INERGEN vs SAPPHIRE is a common question when a data center, control room or archive needs a gas suppression system. Both are ANSUL total flooding systems by Johnson Controls, both are designed to NFPA 2001, and both suit Class A, B and C hazards where an electrically non-conductive agent is needed. The real difference is the agent: INERGEN is an inert gas blend that lowers the oxygen level, while SAPPHIRE uses Novec 1230 fluid (FK-5-1-12). Every figure below comes from the official ANSUL datasheets attached to the two product pages.
AZEIDK supplies both systems as part of its special fire suppression systems work in Saudi Arabia. For a wider comparison of all clean agents, including FM-200, see the clean agent comparison guide.
Quick answer
- Choose ANSUL INERGEN 200-bar when you want an agent made only of gases found in the atmosphere, with zero ozone depletion and no contribution to global warming, and the site has space for high pressure cylinders.
- Choose ANSUL SAPPHIRE when you prefer a liquid stored agent, with five container sizes from 34 L to 180 L and fill quantities in 0.5 kg steps.
- With either system, the room must hold the agent: plan a room integrity test before handover.
How each agent puts out a fire
INERGEN is a mix of 52% nitrogen, 40% argon and 8% carbon dioxide. On discharge it brings the oxygen in the room down from 21% to about 12.5% and raises carbon dioxide to about 3%. Most ordinary combustibles stop burning below 15% oxygen, while the small rise in carbon dioxide makes people breathe more deeply, so the datasheet states that a person can still breathe in the reduced oxygen atmosphere. FM tests cited by ANSUL show that INERGEN at 40% to 50% design concentration inerted propane/air and methane/air mixtures.
SAPPHIRE uses Novec 1230 fluid, listed as FK-5-1-12 in NFPA 2001 and ISO 14520. It is a clear, odourless liquid, super-pressurised with nitrogen in the container, that turns to gas on discharge and leaves no residue on electronics. The datasheet states that exposure at design concentrations up to 10% (NOAEL) is not hazardous to health. Both datasheets still advise that people leave the protected area quickly.
Side by side from the datasheets
| Item | INERGEN 200-bar | SAPPHIRE |
|---|---|---|
| Agent | Nitrogen, argon and CO2 (inert gas) | Novec 1230 fluid (FK-5-1-12) |
| Storage | Gas at 200 bar at 21 °C | Liquid, super-pressurised with nitrogen |
| Containers | One size, red steel, DOT 3AA3000 or ISO 9089-1 minimum | Five sizes of weld-free container: 34, 80, 120, 140 and 180 L |
| Environment | Zero ozone depletion, no global warming contribution | ODP 0.0, GWP 1.0, atmospheric lifetime five days |
| Listings stated | System UL and ULC listed, FM approved | System UL listed |
| Nozzles | 360° or 180° pattern | Six sizes, 360° or 180° pattern |
| Ambient range | 0 to 54 °C (control systems 0 to 49 °C, indoor) | Not stated in this datasheet |
Piping and installation differences
Because INERGEN is stored as a high pressure gas, the design needs a pressure reducer in the distribution piping. It contains a stainless steel orifice plate drilled to the size set by the hydraulic calculation, in nine sizes from 1/2 in. to 4 in. NPT. Manifold piping must withstand at least 3000 psi (206.9 bar), and a manifold is used when three or more containers are needed. Selector valves let one bank of containers protect several hazards.
SAPPHIRE is designed with a UL listed hydraulic flow calculation program that predicts the two-phase flow of Novec 1230 and nitrogen through the pipe network and sets pipe sizes, nozzle drill sizes and discharge time. On multi-container systems one 24 VDC electric actuator sits on the master container and the others open pneumatically through 1/4 in. stainless steel hose. For agent quantity, see Novec 1230 quantity calculation.
Both datasheets require installation by personnel trained by the manufacturer, following the ANSUL design and maintenance manual and NFPA 2001.
Typical rooms for each system
The INERGEN datasheet lists computer rooms, subfloors, tape storage, telecommunication and switchgear rooms, museums and libraries. The SAPPHIRE datasheet lists data processing centers, tape storage, vaults, telecommunication sites including cellular sites, offshore platforms and marine engine rooms. Both overlap in the rooms most Saudi projects ask about, such as data centers, control rooms and electrical rooms. In practice the choice often comes down to the space available for cylinders, the environmental policy of the owner and the design calculation for the specific room.
FAQ
Is INERGEN safe in a normally occupied room?
The datasheet states that INERGEN is suitable for normally occupied hazards and that the gas mix allows a person to breathe in the reduced oxygen atmosphere. Evacuation on alarm is still required.
Is SAPPHIRE the same as Novec 1230?
SAPPHIRE is the ANSUL system name. The agent inside it is Novec 1230 fluid, known in the standards as FK-5-1-12. Cost drivers for this agent are covered in Novec 1230 system cost factors.
What do you need to request a quotation?
Send the room dimensions, any raised floor or ceiling void, the room use and the preferred agent through the contact page. You can also see all ANSUL products on the ANSUL brand page.