A rack PDU for a network cabinet (power distribution unit) is a strip of power outlets built to mount in a 19-inch rack, feeding switches, recorders and servers from one tidy, protected source. To choose one you need three things: the outlet type that matches your equipment cords, the unit’s rated current, and the total load of everything plugged into it.
The structured cabling and network products AZEIDK supplies are listed under network systems.
Below we cover PDU types and how to size the load, with the specifications of the Legrand LCS³ 646813, available from AZEIDK with passive network systems and cabinet accessories.
Key points
- A PDU distributes power inside the rack, mounted horizontally in 1U or vertically beside the equipment.
- Legrand 646813: eight BS 1363 outlets, 13 A, 230 V, 3 kW maximum.
- The LCS³ range also has locking C13/C19 versions, MCB or RCBO versions, surge-protected versions and Zero-U vertical units up to 32 A.
- Size the load from each device’s maximum consumption in its datasheet, not from the number of outlets.
- A PDU does not replace a UPS; it is usually fed from the UPS or a dedicated circuit.
What is a rack PDU and why not a household extension?
A household extension sits on the cabinet floor or is taped to a side, so cords tangle and it is hard to tell what is plugged in where. A PDU fixes to the 482.6 mm (19-inch) rails, has a metal housing and a supply cord of suitable length, so the rack stays tidy and easy to inspect.
That is why it is a standard accessory for cabinets such as the Linkeo 42U floor cabinet or the 18U wall cabinet. For choosing the cabinet itself see 42U and 32U server racks and wall cabinet sizes.
Legrand LCS³ 646813 specifications
From the AZEIDK product page, based on Legrand’s official datasheet:
| Item | Value |
|---|---|
| Outlets | 8 x BS 1363 |
| Rated current | 13 A |
| Voltage | 230 V, 50 to 60 Hz |
| Maximum power | 3 kW |
| Supply cord | 3 m |
| Height | 1U |
| Dimensions | 465 x 44.3 x 52.5 mm |
| Mounting | 19-inch, horizontal or vertical |
| Protection | IP40 |
| Housing | Natural anodised aluminium |
PDU types by outlet and protection
BS 1363 outlets
Suit equipment with UK-plug adapters or cords, such as small recorders, modems and some switches. The 646813 is this type.
C13 and C19 outlets
Servers, enterprise switches and UPS units usually have IEC inlets, so a PDU with C13 or C19 outlets fits them better. Legrand lists locking C13/C19 versions in the LCS³ range that stop cords working loose. The Legrand Keor SPE 2200VA UPS, for example, has C13 and C19 outlets.
Breaker and surge-protected versions
The range includes versions with a built-in MCB or RCBO and surge-protected versions, chosen according to the supply board design and project requirements.
Zero-U vertical PDUs
Mounted vertically at the side of a floor cabinet so they use no rack units; Legrand lists versions up to 32 A. They suit crowded server room cabinets.
For offices and simple uses there is also the AZ-Link 6-way power distribution unit.
How to size a network cabinet PDU
- Add up each device’s maximum consumption in watts from its datasheet, not its typical draw.
- Watch PoE switches: their draw includes the power they feed to cameras and access points, so the PoE budget is part of their load.
- Compare the total with the PDU rating: power is roughly voltage times current, so 13 A at 230 V gives about 3,000 W, the figure Legrand gives for the 646813.
- Leave a margin and do not run the unit at its limit, following the electrical engineer’s design for the supply circuit.
- Check the UPS rating too if the PDU is fed from a UPS.
For preparing a complete network room (power, cooling, earthing) see server room and network room preparation, and for the Legrand UPS with the Linkeo cabinet see Legrand in Saudi Arabia.
Practical installation tips
- Route power cords on one side of the cabinet and data cables on the other.
- Label each outlet with the device it feeds.
- For devices with two power supplies, connect each to a different PDU where the design provides two separate sources.
- Earth the cabinet and PDU according to the manufacturer’s instructions.
Frequently asked questions
What does PDU mean in a network cabinet?
Power distribution unit: a rack-mounted outlet strip that feeds the equipment from organised outlets.
How many outlets does the Legrand 646813 have?
Eight BS 1363 outlets, rated 13 A with a 3 kW maximum.
Do I need C13 or UK outlets?
It depends on your cords: servers and enterprise devices usually have IEC inlets that suit C13/C19, while UK-plug devices suit BS 1363.
Does a PDU protect against power cuts?
No. A PDU only distributes power; protection against outages needs a UPS.
What is the difference between horizontal and vertical PDUs?
A horizontal PDU takes 1U of rack space; a Zero-U vertical PDU mounts at the cabinet side without using rack units.
How do I know the PDU can carry the load?
Add up the maximum consumption of the devices from their datasheets and compare it with the unit’s rating, leaving a margin.
Summary
Choosing a network cabinet PDU starts with the outlet type your equipment needs, then the total load, especially with PoE switches. The 646813 with eight UK outlets suits many network and CCTV cabinets, and the LCS³ range adds C13/C19, breaker and vertical versions for larger cabinets.
Fitting out a network cabinet or server room? Send us the equipment list and locations, and the AZEIDK team will propose the cabinet, PDU and UPS with datasheets. Contact AZEIDK
Related guides
- Civil Defense Licence for Hospitals and Private Medical Complexes: Required Systems and Documents
- Fire Pipes: Types, Schedules, Grooved Joints and Delivery Inspection
- Factory Fire Extinguishers in Saudi Arabia: Type and Size for Production Halls, Stores, Electrical Rooms and Fuel Areas
- PTZ Cameras from Dahua and Hikvision: When to Use Them and How to Choose