PYRAMID CO2 Extinguishers: Sizes and Use in Electrical and Server Rooms

PYRAMID CO2 Extinguishers: Sizes and Use in Electrical and Server Rooms

A CO2 fire extinguisher is the usual choice next to electrical panels and in server rooms. The gas does not conduct electricity and leaves no residue on equipment. But the same gas lowers the oxygen in the room, leaves the horn extremely cold, and cannot fully put out wood, paper or cardboard on its own.

This article covers PYRAMID CO2 sizes from AZEIDK Egypt, portable versus wheeled units, placement in electrical and server rooms, and the limits to know before buying.

Key takeaways

  • PYRAMID CO2 extinguishers from AZEIDK Egypt come in 2, 3, 6, 10, 20 and 30 kg, portable and wheeled, conforming to EN3 and ES 735, EOS-approved, with the Egyptian quality mark.
  • OSHA says CO2 extinguishers are for flammable liquid and electrical fires only, not ordinary combustibles.
  • The proposed 2026 text of NFPA 10 bans dry chemical extinguishers for protecting delicate electronic equipment and requires types listed for Class C hazards.
  • NFPA 10 treats CO2 extinguishers with metal horns as obsolete. They must be removed from service.
  • Never use CO2 in a closed space with people inside without respiratory protection, and never hold the horn.
In this article
  1. How a CO2 fire extinguisher works and why it suits electrical fires
  2. PYRAMID CO2 sizes available from AZEIDK Egypt
  3. Choosing the size: portable or wheeled?
  4. CO2 extinguishers in server rooms and electronic equipment areas
  5. Limits of use and hazards to people
  6. Legal reference and technical reference
  7. Recharging and maintenance
  8. Common mistakes when buying and installing CO2 extinguishers
  9. Frequently asked questions
  10. Conclusion

How a CO2 fire extinguisher works and why it suits electrical fires

CO2 is stored in the cylinder as a liquid under high pressure. On discharge it expands into gas and leaves the horn as a white cloud with dry ice particles. The US Occupational Safety and Health Administration (OSHA) explains that it works mainly by displacing oxygen, with some cooling.

Three practical results:

  • It does not conduct electricity: you can aim it at equipment that is still energized. US standards call this Class C.
  • It leaves no residue: the gas disperses after the fire is out, so there is no powder to clean off equipment.
  • It works on flammable liquids: Class B fires, such as oils and solvents in workshops and plant rooms.

Note: in the European system used by EN3, Class C means gases and there is no electrical class. In NFPA 10, Class C means energized electrical equipment. For a full comparison of extinguisher types, see our guide to fire extinguisher types and uses.

PYRAMID CO2 sizes available from AZEIDK Egypt

The PYRAMID page at AZEIDK Egypt lists two CO2 product groups. Data comes from that page and each datasheet; approvals are stated per product:

ProductSizesConfigurationConformity and approval
PYRAMID CO2 extinguishers2 – 3 – 6 – 10 – 20 – 30 kgPortable and wheeledConform to EN3 and Egyptian standard ES 735; approved by the Egyptian Organization for Standardization and Quality (EOS) and carry the Egyptian quality mark
PYRAMID automatic CO2 (Fire End)3 – 6 – 10 kgFixed inside the protected space with a detection tubeThe AZEIDK page refers to the datasheet, which states the Egyptian quality mark and conformity to ES 735 for the 3 and 6 kg sizes and ES 6115/2007 for the 10 kg size

The manual-unit datasheet lists a one-piece steel cylinder with no welded seams; working pressure 150 bar, test pressure 250 bar, burst pressure at least 400 bar; operating range −20 to +70 °C; and a nickel-chrome plated brass valve with an overpressure safety valve. It states that the 10, 20 and 30 kg sizes are on wheels, with a two-year warranty against manufacturing defects.

Choosing the size: portable or wheeled?

NFPA 10 does not set one size for every electrical room. The proposed 2026 text requires Class C rated extinguishers where energized electrical equipment can be encountered, then sizes and locates them based on the expected Class A or Class B hazard. So start from the space and the user. The table below is practical market guidance, not a code requirement:

LocationWhat to considerTypical choice
Distribution board in an office or corridorUsed by non-specialist staff, usually in an open spaceSmall portable unit (2 or 3 kg), easy to carry
Main electrical room or panel roomMore panels; entered by trained technicians6 kg portable unit near the door; confirm the number in the design
Server roomSensitive equipment; the proposed NFPA 10 text bars dry chemical units for protecting itPortable unit near the door, plus a study of a fixed suppression system for the room
Large switchgear hall or workshop with flammable liquidsOpen area, bigger hazard, longer discharge neededWheeled unit (10, 20 or 30 kg) in a corridor where it can be moved easily

A wheeled unit carries more agent but needs a level floor, a clear route and a trained user. Avoid placing one inside a small electrical room, where a large discharge raises the risk of oxygen depletion. Quantity, travel distance and mounting height are in our guide to extinguisher quantity and spacing.

CO2 extinguishers in server rooms and electronic equipment areas

The proposed 2026 text of NFPA 10, as shown in the Second Draft Report on the NFPA website, requires extinguishers for delicate electronic equipment to be selected from types listed and labeled for Class C hazards. It also states that dry chemical extinguishers shall not be installed to protect such equipment. A paper by the US Fire Equipment Manufacturers’ Association (FEMA) explains that powder residue sticks to surfaces, is hard to remove fully, and can corrode with heat and humidity.

The same paper notes that CO2 is listed for Class B and C, but is not effective on, or listed for, Class A. A server room still holds Class A materials, such as cable insulation and packaging cardboard. So:

  • Isolate power where possible, then use the extinguisher.
  • Watch for re-ignition of solids after the gas disperses.
  • Keep cardboard out of the room, and cover the general Class A hazard in adjacent corridors through the layout.

A portable extinguisher needs a person on site. Full automatic protection needs a fixed system; see our guide to clean agent suppression for server rooms. For small closed electrical panels with nobody inside, PYRAMID automatic CO2 units are available. The brand page and datasheet now name them Fire End. Use and installation are covered in our guide to PYRAMID automatic extinguishers.

Limits of use and hazards to people

Oxygen depletion in closed spaces

OSHA warns never to use CO2 extinguishers in a confined space with people present unless they have proper respiratory protection. A 2000 study by the US Environmental Protection Agency (EPA) lists the effects of CO2 on people: at 7–10%, unconsciousness or near-unconsciousness within a few minutes; at 17–30%, convulsions, coma and death within about a minute. The extinguishing concentration is far above the lethal level. After use in a small room, leave and ventilate before going back in.

Extreme cold at the horn

The horn gets very cold during discharge. Hereford & Worcester Fire and Rescue Service in the UK advises not to hold it, and warns that the extinguisher makes a loud noise when started. Hold the handle, hold the horn only by its dedicated grip if fitted, and never aim at people.

Metal horns and hose conductivity

NFPA 10 lists CO2 extinguishers with metal horns as obsolete units to be removed from service. This appears in the 2018 edition (cited by FEMA) and the proposed 2026 text. The proposed text also requires an annual conductivity test on all CO2 hose assemblies, and replacement of any hose that fails it.

Cooking oil fires

Never use CO2 on cooking oil or fat fires, as the same UK fire service warns. These need dedicated extinguishers and systems.

Legal reference and technical reference

The legally binding reference in Egypt is the Egyptian Code for the Design and Implementation of Fire Protection for Buildings, 2026 edition (Ministerial Decree No. 355 of 2026), with the requirements of the General Directorate of Civil Protection (Ministry of Interior). NFPA 10 is a technical design reference, not mandatory law in Egypt by itself. Manufacturer instructions apply alongside both.

Recharging and maintenance

A CO2 extinguisher must be recharged after any use, even partial. The charge is checked by weighing and comparing with the weight marked on the extinguisher. NFPA 10 sets a hydrostatic test for CO2 cylinders every 5 years and does not allow them the 10-year interval available to some other cylinders. AZEIDK Egypt provides periodic maintenance and recharging as part of its fire extinguisher solutions. For inspection and records, see our fire extinguisher maintenance and recharging guide.

Common mistakes when buying and installing CO2 extinguishers

  • Relying only on CO2 in a space where most of the fire load is paper, wood and cardboard.
  • Placing a dry chemical extinguisher inside a server room to protect the equipment.
  • Putting a large wheeled unit inside a small electrical room, or where it is hard to move.
  • Mounting the extinguisher deep inside the room, away from the door, so the user must pass the fire to reach it.
  • Keeping old units with metal horns in service.
  • Returning an extinguisher to its place after partial use without weighing and recharging it.
  • Ordering by kilograms only, without stating the configuration (portable or wheeled) and the type of space.

Frequently asked questions

Is a CO2 extinguisher suitable for every type of fire?

No. It suits flammable liquids and electrical equipment. OSHA does not recommend it for ordinary combustibles, which may re-ignite.

What CO2 extinguisher size does an electrical room need?

There is no single size. It depends on room size, number of panels and the user, and the design sets quantity and layout. PYRAMID CO2 comes in 2 to 30 kg.

Why not use a dry powder extinguisher in a server room?

Powder residue sticks to equipment and can cause corrosion. The proposed 2026 text of NFPA 10 states that dry chemical extinguishers shall not be installed to protect delicate electronic equipment.

Is using a CO2 extinguisher in a closed room dangerous for people?

Yes. The gas lowers oxygen. OSHA warns never to use it in a confined space with people present without respiratory protection. Use it from near the exit, then leave and ventilate.

How do I know a CO2 extinguisher needs recharging?

After any use. In maintenance, the charge is checked by weighing against the marked weight, per the manufacturer’s instructions.

Conclusion

A CO2 fire extinguisher suits electrical and server rooms because it does not conduct electricity and leaves no residue. Know its limits: it is not enough for solids, it lowers oxygen in closed spaces, and it needs a non-metallic horn and a sound hose. Start from the space and the user, pick the PYRAMID size and configuration, mount it near the exit, and recharge after every use.

Equipping electrical or server rooms in your facility? Describe the spaces and their sizes, and we will suggest PYRAMID CO2 sizes and configurations with the datasheet for each product. Talk to the AZEIDK Egypt team

Share this article