UL Listed Fire Extinguisher Ratings: 2-A:10-B:C vs EN 3 13A/89B in Saudi Arabia

UL Listed Fire Extinguisher Ratings: 2-A:10-B:C vs EN 3 13A/89B in Saudi Arabia

A UL listed fire extinguisher is a model that UL Solutions has tested and rated to ANSI/UL 711, with the rating printed on the label in a form such as 2-A:10-B:C. European extinguishers are rated to EN 3 in a form such as 13A/89B, and there is no official conversion between the two systems. In Saudi Arabia a UL mark alone is not enough: the extinguisher also needs a valid certificate of conformity under the SASO Technical Regulation for Fire Control Materials and Equipment.

Key takeaways

  • The number before A or B in a UL rating reflects the size of the test fire the extinguisher put out. A higher number means more extinguishing capability.
  • The C in a UL rating has no number. It means the agent did not conduct electricity in the test.
  • Under EN 3 an extinguisher is classified by its rating, not its weight or size. A smaller unit that meets 13A is just as effective as a larger 13A unit.
  • No formula converts 2-A into 13A. Compare against the code adopted for the project and the datasheet.
  • The Saudi technical regulation requires a certificate of conformity before extinguishing equipment is placed on the market, and it does not name UL as a substitute.
In this article
  1. What does a UL listed fire extinguisher mean?
  2. How do you read a UL rating such as 2-A:10-B:C?
  3. How do you read an EN 3 rating such as 13A/89B?
  4. UL 711 vs EN 3: side-by-side
  5. Can 2-A be converted to 13A?
  6. What applies to fire extinguishers in Saudi Arabia?
  7. How to check that an extinguisher is really UL listed
  8. Fire extinguishers available from AZEIDK
  9. Frequently asked questions
  10. Conclusion

What does a UL listed fire extinguisher mean?

UL Listed means the extinguisher model was tested by UL Solutions, appears in its listings, and is built under UL’s ongoing factory follow-up. The rating and fire test standard is ANSI/UL 711, published as an identical standard with the Canadian CAN/ULC-S508. It covers rating and fire-test performance for Class A, B, C, D and K fires.

NFPA 10 (2018 edition), Section 4.1.1, states that portable fire extinguishers used to comply with the standard shall be listed and labeled, and shall meet ANSI/UL 711 and CAN/ULC-S508. That is why consultants on projects designed to NFPA 10 ask for UL listed extinguishers, or an equivalent that the project code accepts. For distribution and inspection rules, see our NFPA 10 portable fire extinguishers guide. This reference is to the 2018 edition as cited by the source; newer editions have been issued since, the latest being the 2026 edition, so check the section number in the edition your project uses.

How do you read a UL rating such as 2-A:10-B:C?

The label combines three parts, and each comes from a different test in UL 711.

The A part: ordinary combustibles

The Class A number comes from comparative fire tests on wood cribs and wood panels of different sizes. The rating table in the standard runs from 1-A to 40-A. Ratings from 1-A to 6-A need both crib and panel tests, while 10-A and above need crib tests only. In practice, a 4-A unit has passed a larger test fire than a 2-A unit.

The B part: flammable liquids

Class B is tested on square pans of flammable liquid. UL 711 states that the Class B rating equals 40 percent of the fire area consistently extinguished by an expert operator. From the pan table: the 1-B pan is 2.5 ft² (0.23 m²) and the 20-B pan is 50 ft² (4.65 m²). So a 10-B unit has put out a much larger pan fire in testing than a 1-B unit.

The C part: energized electrical equipment

Class C carries no number. The UL 711 Class C test checks that the agent is electrically nonconductive, and no fire tests on electrical fires are run. To pass, there must be no visible breakdown and current must not rise above 1.0 mA. A C rating tells you the agent is safe on live equipment. It does not measure fire size.

Class K: cooking oils

Class K also has no number. It is tested on a fryer with vegetable oil, and the fire must go out with no re-ignition for at least 20 minutes and no splashing of burning oil.

How do you read an EN 3 rating such as 13A/89B?

The EN 3 series sets the characteristics, performance and test methods for portable extinguishers, and EN 3-7 covers classification and fire tests for Classes A and B. Class A tests use burning wooden cribs, and Class B tests use trays of flammable liquid. The number in 13A or 89B indicates the size of the test fire, so a bigger number means a bigger fire put out.

London Fire Brigade guidance makes two useful points for buyers. Extinguishers are classified by rating, not by size, weight or litres of content, and a smaller unit that meets 13A is just as effective. It also gives the example of a 2.5 kg CO2 extinguisher rated 34B. EN 3 also includes Class F for cooking oils, shown as for example 15F.

UL 711 vs EN 3: side-by-side

ItemUL 711 / CAN/ULC-S508EN 3 (EN 3-7 for rating)
Rating format2-A:10-B:C13A/89B (F may be added for cooking oils)
Ordinary combustibles testWood cribs and panels, 1-A to 40-AWooden cribs; the number indicates test fire size
Flammable liquids testSquare pans; rating is 40% of the area an expert operator puts outLiquid trays; the number indicates test fire size
Electrical equipmentC with no number, after a nonconductivity testNo numeric electrical class; check the manufacturer’s label and datasheet
Cooking oilsClass K, no numberClass F with a number, such as 15F
Usually required byNFPA 10 and projects designed to US referencesProjects designed to European and British references

Note that the letter C means different things. In UL it stands for energized electrical equipment, while in the European fire classes it refers to gas fires. Do not compare the letters one to one.

Can 2-A be converted to 13A?

No official formula converts a UL rating into an EN 3 rating or back, because the test fires and methods differ. Start from the reference the designer and Civil Defense adopted for the project, then pick an extinguisher rated to that reference at the rating the distribution tables call for. If the drawings follow NFPA 10, the tables use UL units such as 2-A and 10-B, and a unit rated only 13A needs the consultant’s approval. For a first estimate of quantities, try our fire extinguisher calculator, then have an engineer review the result.

What applies to fire extinguishers in Saudi Arabia?

The Saudi Fire Protection Code (SBC 801) and Civil Defense decide which buildings need extinguishers and how they are distributed. NFPA 10 is the common technical reference for selection and distribution, and the applicable edition is set by the code and the authority on each project.

Placing an extinguisher on the market is governed by the SASO Technical Regulation for Fire Control Materials and Equipment. It states that equipment in scope shall not be placed on the market without a certificate of conformity from a SASO-approved body, under conformity assessment Type 3, with a technical file that includes the supplier’s declaration of conformity. Its annex of standards lists GSO ISO 7165 for portable extinguishers. The regulation does not mention UL, so a UL mark is not a substitute for Saudi conformity. It also states that the updated product and customs code listings are those published on the SABER platform.

How to check that an extinguisher is really UL listed

  1. Read the label. It should show the full rating, such as 2-A:10-B:C, the listing mark and the model number.
  2. Look the model up in UL Product iQ, UL Solutions’ source for certification information. The method is the same as in our guide on checking UL and FM approval for fire pumps.
  3. Match the datasheet to the label: weight, agent, rating and operating temperature range must agree.
  4. Ask for the valid Saudi certificate of conformity for the same model and check its expiry. A certificate in an old approval file does not prove it is valid today.
  5. Do not accept “UL Approved” or “UL Standard” in a catalogue without a listing you can verify.

Fire extinguishers available from AZEIDK

AZEIDK supplies fire extinguishers in Saudi Arabia, including the Falcon Gold range of dry powder, CO2 and foam units. Ratings and approvals vary by model, so we send the datasheet and the available conformity certificate for each model before approval, and we do not describe any model as UL listed unless its listing can be verified. For the differences between types, see Falcon Gold fire extinguisher types, and for servicing see fire extinguisher maintenance and refilling.

What drives the cost of a UL listed extinguisher?

  • The approval the specification calls for: UL, EN 3 or another.
  • The rating needed at each location. A higher rating means a larger unit or a more effective agent.
  • The agent: dry powder, CO2, foam or wet chemical.
  • Quantity, cabinets and brackets, and installation and signage needs.
  • The maintenance contract after handover.

Frequently asked questions

What is a UL listed fire extinguisher?

It is an extinguisher model tested by UL Solutions to ANSI/UL 711 and included in its listings, with ongoing factory follow-up. Its rating appears on the label in a form such as 2-A:10-B:C.

What does 2-A:10-B:C mean?

2-A is the capability on ordinary combustibles, 10-B the capability on flammable liquids from the pan test, and C means the agent is nonconductive. The numbers are relative: higher means more capability.

Is a 13A extinguisher equal to a 2-A extinguisher?

There is no official equivalence because the two standards use different tests. Follow the reference the designer adopted, and get the consultant’s approval for any substitute.

Is a UL certificate enough to sell an extinguisher in Saudi Arabia?

No. The SASO Technical Regulation for Fire Control Materials and Equipment requires a certificate of conformity from a SASO-approved body and does not name UL as a substitute.

What is the difference between a UL and a UL/FM fire extinguisher?

UL tests and lists extinguishers to UL 711. FM Approvals is a separate approval body. If a model claims both, check each body’s own database, not the catalogue.

How do I verify a UL listed fire extinguisher in Saudi Arabia?

Match the model number on the label against UL Product iQ, then ask the supplier for the datasheet and the valid Saudi certificate of conformity for the same model.

Conclusion

A UL rating such as 2-A:10-B:C and an EN 3 rating such as 13A/89B measure extinguishing capability in two different ways, and no fixed number converts one into the other. Choose the extinguisher to the reference adopted for your project, verify the listing in the issuing body’s database, and do not accept delivery without a valid Saudi certificate of conformity.