A vertical turbine fire pump has its impeller assembly submerged in the water source itself, with the driver and discharge head mounted above on a base over the water. It is chosen when the water level is below the pump: a ground tank under the pump room floor, a well or a wet pit. Horizontal pumps do not suit this situation. In Saudi Arabia AZEIDK supplies the UL-listed WATEX vertical turbine fire pump and the Jack Pump VTP series, both in our fire pumps range.
For a comparison of fire pump types (electric, diesel, jockey, end suction, split case and vertical turbine), see our full guide.
This article covers what is specific to this pump type: when you need it, how column length and number of stages are set, and what changes in the pump room and in maintenance compared with a horizontal pump.
Key points
- The usual choice when the water level is below the pump, which a horizontal pump working on positive suction cannot handle.
- Multistage: each stage is an impeller and bowl, and pressure rises with the number of stages.
- Per AZEIDK product pages: Jack Pump VTP covers 50 to 5,000 gpm; WATEX covers 50 to 1,250 gpm up to 420 psi under UL certificate EX27224.
- Driven by a vertical electric motor, or a diesel engine through a right angle gear drive.
- The room needs headroom and a roof opening to lift the column and bowls for service.
In this article
- What is a vertical turbine fire pump and how does it differ from a horizontal pump?
- When does your project need a vertical turbine fire pump?
- How are column length and number of stages set?
- Vertical turbine fire pump models available from AZEIDK
- Driver: vertical electric motor or diesel with a gear drive?
- Pump room and maintenance
- Frequently asked questions
- Summary
What is a vertical turbine fire pump and how does it differ from a horizontal pump?
A horizontal pump, end suction or split case, waits for water to arrive at its suction flange under positive pressure. A vertical turbine pump goes to the water. The bowl and impeller assembly hangs inside the tank or well, with a stainless steel strainer at the bottom according to the Jack Pump VTP product page, and water rises through a vertical column to the discharge head above the base.
Because the impellers are always submerged, the pump needs no priming and does not rely on suction pressure. That is why it is the usual choice for deep ground tanks in factories and compounds, and for wells at sites far from a water main.
| Item | Horizontal pump (end suction or split case) | Vertical turbine fire pump |
|---|---|---|
| Water position | Above pump centerline or under positive pressure | Below the pump: ground tank, well or wet pit |
| Pressure build-up | Usually a single impeller | Several stages, each an impeller and bowl |
| Driver | Electric or diesel on the same baseplate | Vertical electric motor, or diesel with right angle gear |
| Space | Larger floor area | Smaller floor area, more height |
| Main maintenance | Open casing or pull rotating assembly | Lift column and bowls out of the tank |
When does your project need a vertical turbine fire pump?
The first question is not flow but water level. If the lowest water level in the tank stays above the centerline of a horizontal pump, a horizontal pump is possible and types are compared on flow and pressure. If the lowest level is below the pump centerline, a vertical turbine pump is the usual solution.
Common Saudi situations that lead to this choice:
- A concrete ground fire water tank under the pump room, a frequent layout in factories, warehouses and residential compounds.
- Remote industrial or agricultural sites relying on a well.
- A wet pit or open basin fed from another source.
The decision is settled during engineering design and calculations, because the lowest water level feeds straight into the pressure the pump must produce. For a wider map of pump types see WATEX fire pump types.
How are column length and number of stages set?
A vertical turbine pump builds pressure in stages. Each stage adds part of the head, and the number of stages is chosen to reach the required pressure at the duty point. That is why the Jack Pump VTP page states that pressure varies with the number of stages.
Column length follows from the distance between the pump base and the lowest operating water level, with enough submergence of the bowl assembly below that level. Two points the designer must check:
- Required submergence: the manufacturer sets the minimum bowl submergence at the pump’s highest flow. Ask for it in writing with the model documents.
- The real lowest level: in a tank, the level after the design volume is used; in a well, including drawdown while pumping. Designing on the static level alone is a common mistake.
The height between the lowest water level and the discharge head adds to the required pressure, since the pump lifts that height before it starts feeding the system. Duty point calculation is covered in our NFPA 20 guide.
Vertical turbine fire pump models available from AZEIDK
WATEX vertical turbine
Holds UL certificate EX27224, which names models 100LB, 150LB and 150WV, covering 50 to 1,250 gpm and up to 420 psi per the catalog. The WATEX catalog also lists models such as 150 WV-50, 200 WV-60 and 250 WV-60 that are not named in the published certificate, so confirm their listing from the datasheet before ordering. Details are in our WATEX fire pumps guide.
Jack Pump VTP series
The product page describes it as UL listed per the catalog, designed to UL 448 and NFPA requirements, covering 50 to 5,000 gpm, multistage, with discharge flanges from 2.5 to 12 inches. Example models run from VT80-145 to VT275-430; rely on each model’s performance and dimension tables and ask the supplier for the document linking the offered model to its listing.
Driver: vertical electric motor or diesel with a gear drive?
On the electric version a vertical motor sits directly on the discharge head. On the diesel version the engine stays horizontal and drives the vertical shaft through a right angle gear. That means more floor space beside the pump, an extra alignment between engine and gear drive, and gear oil checks in the maintenance program.
For causes of high or unstable pressure see fire pump faults, and for the brand comparison see Jack Pump or WATEX.
Pump room and maintenance
A vertical turbine pump uses less floor area but needs height. To remove the column and bowl assembly the rotating parts are lifted vertically, so leave a roof hatch or a hoist path above the pump. Coordinate this early with the architect and structural engineer; adding it after the slab is cast is expensive. Room requirements are in our fire pump room article.
Periodic testing follows NFPA 25 like other pumps: churn runs and an annual test at zero, 100% and 150% of rated flow. Per InspectPoint’s summary of the 2023 edition, electric pumps run monthly for 10 minutes and move to weekly in cases that include vertical turbine drivers. These are NFPA 25 reference values; in Saudi Arabia the binding rules are SBC 801 and Civil Defense requirements. Watch the tank or well level during the annual test: a larger drop than expected reveals a submergence problem before a fire does.
Frequently asked questions
When should I use a vertical turbine fire pump instead of a horizontal one?
When the lowest water level is below the pump, such as a ground tank under the room or a well. A horizontal pump needs positive suction and does not suit this case.
Does a vertical turbine pump need priming?
No. When installed correctly the bowls and impellers are permanently submerged.
What capacities does AZEIDK offer in vertical turbine fire pumps?
Per the product pages, Jack Pump VTP covers 50 to 5,000 gpm and WATEX 50 to 1,250 gpm up to 420 psi. The model and number of stages follow the duty point.
Can a vertical turbine pump run on a diesel engine?
Yes, through a right angle gear drive that turns the horizontal engine output to the vertical shaft, as the Jack Pump VTP page states.
What is the most common design mistake?
Setting column length and pressure from the static water level instead of the lowest operating level, so the pump loses submergence at high flow.
Is the WATEX vertical turbine pump UL listed?
Yes, under UL certificate EX27224 for the models it names. Extra catalog models should be checked before ordering.
Summary
A vertical turbine fire pump is the answer when water sits below the pump. It works well when the lowest operating level is calculated correctly, submergence is confirmed by the manufacturer, the stage count matches the required pressure and the room has the height to lift the column. Reviewing this during technical selection before supply saves many site changes, especially in industrial facilities.
Related reading: Split Case Fire Pump, High-Rise Building Fire Pumps and Hazen-Williams Formula for Fire Pipe Friction Loss.
Ground tank or well as your source? Send us the lowest water level, the required flow and pressure and the room layout, and we will send the matching WATEX or Jack Pump vertical turbine model with its datasheet. Contact the AZEIDK team
Related guides
- Fire System Supply and Installation Contract Template: Clauses to Settle Before Signing (Scope, Drawings, Approvals, Testing and Handover, Warranty)
- School and University Gates: Turnstiles, Face or Card Attendance and Dismissal Planning
- FM-200 Fire Suppression System: Design, Safety and Kigali Status
- CCTV Installation Tenders in Saudi Arabia: Specifications, Scope of Work and BOQ