SFFECO Carbon Dioxide (CO2) System

High-pressure carbon dioxide extinguishing system using alloy steel cylinders, with electrically operated master valves and pressure-actuated slave valves. It can be designed for total flooding or local application and leaves no residue after discharge.
Brand
SFFECO Carbon Dioxide (CO2) System

Product Details

Product Overview

High-pressure carbon dioxide extinguishing system using alloy steel cylinders, with electrically operated master valves and pressure-actuated slave valves. It can be designed for total flooding or local application and leaves no residue after discharge.

ModelCarbon Dioxide (CO2) System
System typeHigh-pressure CO2
Available cylinder range2 kg (4.4 lbs) to 100 kg (220 lbs)
Standard cylinder capacity45 (100 lbs)
Operating pressure58 bar (850 psi) at 21 °C (70 °F)
Operating temperature-18 °C to 54.4 °C (0 °F to 130 °F)
ActuationPneumatic, mechanical, electrical
Application methodsTotal flooding or local application
Design standardANSI/NFPA 12
Listing statedUL Listed

Typical applications

  • Generator and engine rooms
  • Electrical and electronics production areas
  • Printing presses and paint booths
  • Flammable material stores

Source: SFFECO official product page and official datasheet. Supplied in Saudi Arabia by AZEIDK with installation and technical support.

Where the SFFECO CO2 system fits

A high-pressure CO2 extinguishing system with alloy steel cylinders and electrically operated master valves, suited to generator and transformer rooms, unoccupied electrical rooms and flammable liquid stores.

  • Gas extinguishing with no residue
  • Electrically operated master valves
  • Suited to unoccupied spaces
  • Supply, installation, configuration and handover by the AZEIDK technical team

AZEIDK supports this product from selection and supply through installation, programming, testing and maintenance across Saudi Arabia. Send us your drawings or BOQ to receive a quotation.

Where it is used in Saudi projects

The SFFECO CO2 system protects normally unoccupied spaces in factories, power and desalination plants and oil and gas facilities, such as generator, engine and transformer rooms, electrical rooms and flammable liquid stores. Because CO2 at extinguishing concentration is dangerous to people, the system is designed with a lock-out valve, a time delay unit and a pre-discharge siren, and the cylinders sit in a room that stays within the 54.4 °C operating limit, which needs attention in equipment rooms during summer.

Key specifications explained (from the datasheet, UL listing EX27524)

  • High-pressure, stored-pressure units with nominal cylinder capacities of 2.0, 4.5, 6.6, 9, 22.5, 45, 53, 66, 80 and 100 kg.
  • Operating pressure 58 bar (850 psi) at 21 °C, and an operating range of -18 °C to 54.4 °C.
  • Master valves of solenoid or differential type, with pressure-operated slave valves.
  • Direction valves and lock-out valves from 1 in. to 2 in., to serve more than one zone or isolate the system during maintenance.
  • Actuation components: manual actuator, pressure-operated siren, time delay unit and pressure switch.
  • Battery frames for 2 to 12 cylinders with manifold, and a mechanical weight loss unit to detect cylinder loss.

Related SFFECO products

For occupied spaces such as server rooms there is the SFFECO 1230 clean agent system, and for small rooms the SFM6 to SFM45 automatic modular extinguishers. See the full range on the SFFECO page and under special fire suppression systems.

FAQ about the SFFECO CO2 system

Is a CO2 system suitable where staff are present?

It is normally used in unoccupied spaces. Where people are sometimes present, the space must be evacuated before discharge using the time delay, alarm and lock-out valve as NFPA 12 requires. For occupied spaces a clean agent system is preferred.

What cylinder sizes are available?

From 2 kg up to 100 kg according to the listing. The 45 kg cylinder is the common project size, and several cylinders are grouped on a frame and manifold for large spaces.

Is the system listed?

The attached datasheet is the UL listing page for the system under file EX27524, and design follows ANSI/NFPA 12.

Technical Documents

Product Catalogue

View the product’s full specifications and technical information in the official catalogue.

This site is registered on wpml.org as a development site. Switch to a production site key to remove this banner.