The FIRETECH F226 foam spray nozzle is an open, non-air-aspirating nozzle for foam-water spray piping. It discharges low-expansion foam onto flammable-liquid fires, then water for cooling, with a similar spray pattern in both cases. It comes in K-43 and K-79, and the choice between them is not a small detail: it sets network pressure, nozzle count and pump size. This guide explains the nozzle using the figures on the AZEIDK product page and how it works with the deluge valve and foam tank.
AZEIDK supplies the F226 as part of its fire fighting systems, with design, hydraulic calculations, installation and testing.
Key points
- An open, non-air-aspirating nozzle, UL listed under Nozzles, Fixed Spray, Foam, file EX27977.
- Listed for use with AFFF and AR-AFFF concentrates per the datasheet.
- Two K-factors: K-43 (2.9 US) and K-79 (5.5 US), with a 140° discharge angle.
- Working pressure 2.1 to 12 bar for K-43 and 0.7 to 12 bar for K-79.
- SS 316 body (ASTM A351 CF8M), 1/2 inch BSPT male connection, NPT optional.
F226 technical data
| Item | K-43 | K-79 |
|---|---|---|
| K-factor (US units) | 2.9 | 5.5 |
| Working pressure | 2.1 to 12 bar | 0.7 to 12 bar |
| Minimum pressure at the farthest nozzle | 2.1 bar | 0.7 bar |
| Discharge angle | 140° | |
| Spacing in the performance table | 3 × 3 m; actual spacing follows the discharge density required for the protected liquid | |
| Connection | 1/2 inch (15NB) BSPT male, NPT male optional | |
| Materials | Body ASTM A351 Gr. CF8M (SS 316), deflector and pin in duplex stainless steel | |
| Weight | Approx. 0.095 kg, natural stainless finish | |
Source: the FIRETECH F226 foam spray nozzle page, where the datasheet can be downloaded.
K-43 or K-79: how to choose
Nozzle flow follows Q = K × √P, with Q in L/min and P in bar. For illustration only (arithmetic from the K-factor, not datasheet figures):
- K-43 at its 2.1 bar minimum: about 62 L/min.
- K-79 at 0.7 bar: about 66 L/min, and at 2.1 bar: about 114 L/min.
In practice:
- K-79 gives more flow at lower pressure, so it suits areas that need a high discharge density or wider nozzle spacing, or networks with limited end pressure.
- K-43 gives less flow per nozzle, so it suits lower densities spread over more nozzles, but it needs at least 2.1 bar at the farthest nozzle.
The final decision comes from the hydraulic calculation: hazard type, exposed area, the discharge density required by the governing code (for example NFPA 16 for foam-water spray systems) and the maximum spacing without dry spots. When ordering, specify K-factor, spray angle, finish, model and end connection.
Where is the F226 used?
Per the product page, the nozzle is used in foam-water deluge and manual spray systems in:
- Chemical process plants; see an example in paint factory fire protection.
- Tanker loading bays and railway gantries.
- Aircraft hangars; see NFPA 409 aircraft hangar fire protection.
- Warehouses.
- Flammable-liquid pumping and metering sheds.
How the F226 works inside a foam system
The nozzle is open, so it does not operate on its own like a closed sprinkler. The sequence in a foam-water deluge system:
- Detection picks up the fire and opens the FIRETECH FX deluge valve; it is compared with Cla-Val in FIRETECH FX vs Cla-Val 134-05.
- Water passes the proportioner with the FIRETECH foam bladder tank to form foam solution at the design ratio; tanks are compared in foam bladder tank comparison.
- All open nozzles on the network discharge together, followed by water for cooling once the concentrate is used.
The full system under NFPA 16 is covered in foam sprinkler systems, and concentrate selection in AFFF foam concentrate in Saudi Arabia.
Common mistakes
- Choosing K-43 without confirming at least 2.1 bar at the farthest nozzle.
- Copying the 3 × 3 m spacing from the performance table instead of calculating the density required for the protected liquid.
- Using a foam concentrate not named in the listing; the datasheet names AFFF and AR-AFFF.
- Ordering without specifying the thread (BSPT or NPT), causing mismatches with site fittings.
Frequently asked questions
What does non-air-aspirating mean?
The nozzle does not mix air into the solution inside its body, so it discharges with a spray pattern similar to water. It is designed for low-expansion foam followed by water.
Is the F226 UL listed?
Yes, per UL Product iQ under Nozzles, Fixed Spray, Foam, file EX27977, model F226.
What is the minimum operating pressure?
0.7 bar for the K-79 and 2.1 bar for the K-43 at the farthest nozzle.
What is the nozzle made of?
An SS 316 body (ASTM A351 CF8M) with a duplex stainless steel deflector and pin.
Can it be used with AR-AFFF for polar solvents?
The datasheet states it is listed for AFFF and AR-AFFF; the difference between them is explained in what is firefighting foam.
Conclusion
The F226 is a UL listed, SS 316 open foam spray nozzle: choose K-79 for more flow at low pressure and K-43 for lower flow with a 2.1 bar minimum, and size it together with the deluge valve and foam tank from the hydraulic calculation.
Designing a foam system for a plant, warehouse or loading bay? Send the drawings, the protected liquid and the area, and the AZEIDK team will prepare the nozzles, deluge valve and foam tank with calculations, supply and installation. Request a quote from AZEIDK
Related guides
- NFPA 10 Guide: Choosing, Placing and Inspecting Extinguishers
- SASO Technical Regulation for Explosive Atmosphere Equipment: Scope, Categories, Marking and Conformity
- Fire Alarm Companies in Jeddah: Comparing Distributors, Consultants and Contractors
- Comprehensive vs Non-Comprehensive Fire and Security Maintenance Contracts: Spare Parts, Emergency Call-Outs and How to Choose