Belden Cable in Saudi Arabia: Fire Alarm, Fire-Resistant, Network, RS-485 and Coax Models

Belden Cable in Saudi Arabia: Fire Alarm, Fire-Resistant, Network, RS-485 and Coax Models

Belden cable is often named directly in Saudi project specifications, so contractors and consultants search for it by brand and model number. AZEIDK supplies six Belden cables that cover the main circuits in a building: fire alarm cable, fire-resistant cable, Cat6 and Cat6A network cable, RS-485 data cable and RG6 coax. This guide explains which model fits which system, using the official Belden datasheets attached to each product page.

AZEIDK supplies and installs these cables as part of its fire alarm systems and low current systems work. Belden cables are available from AZEIDK.

Key points

  • Belden 9581 fire alarm cable: 2 x 14 AWG solid copper, 100% foil shield, red FPLR jacket.
  • Belden 79001FS Safe-T-Line fire-resistant cable: 2 x 1.5 mm², LPCB approved, BS 6387 CWZ and EN 50200 PH120, LSZH jacket.
  • Network cables: 7965E Cat6 U/UTP and 10GXE02 Cat6A S/FTP with an LSZH-type jacket.
  • 3107A for RS-485 networks, and 9116 RG6 coax for TV and satellite distribution.
In this article
  1. Belden fire alarm cable: Belden 9581
  2. Fire-resistant cable: Belden 79001FS Safe-T-Line
  3. Belden network cable: Cat6 or Cat6A
  4. RS-485 cable for panel networks: Belden 3107A
  5. RG6 coaxial cable: Belden 9116
  6. Which Belden cable fits your project?
  7. Belden catalogue, datasheets and quotations
  8. Frequently asked questions
  9. Summary

Belden fire alarm cable: Belden 9581

Belden 9581 is a 2-conductor 14 AWG solid bare copper cable with PVC insulation, an overall Beldfoil shield with 100% coverage, a 16 AWG tinned copper drain wire and a red PVC jacket rated FPLR. Nominal outside diameter is 7.77 mm.

Belden lists it for fire alarms, low-voltage analogue signals and low-voltage control circuits such as 24 V. In commercial towers, hospitals and malls it is typically used for detector and sounder circuits and riser links, once the conductor size has been checked against circuit length and voltage drop.

Fire-resistant cable: Belden 79001FS Safe-T-Line

When the specification requires a circuit to keep working during a fire, you need a fire-resistant cable. Belden 79001FS from the Safe-T-Line family is LPCB approved and meets BS 6387 CWZ, EN 50200 PH120 with Annex E, and IEC 60331-2.

It has two 1.5 mm² solid copper conductors with silicone rubber insulation, an aluminium/polyester shield with a tinned drain wire, and a low smoke zero halogen (LSZH) jacket. Belden lists fire alarm, voice evacuation, PA, control and emergency systems as its applications.

For a full comparison of the two cable types, see FPLR fire alarm cable vs fire-resistant cable.

Belden network cable: Cat6 or Cat6A

ItemBelden 7965EBelden 10GXE02
CategoryCat6, 250 MHzCat6A enhanced, 625 MHz
ShieldingUnshielded (U/UTP) with X-Spline separatorFoil on each pair plus 30% tinned copper braid (S/FTP)
Conductors4 pairs, 23 AWG solid copper4 pairs, 23 AWG solid copper
JacketPVC, CPR EcaLSZH-type, CPR Eca
SpeedGigabit Ethernet10 Gigabit (10GBase-T)

Belden 7965E suits office LANs, IP CCTV, access control and IP intercom. Belden 10GXE02 suits server rooms, Wi-Fi 6 access points and sites with interference or an LSZH requirement. For the general comparison, see Cat6 vs Cat6A network cable.

RS-485 cable for panel networks: Belden 3107A

Belden 3107A is a 2-pair 22 AWG stranded tinned copper data cable with a 100% Beldfoil shield plus 65% tinned copper braid and an oil-resistant PVC jacket rated CM and PLTC. It is used to network fire alarm panels and repeaters, BMS controller buses and access control over RS-485.

RG6 coaxial cable: Belden 9116

Belden 9116 is a Series 6 (RG6) coax with an 18 AWG copper-covered steel centre conductor, gas-injected foam dielectric, Duobond II foil plus 60% aluminium braid, and a PVC jacket rated CM for indoor use. It is used for MATV and satellite distribution in hotels, hospitals and residential towers, and for analogue CCTV runs. See also CCTV cable: coax or Cat6.

Which Belden cable fits your project?

SystemModel
Fire alarm detector and sounder circuits9581
Circuits that must work during a fire, such as voice evacuation79001FS
Office network and IP cameras7965E
Server rooms and LSZH sites10GXE02
Panel networks and BMS3107A
TV and satellite distribution9116

Before ordering, check the conductor size against circuit length and voltage drop, the wiring requirements of the panel or device manufacturer, and the cable rating called for in the project specification and Civil Defense approval.

Belden catalogue, datasheets and quotations

Each model has a product page on the AZEIDK site with a Download Datasheet button for the official Belden file. AZEIDK does not show prices online, because they change with quantity and availability. Send your cable schedule or riser diagram through the quote request form and AZEIDK engineers will check sizes and ratings before pricing. You can also read fire alarm cable types and the network cable types guide.

Frequently asked questions

Does AZEIDK supply Belden cable in Saudi Arabia?

Yes. Belden cables are available from AZEIDK, including 9581, 79001FS, 7965E, 10GXE02, 3107A and 9116, with supply and installation as part of fire alarm and low current systems.

What is the Belden 14 AWG fire alarm cable?

Belden 9581: two 14 AWG conductors with a foil shield and a red FPLR jacket.

What is the difference between Belden 9581 and 79001FS?

9581 is an FPLR fire alarm cable tested for flame spread. 79001FS is an LPCB approved fire-resistant cable meeting BS 6387 CWZ and EN 50200 PH120, so the circuit keeps working during a fire.

Does Belden 10GXE02 support 10 Gigabit?

Yes. Belden states it supports 10GBase-T and all Category 6A and 6 applications.

Where can I download the Belden catalogue or datasheets?

From each product page on the AZEIDK site, or ask the AZEIDK team for them with your quotation.

Can Belden 9116 be used outdoors or in risers?

Belden rates its jacket CM for indoor use; it is not rated for riser or plenum spaces.

Summary

Choosing the right Belden cable starts with the system: 9581 for fire alarm circuits, 79001FS for circuits that must survive a fire, 7965E or 10GXE02 for networks, 3107A for panel networks and 9116 for TV distribution. Contact AZEIDK to have your cable schedule reviewed and priced.