Fire extinguisher discharge time is very short: a 6 kg dry powder extinguisher empties in about 10 to 15 seconds, a small 1 kg unit in about 6 to 10 seconds, and a 6 kg CO2 extinguisher in about 9 seconds or a little more. These figures come from the official datasheets of extinguishers available from AZEIDK. In practice there is no time for test bursts or spraying from far away: get within the stated range and aim at the base of the fire from the first squeeze.
This guide collects discharge time and range by type and size from the datasheets, explains what they mean when you use the extinguisher, and when you need a bigger or wheeled unit.
Key points
- 6 kg dry powder: 6.5 to 8 m range and 10 to 15 seconds discharge, depending on the model.
- 1 kg dry powder: 2 to 5 m range and 6 to 10 seconds.
- 6 kg CO2: about 4 m range and 9 seconds or more, so you must get close to the fire.
- 50 kg wheeled powder: 42 seconds; 10 kg wheeled CO2: 22 seconds.
- Any squeeze, however short, means the extinguisher must be recharged after use.
In this article
- How long does a fire extinguisher last when spraying? Datasheet table
- What a short discharge time means in use
- Why does a CO2 extinguisher have a shorter range?
- When do you need a bigger or wheeled extinguisher?
- Automatic extinguishers: how long do they discharge?
- Can you stop an extinguisher and use it again later?
- Choosing by location
- Frequently asked questions
How long does a fire extinguisher last when spraying? Datasheet table
| Extinguisher | Discharge range | Discharge time |
|---|---|---|
| Falcon Gold 1 kg powder | 5 m | 6 s |
| Falcon Gold 6 kg powder | 8 m | 15 s |
| Falcon Gold 50 kg wheeled powder | 8 m, with 5 m hose | 42 s |
| Falcon Gold 6 kg CO2 | 4 m | 9 s or more |
| Falcon Gold 10 kg wheeled CO2 | 3 m, with 3 m hose | 22 s |
| SFFECO PD1 1 kg ABC powder | 2 m | 6 to 10 s |
| SFFECO PD3 3 kg ABC powder | 3 m | 6 to 12 s |
| SFFECO PD6 6 kg ABC powder | 6.5 m | 10 to 14 s |
| SFFECO PD12 12 kg ABC powder | 8.5 m | 14 to 22 s |
Sources: Falcon Gold product pages on the AZEIDK site, and the official SFFECO portable powder datasheet for stored pressure models. Figures vary between manufacturers and models, so always check the datasheet of the unit you buy.
What a short discharge time means in use
- Get close before you squeeze: start spraying from within the stated range. Spraying from further away wastes part of the few seconds you have.
- Aim at the base of the fire: not at the flames, and sweep side to side as in how to use a fire extinguisher step by step.
- Do not test the extinguisher before a fire: one test squeeze loses contents and means the unit needs recharging.
- Stay safe: keep your back to the exit and withdraw if the fire is not out when the extinguisher is empty.
The Falcon Gold 6 kg CO2 product page states a 4 m range and that the user should get close to the fire before operating it. More in the CO2 extinguisher guide.
Why does a CO2 extinguisher have a shorter range?
CO2 is stored at high pressure, 70 bar operating pressure in the Falcon Gold 6 kg unit, and leaves as a cold gas that disperses quickly in air. That is why its range is shorter than powder and the user has to get closer. Powder is expelled at a lower pressure, 15 bar in the Falcon Gold 6 kg unit, but carries further because it is a fine solid.
When do you need a bigger or wheeled extinguisher?
If a hazard needs more than 15 seconds of firefighting, such as a fuel store, a large workshop or a generator yard, one portable unit is not enough. That is where a wheeled extinguisher comes in: the 50 kg powder unit gives 42 seconds and the 10 kg wheeled CO2 unit gives 22 seconds.
The number and spacing of extinguishers in a building are set by the hazard and travel distance under the NFPA 10 guide and Civil Defense requirements, not by discharge time. But discharge time is a reminder that an extinguisher is for a fire in its early stage; a larger fire needs a fixed system from fire fighting systems.
Automatic extinguishers: how long do they discharge?
A ceiling-mounted automatic unit operates on its own when the temperature rises. The Falcon Gold 6 kg automatic FM-200 extinguisher releases when its brass sprinkler valve reaches 68 °C, with a 16 second discharge time and 8 m range according to the product page. It suits small rooms such as electrical rooms and does not replace portable extinguishers.
Can you stop an extinguisher and use it again later?
Most stored pressure extinguishers stop when you release the lever, so you can spray in bursts during the same fire. After the fire, do not put the extinguisher back: the pressure has dropped and the valve may leak. Send it for recharging as described in fire extinguisher maintenance and refilling.
Choosing by location
In a car, a small unit for a fire in its early stage is enough, as covered in the car fire extinguisher guide. Shops and offices commonly use a 6 kg powder unit plus a CO2 unit near electrical panels, and large warehouses and workshops add wheeled units. AZEIDK is the exclusive agent for Falcon Gold extinguishers, and SFFECO extinguishers are also available from AZEIDK, with technical supply, installation and maintenance.
Frequently asked questions
How many seconds does a 6 kg fire extinguisher last?
A 6 kg dry powder extinguisher empties in roughly 10 to 15 seconds depending on the model: 15 seconds for Falcon Gold and 10 to 14 seconds for the SFFECO PD6.
How far does a fire extinguisher spray?
A 6 kg powder unit reaches 6.5 to 8 m, a 6 kg CO2 unit about 4 m, and a small 1 kg unit 2 to 5 m depending on the model.
How long does a 1 kg car extinguisher last?
About 6 to 10 seconds according to the datasheets, so it is only for a small fire in its early stage.
Should I test the extinguisher after buying it?
No. A test squeeze loses contents and pressure. Check the gauge, label and seal instead.
Why is the range of a CO2 extinguisher shorter?
Because the gas disperses quickly in air after it leaves the horn, so you have to get closer to the fire than with powder.
Need extinguishers of the right size for your shop or warehouse? Send AZEIDK your activity and floor area, and we will propose the types and sizes with their datasheets. Request a quote from AZEIDK
Related guides
- Safety and Fire Fighting Company in Taif: Preparing Hotels, Rest Houses and Shops Before the Civil Defense Inspection
- Fire Systems Maintenance Companies in Taif: Alarm and Fire Fighting Maintenance Contracts for Hotels, Rest Houses and Commercial Buildings
- Sprinkler Test and Drain Valve: How It Works, Choosing the Test Orifice, and the Giacomini A61
- ZKTeco Intercom: VEX-B21L vs VT10-B21L-02 vs VT07-B50L, and Which Fits a Villa or Apartment Building