless trim, salt-water coating and insulation or heat tracing. The page does not quote a UL listing number, so if the specification calls for a particular approval, ask for the document with the technical offer.

SFFECO: SFD-U models, vertical and horizontal

The SFFECO foam bladder tank page lists five models from SFD-U2-BTRFC to SFD-U8-BTRFC in vertical and horizontal versions with a corrosion-resistant finish, for foam deluge and sprinkler systems, fuel storage areas, aircraft hangars and loading racks. Capacity, working pressure and approvals are not given on the page, so they come from the model datasheet when the offer is prepared. The rest of the range is on the SFFECO brand page.

How to choose between the four

  1. Start with the required approval. If the specification calls for a UL listed tank and ratio controller, the published data points to WATEX and FIRETECH; confirm the listing covers the capacity and controller size you need.
  2. Then capacity and orientation. Capacity follows the hydraulic calculation, concentrate percentage and discharge time; orientation follows the floor area and headroom in the room.
  3. Then the concentrate. Make sure the bladder is approved for the concentrate on the project; FIRETECH’s bladder, for example, is listed for AFFF 1% and 3% and AR-AFFF 3×3%. Concentrate selection is covered in our guide to AFFF foam concentrate brands.
  4. Then environment and options. Coastal and marine sites need a suitable coating; critical facilities may need a reserve tank.
  5. Finally supply and support. Lead time and spares such as a replacement bladder vary by brand and size.

Common comparison mistakes

  • Comparing nominal capacity only, without checking that the listing or approval covers that exact size.
  • Pairing a UL listed tank with a ratio controller from another brand that is not part of the same listing.
  • Topping up with a different concentrate from the one already in the tank; see our article on mixing firefighting foam concentrates.
  • Skipping concentrate testing after installation; see AFFF shelf life and testing.

Frequently asked questions

Which is the best foam bladder tank in Saudi Arabia?

There is no single best brand. The right tank is the one that matches the approval, capacity and concentrate in your project specification.

Which AZEIDK foam tanks are UL listed?

According to the product pages, WATEX (certificate EX29807) and FIRETECH (file EX15733), both with a ratio controller.

What is the usual working pressure of a foam bladder tank?

The three tanks with published data (WATEX, FIRETECH and Falcon Gold) are rated at 175 psi, about 12 bar.

Does a bladder tank need a pump or power?

No. Fire water pressure squeezes the bladder and drives the concentrate to the ratio controller.

Can the bladder be replaced?

The WATEX page states the bladder can be replaced on site through the manhole. For the other brands, check the datasheet or ask the AZEIDK team.

When do I need a main and reserve tank?

When the specification or consultant requires protection to stay available during refilling or maintenance; FIRETECH lists this arrangement as an option.

Summary

The four foam bladder tanks AZEIDK supplies work on the same principle; they differ in published approval, capacity range and options. Start from the specification, then capacity, concentrate and environment, and ask for approval documents with the technical offer. The AZEIDK team will select the tank and ratio controller from your project data.

Need a foam bladder tank for a project? Send the concentrate type and percentage, solution flow, discharge time and required approval, and the AZEIDK team will recommend the tank and ratio controller. Contact AZEIDK

Share this article
This site is registered on wpml.org as a development site. Switch to a production site key to remove this banner.