Fire Extinguisher Symbols for Drawings: Sprinkler, Hose Cabinet and Valve Symbols and Extinguisher Layout Plans (NFPA 170)

Fire Extinguisher Symbols for Drawings: Sprinkler, Hose Cabinet and Valve Symbols and Extinguisher Layout Plans (NFPA 170)

Fire extinguisher symbols for drawings, together with sprinkler, hose cabinet and valve symbols, are the shared language between the designer, the contractor, the consultant and the Civil Defense reviewer. Each symbol fixes what an item is and where it goes, and every symbol used on a sheet must appear in the legend. The US reference that standardizes fire safety symbols is NFPA 170, and many design offices in Saudi Arabia build their legends on it. This guide explains, in words and tables, how to read these symbols and how to present a fire extinguisher layout plan that a reviewer can check quickly. If your project needs these sheets prepared, see our shop drawings and coordination service.

Key points

  • NFPA 170 standardizes the safety symbols used on engineering drawings, pre-incident plans and emergency management documents.
  • A symbol that is not in the sheet legend cannot be relied on, however common it is.
  • An extinguisher symbol only fixes a location; agent and size go in a tag beside it or in a schedule.
  • Sprinkler symbols distinguish upright, pendent, sidewall and concealed heads; model data belongs in the sprinkler schedule.
  • The extinguisher layout plan shows locations, types and travel distances, and is checked against NFPA 10 and Civil Defense requirements.
In this article
  1. What is NFPA 170 and why does it matter on fire protection drawings?
  2. Fire extinguisher symbols for drawings: how to read them
  3. Hose cabinet, valve and network device symbols
  4. Fire extinguisher layout plan: what it should contain
  5. Preparing extinguisher and sprinkler plans before submission
  6. Common mistakes in fire fighting drawing symbols
  7. Frequently asked questions
  8. Conclusion

What is NFPA 170 and why does it matter on fire protection drawings?

NFPA 170, Standard for Fire Safety and Emergency Symbols, is published by the National Fire Protection Association. It collects uniform symbols for engineering drawings, pre-incident plans and emergency management, so that an engineer and a fire crew read the same symbol the same way.

In Saudi Arabia, NFPA 170 is a technical reference chosen by the designer or named in the project specification. It does not replace the legend on each sheet. The working rule is simple: follow what the project specification sets, and keep the legend complete and consistent across every sheet. This article does not reproduce the symbol figures published in the standard, which are copyrighted; it describes what distinguishes each symbol and what is written next to it.

Searches for “NFPA 170 PDF” turn up many unofficial copies that may be outdated or incomplete. The authoritative copy is obtained from NFPA (nfpa.org), and that is the version to cite in a submittal or review.

Fire extinguisher symbols for drawings: how to read them

Most offices build the legend in three layers: a base shape for the family (extinguisher, sprinkler, hose cabinet, valve), a mark inside or beside it for the type, and a text tag that links the symbol to an equipment schedule. The sheet stays clean and the full data sits in the schedules.

Fire extinguisher symbol

The extinguisher symbol shows location only unless a tag is added. The agent and capacity are written beside it, and portable, wheeled and cabinet-mounted units are distinguished. The tags below are common examples; your project legend governs.

Extinguisher typeCommon tag on the drawingWhat the schedule states
ABC dry powderDCP or DP with capacityCapacity in kg and rating
Carbon dioxideCO2 with capacityCapacity, proximity to electrical panels and equipment
FoamAFFF or FOAM with capacityCapacity in litres
Wet chemical (kitchens)WC or KCapacity and position relative to cooking equipment
Wheeled unitSame tag marked WheeledCapacity and route for moving it
Extinguisher in a cabinetExtinguisher symbol within a cabinet outline, or FEC tagCabinet type: surface or recessed

For the extinguisher types themselves, see our fire extinguisher selection guide for facilities.

Fire sprinkler symbol

On most drawings a sprinkler is a small circle on the branch line. Its inner mark or an added indicator distinguishes upright, pendent, sidewall (with a throw direction arrow), concealed and dry heads. On alteration projects, existing heads are drawn differently from new and relocated ones.

Detailed data does not ride on the symbol. K-factor, temperature rating, response type, model and SIN belong in the sprinkler schedule. For the differences between head types, see upright vs pendent sprinklers and sprinkler head types and K-factor.

For anyone looking for a sprinkler symbol for CAD: keep symbols as named blocks in the office template, one block and one layer per type. Counting heads and extracting quantities becomes simple, and two similar symbols are not mixed on the same sheet.

Hose cabinet, valve and network device symbols

A fire fighting drawing shows more than extinguishers and sprinklers. The table lists the other items that usually appear and what must accompany each symbol.

ItemCommon tagWhat the schedule or notes must show
Fire hose cabinetFHC or FHRHose diameter and length, cabinet type and contents
OS&Y gate valveValve symbol with type tagSize, and whether it is supervised
Butterfly valveValve symbol with BFV tagSize and indicator type
Check valveSymbol with flow arrowSize and direction
Alarm valve or zone control valveACV or ZCVSize and the zone it feeds
Flow switch and tamper switchFS and TSZone number and fire alarm panel connection
Fire department connectionFDCNumber of inlets and position on the facade
Fire pumpFP, or JP for the jockey pumpFlow and pressure from the pump schedule

For hose cabinet contents, see fire hose cabinet types and sizes.

Fire extinguisher layout plan: what it should contain

The fire extinguisher layout plan is a separate sheet or a layer of the fire fighting sheet. Its job is to prove that every point on the floor lies within the permitted travel distance of a suitable extinguisher. A good plan includes:

  • A plan of each floor with room names and uses, since use drives the hazard level.
  • Each extinguisher symbol tagged with agent and capacity.
  • The hazard level of each area (light, ordinary or extra).
  • Circles or routes showing travel distance from each extinguisher.
  • Hose cabinet locations and extinguisher signs.
  • A summary table of extinguisher numbers by type and size per floor.

Travel distance is the actual walking distance to the extinguisher, not a straight line through walls. For Class A fires NFPA 10 sets a maximum travel distance of 75 ft (22.9 m), the same figure used in US OSHA regulations; for Class B it depends on the extinguisher rating and liquid depth. Circles on the plan are therefore a quick check only, and enclosed corridors and single-entry rooms are verified along the real route.

Quantities, areas and mounting heights are covered in our NFPA 10 extinguisher guide, and the fire extinguisher calculator gives a first estimate. The edition and requirements that apply to your facility are set by the Saudi Fire Code SBC 801 and Civil Defense for the occupancy.

Preparing extinguisher and sprinkler plans before submission

  1. A legend on every sheet, or a dedicated legend sheet referenced by number.
  2. North arrow, scale, sheet title, revision number and date.
  3. Clear distinction between existing, new and removed items on alteration works.
  4. Drawing on the latest architectural background, especially after fit-out and ceiling changes.
  5. Tags that match the equipment schedule and the material submittal.
  6. Coordination with lighting, HVAC and doors so heads and extinguishers are not obstructed.

For the full content of shop drawings and their approval path, see fire protection shop drawings. If your sheets are ready and need a check before submission, that is the scope of our drawings and specifications review.

Common mistakes in fire fighting drawing symbols

  • Symbols used on the sheet but missing from the legend, or the reverse.
  • One symbol used for two different types, such as pendent and concealed heads.
  • Extinguishers without agent or capacity tags, so the supplier cannot tell what to supply.
  • Symbols from different offices on the same project after contractor files are merged.
  • Travel distance circles drawn through walls without checking the actual route.
  • A summary table that does not match the number of symbols on the sheet.

Frequently asked questions

What is the fire extinguisher symbol on drawings?

It is the symbol the project legend assigns to an extinguisher location, tagged with agent and capacity such as DCP 6 kg or CO2. The US reference for standard fire safety symbols is NFPA 170.

Is NFPA 170 mandatory in Saudi Arabia?

It is a technical reference adopted by the designer or the specification. What binds a project is the Saudi Building Code, Civil Defense and the contract; what matters most is a clear, consistent legend.

Where can I get the NFPA 170 PDF?

Obtain the official copy from NFPA. Do not rely on files from unofficial sites in a submittal, as they may be outdated or incomplete.

How do I tell upright and pendent sprinkler symbols apart?

Each project marks them differently and explains it in the legend. The sprinkler schedule, with model and SIN for each type, is the final check.

What does a fire extinguisher layout plan include?

Floor plans, extinguisher locations with type and size, the hazard level of each area, travel distances and a summary count.

Are travel distance circles on the plan enough?

They are a quick check. Travel distance is measured along the actual walking route, so corridors and enclosed rooms are checked one by one.

Conclusion

Reading fire extinguisher and sprinkler symbols starts with the legend, then the tag beside each symbol, then the equipment schedule. NFPA 170 gives a common symbol language, but acceptance depends on consistency with the project specification and Civil Defense requirements, and on an extinguisher layout plan that proves travel distances along real routes.

Need fire fighting drawings and an extinguisher layout plan for your project? Send the architectural drawings and room uses, and the AZEIDK team will prepare the shop drawings and legend with you. Contact the AZEIDK team

References: NFPA 170 page on the official NFPA website (https://www.nfpa.org/product/nfpa-170-standard/p0170code); US OSHA 29 CFR 1910.157, Portable fire extinguishers, paragraphs (d)(2) and (d)(4) (https://www.osha.gov/laws-regs/regulations/standardnumber/1910/1910.157); AZEIDK NFPA 10 guide (https://azeidkgroup.com/en/sa/media-center/nfpa-10-portable-fire-extinguishers-guide/).
Share this article