Fire Valves
American Fire Control (AFC) Vertical Indicator Post – Model 5100
Brand
American Fire Control (AFC)
View Product
→
AZEIDK Solutions
Integrated Engineering Solutions for Safer Facilities
Fire protection, low current systems, and electromechanical solutions.
Fire Protection & Life Safety
Fire Alarm SystemsAddressable and conventional detection and alarm→Fire Fighting SystemsSprinkler networks, fire pumps and components→Special Fire Suppression SystemsGas and aerosol systems for sensitive equipment→Kitchen Fire Suppression SystemsHood and cooking equipment protection→Smoke Extraction & Emergency VentilationSmoke control to keep escape routes usable→Fire-Rated Doors & Emergency ExitsFire-rated doors and exit hardware→Electromechanical Works
HVAC, Electrical & Plumbing WorksElectromechanical (MEP) works coordinated with fire protection and low current systems→Engineering delivery process
Regulatory & compliance support

Fire Alarm Systems
Addressable and conventional fire alarm systems, designed, installed and tested by AZEIDK
Need the right engineering solution?
Talk to the AZEIDK Team →
The American Fire Control (AFC) BFG-300 and BFG-301 Grooved Fire Butterfly Valves are designed to control and isolate water flow within fire protection piping systems.
The valve features a compact design, manual gear operation, a clear valve-position indicator and a built-in supervisory switch.
This product page combines two models from the same product family:
• BFG-300.
• BFG-301.
The catalogue presents both models as one product family with the same image and main technical specifications, so they are grouped under one product page.
Key Features:
• Fire protection butterfly valve.
• Grooved-end connections.
• Design complies with API 609.
• Ductile iron disc fully encapsulated with EPDM.
• Bubble-tight shutoff.
• Flag-type valve-position indicator.
• Low operating torque.
• High cycle life.
• Built-in supervisory switch.
• Suitable for connection to fire alarm and monitoring systems.
• Manual gearbox operation.
• Top gearbox mounting flange to ISO 5211.
• Groove dimensions comply with AWWA C606.
• Working pressure of 300 PSI or 21 bar.
• Operating temperature from 0°C to 80°C.
• Suitable for indoor and outdoor use.
• Fusion-bonded epoxy coating to AWWA C550.
• UL Listed as shown in the catalogue.
• FM Approved as shown in the catalogue.
• Available in sizes from 2 to 12 inches.
Operation:
The valve is operated using a manual handwheel connected to a gearbox.
Rotating the handwheel causes the gearbox to rotate the internal valve disc through an angle of up to 90 degrees:
• When the disc is parallel to the water flow, the valve is open.
• When the disc is perpendicular to the water flow, the valve is closed.
The external indicator provides a visual indication of valve position. The built-in supervisory switch can also send a signal to the fire alarm or monitoring system when the valve moves away from its required position.
Available Sizes:
• 2 inches.
• 2.5 inches.
• 3 inches.
• 4 inches.
• 6 inches.
• 8 inches.
• 10 inches.
• 12 inches.
Valve Construction Materials:
• Valve body: Ductile Iron ASTM A536 65-45-12.
• Stem shaft: Stainless Steel 416.
• Disc: Ductile iron encapsulated with EPDM.
• Stem O-rings: EPDM.
Gear Operator Materials:
• Gear housing: Ductile Iron ASTM A536 65-45-12.
• Gear cover: Ductile Iron ASTM A536 65-45-12.
• Worm: Carbon Steel AISI 1045.
• Worm gear: Ductile Iron ASTM A536 65-45-12.
• Handwheel: Ductile Iron ASTM A536 65-45-12.
Supervisory Monitoring:
The valve includes a built-in supervisory switch that can be connected to a fire alarm system to monitor the valve position.
This helps detect unauthorized or accidental movement of the valve from the fully open position toward a partially or fully closed position.
Applications:
• Automatic sprinkler systems.
• Fire hydrant systems.
• Fire hose networks.
• Fire pump rooms.
• Fire protection water-distribution lines.
• Fire network zone isolation.
• Grooved piping systems.
• Indoor and outdoor fire protection systems.
• Systems requiring valve-position monitoring from the fire alarm panel.
Standards and Approvals Shown in the Catalogue:
• UL Listed.
• FM Approved.
• API 609.
• AWWA C606 for grooved-end dimensions.
• AWWA C550 for the protective coating.
• ISO 5211 for the operator mounting flange.
The appropriate valve size should be selected according to pipe diameter, flow rate, working pressure, hydraulic calculations and project requirements.
View the product’s full specifications and technical information in the official catalogue.