ANSUL INERGEN 200-Bar Inert Gas Fire Suppression System

ANSUL INERGEN 200-bar IG-541 inert gas fire suppression for server, telecom and archive rooms, safe for occupied spaces, designed to NFPA 2001, UL and ULC listed and FM approved.
Brand
أسطوانات نظام الإطفاء بالغاز الخامل ANSUL INERGEN

Product Details

Product Overview

The ANSUL INERGEN system from Johnson Controls is an automatic inert gas fire suppression system using INERGEN agent, a blend of nitrogen, argon and carbon dioxide. It puts out the fire by lowering the oxygen in the room below the level that supports combustion, while the atmosphere stays breathable for people leaving the area, and it leaves no residue on equipment.

SystemANSUL INERGEN 200-bar inert gas fire suppression system
AgentINERGEN (IG-541): 52% nitrogen, 40% argon, 8% carbon dioxide
How it worksLowers oxygen to about 12.5% while raising carbon dioxide to about 3%
Fire classesA, B and C
Charging pressure200 bar at 21 °C (2900 psi at 70 °F)
ContainersHigh-strength alloy steel, red finish, forged brass valve with gauge, one size
ActuationAutomatic through the AUTOPULSE control system, or manual/pneumatic lever actuators
Operating temperature0 to 54 °C
Standards and listingsNFPA 2001, UL and ULC listed, FM approved

Applications

  • Server rooms, data centres and raised floors
  • Telecom rooms and electrical switchgear
  • Museums, libraries and archive rooms
  • Occupied spaces with sensitive or irreplaceable equipment

Frequently asked questions

Is INERGEN safe for people?

According to the official datasheet, the agent allows breathing in the reduced-oxygen atmosphere, because the rise in carbon dioxide to about 3% stimulates breathing. The area must still be evacuated following safety procedures.

Does the agent harm the environment?

No. INERGEN is a blend of gases found in the atmosphere, with no ozone depletion and no contribution to global warming, as stated by the manufacturer.

How is the number of containers decided?

By design and hydraulic calculation based on the room volume and NFPA 2001. The AZEIDK technical team prepares the design and the room integrity test.

Specifications are taken from the official Ansul datasheet (Form No. F-2001292-05). You can download the datasheet from AZEIDK. Supplied by AZEIDK in Saudi Arabia with design, installation and maintenance.