Occupancy Classification in the Saudi Building Code: Groups A, B, E, F, H, I, M, R and S and Their Effect on Fire Systems

Occupancy Classification in the Saudi Building Code: Groups A, B, E, F, H, I, M, R and S and Their Effect on Fire Systems

Occupancy classification assigns a building, or part of it, to a use group (assembly, business, educational, factory, high-hazard, institutional, mercantile, residential, storage, utility). It is the first decision in any fire system design, because the code writes its alarm, sprinkler and egress requirements by occupancy group. A wrong classification means an incomplete or needlessly expensive design, and comments at Civil Defense approval.

This guide explains the occupancy groups of the International Building Code on which the Saudi Building Code is based, Saudi examples for each group, how classification drives fire systems, and common mistakes. AZEIDK’s engineering design and calculations team starts every project by confirming the occupancy classification before selecting systems.

Key points

  • According to the International Code Council (ICC), the 2018 Saudi Building Code was revised based on the 2015 International Codes; occupancy classification sits in Chapter 3 of the building code.
  • Main groups: A assembly, B business, E educational, F factory, H high-hazard, I institutional, M mercantile, R residential, S storage, U utility.
  • Many groups have subgroups, such as A-1 to A-5, H-1 to H-5 and R-1 to R-4.
  • Sprinkler and alarm requirements in SBC 801 are read by occupancy group, with area, height and occupant load limits.
  • One building can hold several occupancies, and small accessory areas follow special rules.
In this article
  1. What is occupancy classification and why does every project start with it?
  2. Occupancy groups: reference table
  3. Institutional and educational details
  4. How classification drives fire systems
  5. Mixed occupancies and accessory areas
  6. Steps to classify your project
  7. Common classification mistakes
  8. FAQ
  9. Summary

What is occupancy classification and why does every project start with it?

It answers one question: what is this space actually used for, and by whom? A dining hall for fifty people differs from an office of the same size, and a store of flammable materials differs from one of non-combustible goods. The code builds on this: number of exits, whether sprinklers are needed, the type of alarm system and fire separations all change by group. The classification therefore appears on the first sheet of the Civil Defense drawings and in the design basis report. For how the two codes relate, see SBC 801 vs SBC 201 vs Civil Defense requirements.

Occupancy groups: reference table

Definitions below summarise IBC Chapter 3 as published by Blount County, Tennessee; Saudi examples follow the same definitions. Always check the adopted SBC 201 text.

GroupShort definitionSaudi examples
A-1Performing arts or motion pictures, usually fixed seatingCinemas, theatres
A-2Food and/or drink consumptionRestaurants, food courts
A-3Worship, recreation, other assemblyMosques, recreation halls
A-4Indoor sports with spectator seatingIndoor arenas
A-5Outdoor activitiesOpen stadiums
BOffice, professional and service transactions; assembly under 50 personsOffices, outpatient clinics, banks
EEducation of 6 or more persons through 12th gradeSchools
F-1 / F-2Manufacturing, moderate or low hazardIndustrial facilities
H-1 to H-5Physical or health hazard materials above code allowancesChemical and flammable stores above permitted quantities
I (incl. I-1, I-2, I-3)Institutional with care or supervision; I-2 is 24-hour medical careHospitals and healthcare
MDisplay and sale of merchandise to the publicMalls and shops
R-1Transient residentialHotels, serviced apartments
R-2 / R-3R-2 multiple permanent dwelling units; R-3 one- and two-family dwellingsApartment buildings, villas
S-1 / S-2Non-hazardous storage, moderate or low hazardWarehouses and logistics
UAccessory and utility structuresSmall ancillary buildings

Institutional and educational details

  • E: also covers day care for more than 5 children older than 2½ years.
  • I-1: more than 16 persons in 24-hour supervised residential care who can respond to emergencies without physical staff assistance.
  • I-2: 24-hour medical, surgical, psychiatric or nursing care for more than 5 persons not capable of self-preservation; 5 or fewer are treated as R-3.
  • I-3: more than 5 persons under restraint or security.
  • R-4: residential care for more than 5 and up to 16 occupants, excluding staff.

How classification drives fire systems

In SBC 801, automatic sprinkler and fire alarm requirements are written under occupancy group headings, each with its own area, occupant load or storey limits. You cannot answer “are sprinklers mandatory?” or “is an alarm system required?” before fixing the group; see are sprinklers mandatory? and when is a fire alarm system mandatory?. Building-code occupancy differs from the NFPA 13 hazard classification (light, ordinary, extra): the first decides whether a system is needed, the second sets sprinkler density and pump size.

Mixed occupancies and accessory areas

Many Saudi buildings combine uses: shops below apartments, a hotel with a restaurant and ballroom, a factory with offices and a warehouse. Each part is classified by its use, then the separation approach permitted by the code is chosen. Per the same summary, an assembly room for fewer than 50 people accessory to another occupancy takes that occupancy’s classification, assembly areas under 750 sq ft (about 70 m²) accessory to another occupancy are not treated as assembly, and assembly rooms accessory to Group E are not Group A. Read the adopted text carefully before relying on these exceptions.

Steps to classify your project

  1. Write down the actual use of every space.
  2. Calculate the occupant load.
  3. Review stored materials and quantities for any H areas.
  4. Apply accessory and mixed-occupancy rules per SBC 201.
  5. Show the classification and occupant loads on the plans and design report.
  6. Read the SBC 801 sprinkler, alarm and voice evacuation triggers for each group.

Common classification mistakes

  • Classifying by trade name instead of actual use.
  • Ignoring a store whose hazardous material quantities push part of it into Group H.
  • Not updating the classification after a change of use, such as an office turned restaurant. An existing systems assessment shows what must be added.
  • Confusing occupancy classification with NFPA 13 hazard classification.
  • Leaving occupant loads off the drawings.

FAQ

What is occupancy classification in the Saudi Building Code?

Assigning a building or space to a use group such as A, B, M, R or S, which drives fire, egress and construction requirements.

How is a restaurant classified?

Food and drink spaces are Group A-2, subject to the small accessory area rule for fewer than 50 persons.

What is the difference between R-1 and R-2?

R-1 is transient, such as hotels; R-2 is multiple dwelling units with more permanent occupants, such as apartment buildings.

When is a warehouse Group H instead of S?

When it holds physical or health hazard materials above the quantities the code allows.

Is occupancy classification the same as NFPA 13 hazard classification?

No. Occupancy decides whether a system is required; NFPA 13 hazard class sets sprinkler density and hydraulics.

Who sets the occupancy classification?

The designer in the design report and drawings, reviewed by the consultant and approved by Civil Defense with the plans.

Summary

Occupancy classification is the key to reading the rest of the code. Fix it for every part of the building, document it with occupant loads, and review it whenever the use changes.

Need your occupancy classification confirmed? Send us the architectural drawings and a description of the use, and the AZEIDK team will review the classification and the fire system requirements that follow. Contact AZEIDK

References: Occupancy Classifications (IBC Chapter 3 summary) (Blount County, Tennessee), Saudi Arabia and the International Codes (International Code Council)