Idle pallet storage looks like a minor matter in a warehouse, yet it is one of the hardest loads a sprinkler system can face. An empty wood pallet is full of voids and exposes bare timber on every side, so it ignites quickly and releases a lot of heat. That is why NFPA 13 treats idle pallets as special storage with criteria of their own, and why a system designed for the ordinary goods in the warehouse may not be enough.
This guide explains why idle pallets differ from stored goods, what NFPA 13 sets for pile height and spacing, the difference between wood and plastic pallets, and how the design is built within AZEIDK’s fire fighting systems for the warehouses and logistics sector.
Key points
- NFPA 13 (2025 edition) covers idle pallet storage in Section 20.17, separately from commodities and from low-piled storage.
- Under an Ordinary Hazard Group 2 design, wood pallet piles are limited to 1.8 m (6 ft) and plastic pallet piles to 1.2 m (4 ft).
- Piles are separated by at least 2.4 m (8 ft) of clear space or 7.6 m (25 ft) of stored commodity.
- Idle pallets may not be stored on solid-shelf racks.
- Plastic pallets are treated like wood only if shown to be of equal or lower hazard and listed for that equivalency.
Why are idle pallets a high hazard?
When a pallet carries goods, cartons and product cover much of the wood. An empty stack is dozens of timber boards with gaps that let air in from every direction, so fire climbs the pile fast. The National Fire Sprinkler Association (NFSA) describes idle pallets as special storage whose protection must be evaluated separately.
A common problem in Saudi warehouses is that sprinklers are calculated for the stored goods, then idle pallets pile up in a corner or next to the loading doors at a height the system was never designed for. The weakest point in the warehouse becomes the one nobody planned for.
What does NFPA 13 require for idle pallet storage?
According to a PHCP Pros summary of Section 20.17 of NFPA 13 (2025), the criteria apply to indoor storage only and allow several protection schemes depending on storage and ceiling height:
| Protection scheme | Wood pallets | Plastic pallets |
|---|---|---|
| Ordinary Hazard Group 2 (density/area) | Piles up to 1.8 m | Piles up to 1.2 m |
| Control mode density/area (CMDA) | Storage 1.8 to 6.1 m, ceiling up to 9.1 m | Outside a dedicated room: piles up to 3.0 m, ceiling up to 9.1 m |
| Dedicated room | No equivalent | Piles up to 3.7 m with a 3-hour fire wall |
| ESFR sprinklers | Storage 6.1 to 10.7 m, ceiling 9.1 to 12.2 m | No storage height limit, ceiling up to 12.2 m |
| In-rack sprinklers | Per Section 25.7 | Per Section 25.7 |
The same summary gives a CMDA design density for plastic pallets outside a dedicated room of 0.6 gpm/ft² over 2,000 ft², with sprinklers of K-factor 16.8 or larger. These are reference figures; the actual design follows the edition adopted for the project and the datasheet of the selected sprinkler.
Wood or plastic pallets?
Many warehouses are switching to plastic pallets because they are lighter, cleaner and last longer. From a fire standpoint, NFPA 13 defines a plastic pallet as any pallet with plastic in any part of its construction and treats it as a higher hazard than wood. It is treated like wood only if testing shows equal or lower hazard and it is listed for that. The designer must know the pallet type before calculating the system, and must be told if it changes after start-up.
Where should idle pallets go in the warehouse?
The simplest and cheapest fix is usually organisation before sprinklers:
- Assign a defined pallet area on the layout and design the system for it from the start.
- Keep piles within the design height and mark that height on the wall.
- Leave clear aisles around piles at the distances set in the standard.
- Never store pallets on solid-shelf racks or in front of hose cabinets and exits.
- Where possible, store pallets outside, away from walls, at a distance agreed with the consultant.
These are the points an inspector usually checks, and they tie into the warehouse Salamah licence requirements.
Is the existing sprinkler system enough?
In an existing warehouse the first question is what the system was designed for: sprinkler type, K-factor, density, design area and pump pressure. That is then compared with what the actual pallet storage needs. The outcome may be that lowering pile height is enough, that the area needs different sprinklers, or that the pump cannot meet the new demand.
We cover high-piled storage and ESFR in warehouse fire protection, the calculation method in sprinkler hydraulic calculations, and sprinkler types and K-factors in sprinkler head types. Reviewing an existing system and recalculating it falls under our engineering design and calculations service.
Common mistakes in pallet areas
- Stacking pallets close to the roof because the space is free, without checking the design height.
- Replacing wood pallets with plastic ones without telling the system designer or reviewing the calculations.
- Leaving pallets next to loading doors, where they block escape routes and fire service access.
- Storing broken pallets with sound ones, which adds voids and speeds ignition.
- Leaving the pallet area off the protection drawings submitted for approval, so the issue first appears at inspection.
Regulatory framework in Saudi Arabia
SBC 801 and the requirements of the General Directorate of Civil Defense are the binding basis for requiring sprinklers in a warehouse. NFPA 13 is the technical reference the designer adopts for protection details such as pallet height limits and densities, according to the edition specified in the project documents.
FAQ
What is the maximum pile height for wood pallets?
It depends on the scheme. Under an OH2 design in NFPA 13 (2025) the limit is 1.8 m; with CMDA or ESFR sprinklers designed for it, piles can go higher within ceiling and density limits.
Are plastic pallets more dangerous than wood?
NFPA 13 treats them as a higher hazard unless a model is tested and listed as equal or lower hazard. That is why their limits are tighter and densities higher.
Can idle pallets be stored in racks?
Not on solid-shelf racks. They can go in open racks if protected with in-rack sprinklers under the dedicated criteria.
What spacing is required between pallet piles?
Under an OH2 design, piles are separated by at least 2.4 m of clear space or 7.6 m of stored commodity.
Do pallets stored outdoors need sprinklers?
Section 20.17 covers indoor storage. Outdoor storage is assessed by distance from buildings and hydrant coverage, agreed with the consultant and the competent authority.
How do I know if my system protects the pallet area?
By reviewing the original design data (sprinkler type, density, design area and pump) against actual storage. AZEIDK offers this review under its engineering design and calculations service.
Summary
Idle pallets are not ordinary goods as far as fire standards are concerned. Pile height, pallet type and spacing decide whether the sprinklers can control a fire. Marking a clear pallet area on the layout from day one costs far less than modifying the system after start-up.
Not sure your pallet area is protected? Send us the warehouse layout and current sprinkler design data, and we will review heights and densities with you. Contact the AZEIDK team
Related guides
- When Is a Fire Alarm System Mandatory? SBC 801 Requirements by Occupancy
- Cat6 vs Cat6A: Speed, Distance, Shielding (UTP, F/FTP) and LSZH, and When to Choose Each
- Fire Protection and Safety Companies in Jeddah: A Practical Selection Guide
- Fire Alarm System Installation in Saudi Arabia: Stages, Cabling and Pre-Approval Checks