Tornatech Fire Pump Controllers: GPx Electric and GPD Diesel Models and What to Check in the Submittal

Tornatech Fire Pump Controllers: GPx Electric and GPD Diesel Models and What to Check in the Submittal

Tornatech fire pump controllers are among the names that appear most often in Saudi fire pump room specifications. They come in two main families: GPx controllers for electric fire pumps and the GPD controller for diesel fire pumps. This article sets out what the official data sheets say about each model, how to choose the starting method for the motor, and what to check in the submittal before supply.

Tornatech is one of the suppliers AZEIDK works with on firefighting system projects in the Kingdom, within technical supply, installation and testing, commissioning and handover.

Key takeaways

  • Tornatech builds controllers in Canada for all markets, in Belgium for European markets and in Dubai for the Middle East and Asia.
  • The GPD diesel controller and the GPx electric controllers are built to NFPA 20, UL listed to UL 218 and FM approved under Class 1321/1323, according to the data sheets.
  • Controllers built in Dubai are supplied as standard with a 55°C ambient rating, which matters for Saudi pump rooms.
  • Pick the starting method of an electric controller from the motor size and the capacity of the power source, not from price alone.
In this article
  1. Which models does Tornatech offer?
  2. The GPD controller for diesel fire pumps
  3. GPx controllers for electric fire pumps: choosing the starter
  4. Why the 55°C rating matters in Saudi Arabia
  5. What to check in a Tornatech submittal
  6. Maintenance and testing
  7. Frequently asked questions

Which models does Tornatech offer?

Tornatech publishes a separate data sheet for each model. The models seen most often on fire pump projects are:

ModelPump typeStarting method per data sheet
GPAElectricFull voltage, across the line
GPSElectricReduced voltage, electronic soft starter
GPYElectricReduced voltage, wye-delta open transition
GPDDieselEngine cranking from two batteries with two independent chargers

All of them carry a digital operator interface (ViZiTouch on current versions) that shows pressure and status and records events and pressure with date and time. Tornatech also offers JPx jockey pump controllers, which keep the system pressured; see jockey pump sizing and pressure settings.

The GPD controller for diesel fire pumps

The official GPD data sheet (February 2019) lists:

  • Approvals: built to the latest edition of NFPA 20, UL listed to UL 218 Fire Pump Controllers, CSA C22.2 No. 14, FM Global Class 1321/1323, seismic certification, with CE marking as an option.
  • Charging: two independent, fully automatic battery chargers with 10 A continuous and 500 mA trickle charge, plus voltage and current readings for each battery.
  • Pressure sensing: an externally mounted pressure transducer with a protective cover, rated and calibrated for 0 to 500 psi, with a run test solenoid valve.
  • Pressure and event recorder: events are kept in memory for the life of the controller under normal operation and can be downloaded by USB.
  • Alarms: engine fail to start, high engine temperature, low oil pressure, overspeed, low fuel level, battery or charger failure and more.
  • Remote alarm contacts: engine run, common controller trouble, common engine trouble and common pump room trouble, which are wired to the fire alarm panel or the building management system.

For the full diesel set, see diesel fire pump components under NFPA 20.

GPx controllers for electric fire pumps: choosing the starter

Across-the-line starting (GPA) is the simplest, but it draws a high starting current. GPS or GPY become relevant when the motor is large or the transformer or generator has limited capacity. The GPY data sheet also lists:

  • A circuit breaker with an instantaneous trip of not more than 20 times the motor full load current.
  • A locked rotor protector that trips between 8 and 20 seconds.
  • Suitability as service entrance equipment.
  • A manual emergency handle for direct-on-line starting.

The final choice rests on the electrical designer’s calculations and the consultant’s specification. See the general criteria in fire pump controller selection and the wiring in fire pump controller wiring diagram.

Why the 55°C rating matters in Saudi Arabia

The standard ambient range in the data sheets is 4 to 40°C, with an option up to 55°C. The data sheets state that controllers built in Dubai by Tornatech FZE are supplied with the 55°C rating as standard. Many Saudi pump rooms are not air-conditioned, so ask the supplier to state the place of manufacture and the ambient rating in the quotation and in the submittal.

For the enclosure, the standard is NEMA 2 (IP31), with options for NEMA 12, 3R, 4 and stainless steel 4X, and IP54 up to IP66. Pump rooms exposed to spray or coastal sites deserve a higher rating.

What to check in a Tornatech submittal

  1. The full model number, supply voltage and frequency, and motor power.
  2. Evidence of UL listing and FM approval for that exact model, as described in how to check a fire pump’s UL and FM approval.
  3. Place of manufacture and ambient temperature rating.
  4. Enclosure rating.
  5. The list of remote alarm contacts needed for the fire alarm interface.
  6. Dimensional and wiring drawings from the data sheet.

Maintenance and testing

The event recorder is a useful tool during weekly and annual tests, because it shows cut-in and cut-out pressure, the number of starts and any earlier alarm. See fire pump controller maintenance and testing, and for repeated alarms see fire pump faults and troubleshooting. For the engine itself, see Clarke diesel fire pump engines.

Frequently asked questions

Are Tornatech controllers UL listed and FM approved?

The GPD and GPY data sheets state UL listing to UL 218 and FM Global approval under Class 1321/1323. Always check the exact model being supplied.

What is the difference between GPA, GPS and GPY?

All three control electric fire pumps. GPA starts the motor directly at full voltage, GPS uses an electronic soft starter, and GPY uses a wye-delta connection to reduce starting current.

Can the event log be downloaded from the controller?

Yes. The GPD data sheet states that pressure and event data are shown on the display and can be downloaded through a USB port.

Does AZEIDK supply Tornatech controllers on their own?

Tornatech is one of the suppliers AZEIDK works with, and the controller usually comes as part of a complete fire pump set to the project specification. See our fire pumps section.

Equipping a pump room or replacing an old controller? Send AZEIDK the pump, motor and power source data, and our team will propose the right controller and prepare the submittal. Request a quote from AZEIDK