ANSUL SAPPHIRE Novec 1230 Clean Agent Fire Suppression System
Brand
Ansul
View Product
→
AZEIDK Solutions
Integrated Engineering Solutions for Safer Facilities
Fire protection, low current systems, and electromechanical solutions.
Fire Protection & Life Safety
Fire Alarm SystemsAddressable and conventional detection and alarm→Fire Fighting SystemsSprinkler networks, fire pumps and components→Special Fire Suppression SystemsGas and aerosol systems for sensitive equipment→Kitchen Fire Suppression SystemsHood and cooking equipment protection→Smoke Extraction & Emergency VentilationSmoke control to keep escape routes usable→Fire-Rated Doors & Emergency ExitsFire-rated doors and exit hardware→Electromechanical & Contracting
HVAC, Electrical & Plumbing WorksElectromechanical (MEP) works coordinated with fire protection and low current systems→Smart Buildings & Systems IntegrationNetworks, CCTV, access control, fire alarm and BMS working as one→General ContractingProject delivery and trade coordination, with life safety built in from day one→Civil Defense, Salamah & Balady TransactionsSubmitting and following up Salamah licences (instant and non-instant) and Balady requests, preparing technical reports and closing inspection notes→Engineering delivery process
Regulatory & compliance support

Fire Alarm Systems
Addressable and conventional fire alarm systems, designed, installed and tested by AZEIDK
Need the right engineering solution?
Talk to the AZEIDK Team →
Hood Safer CabinetSafer is an automatic fixed fire suppression system that protects the inside of electrical panels, control cabinets and server racks. Pressurised detection tubing runs inside the cabinet; when the temperature reaches about 100 °C or a flame touches it, the tube bursts at the fire and releases FK-5-1-12 directly onto the source, with no power supply or separate detectors needed.
| System | Hood Safer CabinetSafer automatic fixed fire suppression system for electrical applications |
|---|---|
| Agent | FK-5-1-12 |
| Detection and actuation | Pressurised linear detection tubing that ruptures at about 100 °C or on flame contact and forms a diffuser; no external power source needed |
| System type | Direct Low Pressure |
| Cylinder pressure | 15 bar (nitrogen) |
| Detection tube | CS400, 6 mm, minimum bend radius 60 mm, optimum 150 mm |
| Maximum distance | 20 m from the cylinder to the furthest burst point |
| Monitoring | CS300 volt-free pressure switch (NO/NC) that can signal the fire alarm panel |
| Mounting | Vertical, never more than 45 degrees from vertical, in an area not above 60 °C |
| Maintenance | Visual inspection every 3 months and full service every 12 months per BS 5306-3 |
No. Detection and actuation are mechanical through the pressurised tubing. The CS300 pressure switch can be added to signal the fire alarm panel.
Yes. Adjacent cabinets can be covered with tee connectors, provided the distance from the cylinder to the furthest point does not exceed 20 m.
Specifications are taken from the official Hood Safer CabinetSafer Technical Manual. You can download the datasheet from AZEIDK. Supplied by AZEIDK with design, installation and maintenance.
View the product’s full specifications and technical information in the official catalogue.