Split Case Fire Pump: When to Choose a Horizontal Split Case and What to Check on the Datasheet

Split Case Fire Pump: When to Choose a Horizontal Split Case and What to Check on the Datasheet

A split case fire pump (horizontal split case) is a centrifugal pump whose casing splits horizontally along the shaft centerline, with water entering a double-suction impeller from both sides. It is the usual choice when the required flow goes beyond what an end suction pump covers and water reaches the suction under positive pressure from a tank or main. In Saudi Arabia AZEIDK supplies three series of this type: the SFFECO SFP series, the UL-listed WATEX WS split case pump and the Jack Pump MSC series, all in our fire pumps range.

For a comparison of fire pump types (electric, diesel, jockey, end suction, split case and vertical turbine), see our full guide.

This article explains when a split case pump is the right choice, what to check on the datasheet, and what NFPA 20 requires in the suction piping around it. Most problems with this pump type start in the pump room, not at the factory.

Key points

  • The casing splits horizontally, so the top half lifts off and the rotating assembly comes out without disturbing suction and discharge piping or the driver.
  • The double-suction impeller balances axial thrust on the bearings.
  • Per AZEIDK product pages: SFFECO SFP covers 150 to 3,500 gpm, Jack Pump MSC 300 to 8,000 gpm and WATEX WS 300 to 2,000 gpm.
  • It needs positive suction. Where the water level is below the pump, a vertical turbine pump is the usual answer.
  • Any elbow or tee in a plane parallel to the pump shaft must sit at least 10 pipe diameters from the suction flange.
In this article
  1. What is a split case fire pump and how does it work?
  2. When should you choose a split case fire pump over an end suction pump?
  3. Split case fire pump models available from AZEIDK
  4. Suction piping for a split case pump: what NFPA 20 requires
  5. Foundation and alignment in the pump room
  6. Maintaining and testing a split case pump
  7. What to check on the datasheet before approval
  8. Frequently asked questions
  9. Summary

What is a split case fire pump and how does it work?

In an end suction pump water enters at the front, along the shaft axis. In a split case fire pump the casing guides water to both eyes of the impeller at once. This double-suction design roughly balances the axial forces. The Jack Pump MSC product page notes that the short bearing span helps reduce vibration.

The feature maintenance crews value most is how the pump opens. The upper casing half is unbolted and lifted, and the complete rotating assembly (shaft, impeller, bearings and wear rings) is removed without disconnecting suction and discharge piping or moving the driver. Downtime is shorter and alignment is preserved.

The product page also states that MSC rotation can be reversed using identical parts, so suction can be on the left or right to suit the room layout. This is specified at order stage, not after delivery.

When should you choose a split case fire pump over an end suction pump?

The decision starts with the duty point from the hydraulic calculation, then the water source and room space. The figures below are those published on AZEIDK product pages:

ItemEnd suctionSplit case
Jack PumpVES: 50 to 1,000 gpm, 84 to 230 psiMSC: 300 to 8,000 gpm, 82 to 369 psi
WATEXWE: 25 to 1,000 gpm, up to 530 psiWS: 300 to 2,000 gpm, up to 420 psi
Impeller inletSingle sideBoth sides
Main maintenance accessBack pull-outLift the upper casing half
FootprintShorter, lighter baseLonger, heavier base
Water sourcePositive suctionPositive suction

Between roughly 300 and 1,000 gpm both types are possible. The choice then comes down to efficiency at the duty point on the curve and what the project specification and consultant prefer. Above that range, the split case pump is the normal choice for large flows in factories, warehouses and foam systems.

If the tank is below the pump centerline or the source is a well, a horizontal pump is not suitable and the usual choice is a vertical turbine pump. A horizontal pump is selected for positive suction, not for lifting water from a level below it.

Split case fire pump models available from AZEIDK

WATEX WS series

The series holds UL certificate EX27018 to UL 448 for stationary fire pumps. The certificate names WS 80-270, WS 100-310, WS 100-360, WS 125-290, WS 125-360 and WS 150-460. The WATEX catalog also lists WS 150-460C, which is not named in the published certificate, so confirm its listing from the datasheet before ordering. Full details are in our WATEX fire pumps guide.

Jack Pump MSC series

The product page describes it as UL listed per the catalog, designed to UL 448 and NFPA requirements, with electric or diesel drive. Example models include MSC5-80-250; check each model’s performance and dimension tables. For a brand comparison see Jack Pump or WATEX.

SFFECO SFP series

The SFFECO SFP horizontal split case fire pumps page lists models from SFP150 to SFP3500, rated 150 to 3,500 gpm with maximum working pressure from 220 to 410 psi, electric or diesel driven, and states UL Listed and FM Approved. Confirm the listing of the exact model at its speed on the datasheet before approval.

AZEIDK supplies fire pumps from SFFECO, WATEX and Jack Pump. When a project specification calls for another brand, AZEIDK’s supply team works on sourcing it to the required specification and approvals.

Suction piping for a split case pump: what NFPA 20 requires

A double-suction impeller needs balanced flow on both sides. Consulting-Specifying Engineer summarizes the NFPA 20 suction piping rules as follows:

  • Ten-diameter rule: where the centerline plane of an elbow or tee is parallel to a horizontal split case pump shaft, it must be at least 10 pipe diameters from the suction flange. There is no distance limit when the plane is perpendicular to the shaft.
  • Velocity: no more than 15 ft/s (4.57 m/s) within 10 pipe diameters of the suction flange.
  • Suction pressure: at 150% of rated flow, pressure at the suction flange must not fall below minus 3 psi.
  • Reducers: size changes use eccentric tapered reducers, installed to avoid air pockets.
  • Valves: check valves and backflow preventers at least 10 pipe diameters from the suction flange, and no suction valve other than an OS&Y gate valve within 50 ft of the pump.

These points come from the magazine’s summary of NFPA 20. The edition adopted for your project is the final reference. These are NFPA 20 reference values; in Saudi Arabia the binding rules are the Saudi Fire Protection Code SBC 801, Civil Defense requirements and the edition named in the project specification. Accessories such as vortex plates and flow meters are covered in our NFPA 20 guide.

Foundation and alignment in the pump room

Consulting-Specifying Engineer notes that horizontal split case pumps must be mounted on a concrete housekeeping pad. Because pump and driver share a long baseplate, coupling alignment is checked after anchoring and again after the piping is connected, since unsupported pipe weight is enough to pull it out. Piping is carried on its own supports, not on the pump casing. Room requirements such as ventilation, drainage and lighting are in our fire pump room article.

Maintaining and testing a split case pump

Inspection and testing follow NFPA 25. Per InspectPoint’s summary of the 2023 edition, diesel pumps run weekly for at least 30 minutes and electric pumps monthly for at least 10 minutes, with some cases, such as high-rise service, moving electric pumps to weekly runs. The annual test flows the pump at churn, 100% and 150% of rated capacity, and results are compared with the original acceptance test curve.

Specific to split case pumps: check packing or mechanical seals on both sides of the shaft, watch both bearing temperatures, and inspect wear rings whenever the casing is opened. Routine steps are in electric fire pump maintenance and fault causes in fire pump faults and troubleshooting.

What to check on the datasheet before approval

  • The exact model at the exact speed is listed, not just the series. See how to check UL and FM approval.
  • Rated flow and pressure, and where the duty point sits on the curve.
  • Maximum casing working pressure against churn pressure plus maximum suction pressure.
  • Rotation direction and suction side to match the room layout.
  • Flange standard and sizes, seal type and impeller material.
  • Driver type (electric or diesel) and power at 150% flow.

Frequently asked questions

What is the difference between a split case and an end suction fire pump?

A split case pump has a horizontally split casing and a double-suction impeller and covers higher flows. An end suction pump takes water from one side, is more compact and suits flows up to about 1,000 gpm.

Can a split case pump draw from a tank below the pump?

No. A horizontal split case pump works with positive suction. Where the water level is below the pump, the usual choice is a vertical turbine pump.

What capacities does AZEIDK offer in split case pumps?

Per the product pages, SFFECO SFP covers 150 to 3,500 gpm, Jack Pump MSC 300 to 8,000 gpm and WATEX WS 300 to 2,000 gpm. The model is chosen from the duty point and curve, not the series range.

Is the WATEX WS pump UL listed?

Yes. The series holds UL certificate EX27018 to UL 448, which names the models. Any model not named there should be checked before ordering.

Why does NFPA 20 restrict elbows near a split case pump suction?

An elbow parallel to the shaft feeds the two impeller eyes unevenly, raising bearing load and vibration. That is why it must be at least 10 pipe diameters from the suction flange.

Can a split case pump be serviced without removing the piping?

Yes, that is its main advantage. The upper casing half lifts off and the rotating assembly comes out while piping and driver stay in place.

Summary

A split case fire pump is the natural choice for large flows from a positive suction source, and its clearest advantage is maintenance without breaking the piping. It does need carefully designed suction piping, a model listed at the correct speed, and alignment checked after the piping is connected. Settling these points during technical selection costs far less than finding them at the acceptance test.

Need a split case fire pump for your project? Send us the required flow and pressure, the water source and the pump room layout, and we will send the matching SFFECO, WATEX or Jack Pump model with its datasheet and curve. Contact the AZEIDK team

References: Piping arrangements for fire pumps (Consulting-Specifying Engineer); NFPA 20: Fire pump design (Consulting-Specifying Engineer); Fire Pump Testing Requirements (InspectPoint); Jack Pump Catalog 2024 (AZEIDK brand page) (Jack Pump); AZEIDK WATEX WS and SFFECO SFP product pages