Fire pumps in Riyadh are usually ordered by contractors on towers and compounds, owners of warehouses and factories in the industrial cities, and owners of existing buildings replacing an old pump. The right question is not “what does a pump cost?” but: what flow and pressure does the design need, where is the water level relative to the pump, and does the consultant require a UL listed or FM approved unit? Once those are answered, choosing the model is straightforward.

AZEIDK supplies fire pumps from SFFECO, WATEX and Jack Pump, plus non-listed 3PUMP packages, shown in the fire pumps section under fire fighting systems. If the consultant specifies another brand, the supply team works to source it to the required approvals. For a detailed comparison of pump types see fire pump types and selection.

Key points

  • Pump size comes from the hydraulic calculations of the approved design, not from floor area alone.
  • The water source decides the type: a tank above the pump suits end suction or split case; water below the pump usually needs a vertical turbine.
  • The SASO technical regulation requires a certificate of conformity for fire pumps, issued through the SABER platform.
  • Riyadh heat and dust make pump room ventilation and the care of batteries and filters part of design and maintenance.
  • AZEIDK has a Riyadh office, two showrooms and a warehouse in Al Yasmin.
In this article
  1. What do Riyadh facilities need from a fire pump?
  2. Choosing a fire pump in Riyadh by water source and flow
  3. Documents and approvals in Riyadh
  4. Pump rooms in Riyadh heat and dust
  5. AZEIDK branches in Riyadh
  6. Frequently asked questions

What do Riyadh facilities need from a fire pump?

Riyadh mixes office and residential towers, warehouses, factories and hospitals, and each needs something different from the pump set:

FacilityWhat drives pump selectionPractical note
Office and residential towersPressure needed at the top floorPressure zones or pressure reducing valves may be used per design
Warehouses and logisticsStorage height and commodity in the sprinkler designHigh-piled storage pushes required flow up sharply
Factories in industrial citiesLargest water demand across sprinklers, hydrants and any foam systemOften an electric pump, a standby diesel pump and a jockey pump
HospitalsSprinklers in every department and continuity during maintenanceAny pump shutdown is planned in advance with hospital management
Residential compoundsSprinklers, hose cabinets and hydrants across separate buildingsUsually a shared ground tank and a single pump room

For towers see fire pumps for high-rise buildings, and for PRVs see fire pressure reducing valves.

Choosing a fire pump in Riyadh by water source and flow

Start with three numbers from the designer: flow in gallons per minute (GPM), required pressure, and water level relative to the pump centreline. Then pick the type:

Pump typeWhen it fitsAvailable from AZEIDK
End suctionSmall to medium flows, water above the pumpJack Pump VES series (UL listed) and WATEX WE series
Split caseLarger flows for big factories and warehousesJack Pump MSC series and WATEX WS series
Vertical turbineWater below the pump, such as deep ground tanksJack Pump VTP series and WATEX vertical turbine
Non-UL packagesProjects whose specification does not require a listing3PUMP packages: electric, diesel and jockey

We do not quote a size before the calculations. The method is in fire pump sizing to NFPA 20, and a brand comparison in Jack Pump vs WATEX.

Documents and approvals in Riyadh

  • Calculations and drawings: the engineering office sets flow, pressure, tank size and the pump room.
  • Submittal: the supplier provides the datasheet, performance curve and listing certificate (UL 448 or FM) where specified, plus controller and driver details.
  • SABER conformity: the SASO technical regulation for fire control materials and equipment requires a certificate of conformity for fire pumps.
  • Testing and commissioning: an on-site performance test witnessed by the consultant before handover, under testing, commissioning and handover.
  • Salamah licence: AZEIDK handles the technical report through an approved engineering consultancy office and issues the safety equipment installation certificate for the systems it installs. See Civil Defense approval support.

Pump rooms in Riyadh heat and dust

  • Ventilation and heat: a diesel pump needs enough combustion and cooling air, and summer heat builds up quickly in a poorly ventilated room.
  • Batteries: diesel starting batteries age faster in heat and need regular checks.
  • Dust: it collects on air filters and panels, so cleaning is part of routine maintenance.
  • Fuel: diesel tank level and condition are checked on each visit.

Diesel pump components are covered in diesel fire pump components and NFPA 20, and controller service in fire pump controller maintenance.

AZEIDK branches in Riyadh

Details as shown on the contact page:

BranchAddressPhone
Riyadh officeSalah Al Din Street, Al Malaz+966 54 376 0300
Riyadh showroom, Salah Al Din StreetSalah Al Din Street, Al Malaz+966 54 364 7373
Riyadh showroom, Al Dhahran StreetAl Dhahran Street+966 54 366 7373
Riyadh warehouseAl Yasmin–

Project pump orders usually start at the office with the calculations or bill of quantities. Spare parts and accessories can be checked at the nearest showroom. If the existing pump is old, see replacing a fire pump in an existing building.

Frequently asked questions

Where can I buy a fire pump in Riyadh?

AZEIDK supplies Jack Pump, WATEX and SFFECO pumps and 3PUMP packages; project orders start at the Riyadh office.

What size fire pump does a Riyadh building need?

The designer sets it from the hydraulic calculations: required flow, pressure and water source, not floor area alone.

Does a fire pump need a SABER certificate?

Yes. The SASO technical regulation for fire control materials and equipment requires a certificate of conformity for fire pumps through SABER.

Do I need a diesel pump as well as an electric one?

The design decides, based on power supply reliability and project requirements; many factories and large facilities use a standby diesel pump.

Have pump calculations for a Riyadh project? Send the flow, pressure and drawings and AZEIDK will propose the right pump set. Contact AZEIDK

References: NFPA 20, the SASO technical regulation for fire control materials and equipment, and Riyadh branch details from the AZEIDK contact page.