PYRAMID AFFF Foam Extinguishers: 6 to 45 L and When to Use Them

PYRAMID AFFF Foam Extinguishers: 6 to 45 L and When to Use Them

A diesel, petrol or oil fire on a workshop floor does not behave like a wood or cardboard fire. The liquid spreads, floats and gives off vapour that can reignite after the flames seem to be out. The AFFF foam fire extinguisher is built for this hazard: it knocks down the flames and also covers the liquid surface with a layer that holds the vapour back.

This article covers PYRAMID AFFF foam extinguishers in their four sizes (6, 9, 25 and 45 litres): when foam is the right choice, when to avoid it, where to install it, and what NFPA 10 recommends for inspection and maintenance. For the full extinguisher range, see fire extinguishers from AZEIDK Egypt.

Key takeaways

  • AFFF foam is mainly for flammable liquid fires such as oils and petroleum products. It forms a layer that cools the surface and prevents reignition.
  • PYRAMID foam extinguishers come in 6 and 9 L portable units, and 25 and 45 L wheeled units for fuel and flammable liquid storage areas.
  • Foam is water-based. Do not use it on live electrical equipment unless the label clearly allows it. For electrical panels, use CO2.
  • Standard AFFF performs poorly on liquids that mix with water, such as alcohols and ketones. These need alcohol-resistant foam.
  • Under NFPA 10 (2026 edition), a technical reference and not Egyptian law: monthly inspection, annual maintenance, an internal examination of foam units every 3 years, and a hydrostatic test every 5 years.
In this article
  1. How does an AFFF foam fire extinguisher work on liquid fires?
  2. PYRAMID foam extinguisher specifications from the datasheets
  3. When to choose a foam extinguisher, and when not to
  4. Where to install foam extinguishers: examples
  5. Inspection and maintenance: what NFPA 10 (2026 edition) recommends
  6. Common mistakes with foam extinguishers
  7. Frequently asked questions
  8. Conclusion

How does an AFFF foam fire extinguisher work on liquid fires?

AFFF stands for aqueous film-forming foam. The agent leaves the extinguisher as a water-based solution that mixes with air at the nozzle and turns into foam. On a hydrocarbon liquid such as petrol or diesel, the foam spreads and works in three ways at once:

  • Smothering: it separates the liquid surface from oxygen.
  • Vapour suppression: it limits the flammable vapour rising from the liquid. The vapour burns, not the liquid itself.
  • Cooling: the water content lowers the temperature of the surface and nearby metal parts.

Dry powder knocks down flames fast but leaves no barrier, so a hot liquid can reignite. Foam stays on the surface. Compare all types in our guide to fire extinguisher types and uses.

PYRAMID foam extinguisher specifications from the datasheets

The PYRAMID page at AZEIDK Egypt lists AFFF foam extinguishers in two groups. The 6 and 9 L portable units conform to the European standard EN3 and to Egyptian standards, and are approved by the Egyptian Organization for Standardization and Quality (EOS) with the Egyptian quality mark. The Egyptian standard number for each model is given on its datasheet and conformity certificate. The 25 and 45 L units are wheeled, and the page describes them for fuel and flammable liquid storage areas. The main datasheet data for each group:

Item6 and 9 L (portable)25 and 45 L (wheeled)
Working pressure17.5 bar17.5 bar
Test pressure35 bar35 bar
Burst pressure70 bar or more70 bar or more
PropellantExternal CO2 cartridge, or stored pressure (nitrogen)External cartridge, or stored pressure (nitrogen)
Operating temperature range-20 °C to +70 °C-20 °C to +70 °C
CylinderSteel with red electrostatic polyester coating, or stainless steelStainless steel, or steel with red electrostatic coating
Valve headNickel-chrome plated brass with pressure gauge and safety relief valveNickel-chrome plated brass with pressure gauge and safety relief valve
DischargeHose with nozzle, intermittent or continuous discharge5 m hose with nozzle, intermittent or continuous discharge
Mounting and mobilitySteel wall bracket and a base standTwo main wheels and a front support
Warranty2 years against manufacturing defects2 years against manufacturing defects

The fire rating of each size is printed on the label. Use it for quantity and spacing.

When to choose a foam extinguisher, and when not to

Foam is for hydrocarbon liquids that do not mix with water. The table covers the cases we meet on site:

HazardIs AFFF suitable?Note
Petrol, diesel, lubricating oil, hydraulic oilYesThe main use of foam, with the benefit of preventing reignition
Ordinary solids (wood, paper, cardboard)Check the labelMany foam extinguishers carry a class A rating; confirm it on the label
Alcohols, ketones and solvents that mix with waterLimitedThese liquids break down standard foam and need alcohol-resistant foam
Live electrical equipmentNoIsolate power first, and use a CO2 extinguisher on panels and electrical equipment
Cooking oil in commercial kitchensDo not rely on itCommercial kitchens use a wet chemical system over the hood
Combustible metalsNoNeed special class D agents

Why not use foam on electrical equipment?

Foam is a conductive water-based solution. EN 3-7 includes a dielectric test, and an extinguisher that does not pass it must carry a warning not to use it on live electrical equipment. The published PYRAMID foam datasheets do not state a result for this test, so we treat these units as not for energized equipment. In electrical panel rooms, the right choice is PYRAMID CO2 extinguishers: the gas does not conduct electricity and leaves no residue.

Polar solvents: a note for paint and chemical stores

Liquids that mix with water, such as alcohols, ketones and esters, pull water out of the foam, so the blanket breaks down quickly. In a store holding mainly these materials, review the foam agent type with the supplier before approval.

Where to install foam extinguishers: examples

Typical Egyptian sites where foam fits. The final choice follows the risk assessment and the drawings approved by the civil protection authority:

  • Car service workshops and garages: fuel and engine oil leaks around lifts and oil-change bays. A 6 or 9 L unit near the entrance to the work area, not directly over the leak point.
  • Production lines with hydraulic or cutting oils: presses, injection moulding and machining. Portable units beside the machines, with a CO2 unit for the control panels.
  • Drum stores and flammable liquid stores: this is where the 25 and 45 L wheeled units fit. They deliver more foam and more reach with a 5 m hose. For when a wheeled unit is needed and how to size it, see wheeled fire extinguishers.
  • Fuel and oil loading and unloading areas: a wheeled unit at the edge of the area, on a level path where it is easy to pull.

Place each unit on the exit path, away from the likely spill, within the datasheet operating range (-20 °C to +70 °C). For quantity, travel distance and mounting height, see how many fire extinguishers you need.

Inspection and maintenance: what NFPA 10 (2026 edition) recommends

The binding reference in Egypt is the Egyptian Code for the Design and Implementation of Fire Protection for Buildings, 2026 edition (Ministerial Decree No. 355 of 2026), together with the requirements of the General Directorate of Civil Protection (Ministry of Interior). NFPA 10 is a technical reference for extinguisher inspection and maintenance. The points below come from the 2026 edition as published by NFPA in the Second Draft Report of its revision cycle. They are NFPA guidance, not Egyptian law, and apply together with the manufacturer’s instructions:

ActionNFPA 10 frequencyWhat to check on a foam unit
Visual inspectionMonthly, at intervals not exceeding 31 daysUnit in place and unobstructed, gauge in the green, seal intact, hose and nozzle clear
MaintenanceAnnually, by a qualified technicianCylinder, label and bracket condition; on wheeled units, hose and wheels
Internal examinationEvery 3 years for foam unitsDischarge the unit, examine the cylinder inside, then recharge with the agent the manufacturer specifies
Foam agent replacementPer the manufacturer, not exceeding the 5-year hydrostatic test intervalFollow the manufacturer’s period if it is shorter
Hydrostatic testEvery 5 yearsPressure test of the cylinder with water

The same edition allows inspection by an electronic monitoring system instead of manual inspection, with the approval of the authority having jurisdiction. It also allows a performance-based inspection programme with intervals not exceeding 90 days, which needs that approval and a site-specific technical justification. On units with an external CO2 cartridge, check the cartridge, its seal and its weight to the manufacturer’s instructions, as it is a separate part from the cylinder. For recharging and testing details, see fire extinguisher maintenance and recharging, and for periodic maintenance programmes, AZEIDK Egypt services.

AFFF contains fluorinated compounds, so collect replaced or discharged foam and dispose of it to the manufacturer’s instructions. Do not wash it into drains.

Common mistakes with foam extinguishers

  • Aiming the foam hard at the liquid surface, which splashes burning fuel and spreads the fire. Aim at a wall or barrier behind the spill, or let the foam flow gently onto the surface.
  • Putting a single foam unit in an electrical panel room because it “puts out everything”.
  • Relying on standard foam in a store of water-miscible solvents without checking the agent type.
  • Placing the unit right beside the leak source, where it cannot be reached once the fire starts.
  • Putting off the internal examination and agent replacement because the gauge still reads green.
  • Leaving foam units in direct summer sun on sites where the temperature can exceed the operating range.
  • Choosing a 6 L unit for a large drum store instead of a wheeled unit.

Frequently asked questions

What is the difference between foam and dry powder on a petrol fire?

Powder knocks the flames down fast but leaves no barrier, so the fire can return if the liquid stays hot. AFFF covers the surface with a layer that limits vapour and cools the liquid, which lowers the chance of reignition.

Can I use a foam extinguisher on an electrical panel?

We do not recommend it. Foam is water-based, and the published datasheet does not state that the unit passed the EN 3-7 dielectric test. Isolate the power and use a CO2 extinguisher on electrical equipment.

When should I choose 25 or 45 L instead of 6 or 9 L?

When the stored liquid quantity or the possible spill area is large, as in drum stores and fuel storage areas. The large sizes are wheeled and have a 5 m hose, so they give more foam and a longer safe distance.

How often is the foam charge replaced?

Replace the foam agent at the interval the manufacturer sets. Under NFPA 10 (2026 edition) that interval must not exceed the 5-year hydrostatic test, and foam units also get an internal examination every 3 years. This is technical guidance, not Egyptian law.

Is a foam extinguisher suitable for a commercial kitchen?

For cooking oil fires in commercial kitchens, the usual solution is a wet chemical system over the hood. See kitchen fire suppression systems.

Conclusion

An AFFF foam extinguisher is the right tool when the main hazard is fuel or oil that does not mix with water, because it puts the fire out and stops it reigniting. Choose the size by liquid quantity and possible spill area, place it on the exit path away from the leak source, and keep a CO2 unit beside any electrical equipment. Monthly checks, the internal examination, on-time agent replacement and periodic testing keep it ready.

Running a workshop or an oil store and need to decide sizes and locations? Send us the liquids, quantities and floor area, and we will propose a PYRAMID layout with the datasheet for each size. Talk to the AZEIDK Egypt team

References: PYRAMID fire extinguishers (AZEIDK Egypt, in Arabic); Datasheet: AFFF foam extinguishers 6 and 9 L (AZEIDK Egypt, in Arabic); Datasheet: AFFF foam extinguishers 25 and 45 L (AZEIDK Egypt, in Arabic); NFPA 10, Second Draft Report (Annual 2025 revision cycle, 2026 edition) (NFPA); Fact File 97: EN 3-7 Dielectric Test (Fire Industry Association); Are You Alcohol Resistant? (Firehouse)