Low Current Systems Handover Documents: As-Built Drawings, IP Address Table, Passwords and Test Reports

Low Current Systems Handover Documents: As-Built Drawings, IP Address Table, Passwords and Test Reports

Low current systems handover does not end when the cameras record and the doors open with a card. The owner is really taking over a network of devices, each with an IP address, an admin account, a password and saved settings. If that information is not handed over in an organised file, every later repair or extension depends on the contractor who installed the system. This article explains what the handover file for CCTV, networks, access control, PA and intercom should contain, and how an owner can check it before signing.

AZEIDK delivers low current systems from design to handover and offers documentation and final handover to collect drawings, test results and manuals in one file.

Key points

  • The handover file has four parts: as-built drawings, device and address tables, configuration backups and test results.
  • Passwords go to a named person in a sealed envelope or protected file, never inside the general file.
  • The IP address table links every device to its location, switch port and cable number on the patch panel.
  • Temporary contractor accounts are deleted or disabled on handover day, and an admin account is created for the owner.
  • Fire systems have their own handover documents; this file covers low current systems.
In this article
  1. Why low current handover is different
  2. What the handover file contains
  3. The IP address table
  4. Passwords and accounts
  5. How the owner checks the file before signing
  6. Common mistakes in handover files
  7. FAQ

Why low current handover is different

For fire systems the owner receives drawings, test results and manuals, as covered in fire systems handover documents. Low current systems add a layer that never appears on a drawing: software configuration. The recorder holds the recording schedule, retention and user rights; the switch holds VLANs and PoE settings; the access control panel holds the card database and time schedules. If these settings are lost, or the owner does not know one device password, the device may have to be factory reset and programmed again.

What the handover file contains

PartContentReviewed by
As-built drawingsActual positions of cameras, readers, speakers and data points, cable routes, telecom rooms and risersConsultant or owner’s engineer
Device scheduleModel, serial number, firmware version and location of every deviceIT or security lead
IP address tableAddress, subnet, gateway, VLAN, switch port and cable number for each deviceNetwork administrator
Cable schedule and labelsEach cable number at both ends and on the patch panel, with its test resultNetwork administrator
Configuration backupsBackup files from recorders, switches, access control panels and the PBXIT team
Test resultsReports for cameras, recording, doors, fire alarm door release and PA intelligibilityConsultant and owner
Manuals and warrantiesManufacturer manuals, warranty certificates and a proposed maintenance scheduleFacility management

The IP address table

A good table answers one question fast: if camera 27 stops, where is it, which switch and port feed it, and what is its address? Each row holds the device name as shown in the VMS, its floor and room, IP address, switch and port, and the cable number matching the patch panel label. It is handed over in an editable format, not just a PDF, because the owner will add to it at every extension. Where the network is split for cameras, doors and phones as described in ELV network VLAN design, the VLAN of each device is listed.

Passwords and accounts

  • Every recorder, controller and managed switch has at least one admin account in the owner’s name.
  • Temporary technician accounts are deleted or disabled, and any password used during installation is changed.
  • Passwords are not written in the address table or the printed manual; they go to a person the owner names in writing.
  • Cloud accounts for mobile viewing are registered with a company email, not a technician’s.

These steps reduce the risks covered in CCTV hacking protection and stop the contractor keeping access after the contract ends.

How the owner checks the file before signing

A practical sample is enough: pick three cameras, two doors and one data point and trace them from drawing to table to site. If the sample matches, the file is usually sound. Then log in with the owner account on the recorder and the access controller, and confirm the backup files open. Open items go on the pre-handover snag list with a closing date for each.

Common mistakes in handover files

  • Design drawings handed over instead of as-built drawings.
  • Address table missing devices added through variation orders.
  • Patch panel labels that do not match the labels at the device.
  • A configuration backup taken before the last change made during testing.
  • The viewing app registered to a technician’s personal account.

FAQ

Can the owner ask for every device password?

Yes. The devices belong to the facility after handover, and this should be a clear clause in the supply and installation contract.

When is the final configuration backup taken?

After acceptance tests and their corrections. The backup is dated so the owner knows it is the latest.

Is an electronic file enough?

It is easier to update. A short printed copy of the address and cable tables in the telecom room still helps the technician on site.

Who updates the file after handover?

The maintenance provider. The low current maintenance contract should require every device or address change to be recorded.

Taking over a low current project soon? AZEIDK can review the handover file and check it against the site before you sign. Contact AZEIDK

References: TIA-606 (administration and labelling of telecommunications infrastructure), manufacturer manuals for recorders and access controllers.
Share this article
This site is registered on wpml.org as a development site. Switch to a production site key to remove this banner.