HoodSafer for Grill Shops, Shawarma Shops and Bakeries in Egypt

HoodSafer for Grill Shops, Shawarma Shops and Bakeries in Egypt

Grill shops, shawarma shops and bakeries in Egypt are not ordinary restaurant kitchens. An open charcoal grill runs for long hours, a chip fryer sits next to it, and one long hood along the shopfront collects the grease from both. Asking for “a kitchen system” is not enough. You need to know which appliance the system actually covers and which needs a written decision from the manufacturer.

This article explains how a grill restaurant fire suppression system from HoodSafer handles the grill, the fryer and the long hood. It is based on the HoodSafer technical manual supplied by the AZEIDK Egypt kitchen fire suppression team, and states plainly what the manufacturer’s appliance list leaves out: the vertical shawarma broiler and bakery ovens.

Key takeaways

  • The HoodSafer appliance table lists charcoal, wood, gas, electric and lava stone grills, single and double pan fryers, grill plates, rangetops and woks.
  • Under Table 1 of the manual, each grill up to 70 x 70 cm needs one H1 nozzle; another section of the same manual conflicts with this, so confirm with the manufacturer. A single pan fryer up to 60 x 60 cm needs one H2 nozzle, counted as two flow points.
  • Open flame grills use a 260 °C thermobulb link. Fryers use 182 °C.
  • The vertical shawarma broiler and bakery ovens are not in the appliance table. Do not assume coverage without written manufacturer confirmation.
  • A long hood needs one extra filter nozzle for every 2 m beyond the first 3 m, and may need more than one cylinder.
In this article
  1. Why a grill restaurant fire suppression system needs its own calculation
  2. Which cooking appliances does HoodSafer cover?
  3. The grill: open charcoal and a higher rated link
  4. The fryer: the most dangerous appliance in the shop
  5. Shawarma and bakery ovens: what the manufacturer’s list does not include
  6. The long hood: how nozzles grow with length
  7. A worked example for a grill shop
  8. Installation points for hot shops
  9. Common mistakes in grill shops and bakeries
  10. Frequently asked questions
  11. Conclusion

Why a grill restaurant fire suppression system needs its own calculation

In an ordinary restaurant kitchen the load is spread over a rangetop, a fryer and a grill plate. In a grill shop the main load is an open charcoal or wood grill. Flame, embers and airborne grease rise straight into the hood filters and the duct, and with service running from midday to after midnight, grease builds up quickly.

According to Markel, citing NFPA 96 (2017 edition, Table 11.4), exhaust systems serving solid fuel cooking should be inspected monthly for grease buildup. That is the shortest interval in the table, against quarterly for high-volume and semiannually for moderate-volume cooking; check the edition in force at design stage. This is guidance from a US technical standard, not a legal requirement in Egypt, where the binding reference is the Egyptian fire code, 2026 edition, but it shows how high the risk is.

In a bakery the main appliance is a closed oven, sometimes with a fryer or grill plate beside it. The first question is not system size but which appliances under the hood are on the system’s list.

Which cooking appliances does HoodSafer cover?

HoodSafer is a wet chemical kitchen suppression system designed and manufactured in Turkey. The HS series is fully mechanical and needs no pressurised component for actuation; the HSP series uses pneumatic detection. The system holds EN 17446:2021 certification with BSI Kitemark (KM 767382) and is approved by the General Directorate of Civil Protection in Egypt, as shown on the HoodSafer page at AZEIDK Egypt.

The manual requires nozzles for every hood section and for every appliance under the hood. Its Table 1 gives the largest surface one nozzle covers:

Appliance (as in the manufacturer’s table)Max surface per nozzleNozzle typeFlow pointsNozzle height above surface
Charcoal grill70 x 70 cmH1190 to 115 cm
Wood grill70 x 70 cmH1190 to 115 cm
Gas, electric, lava stone or ceramic stone grill70 x 70 cmH1190 to 115 cm
Grill plate60 x 120 cmH3190 to 115 cm
Rangetop70 x 70 cmH3190 to 115 cm
Single pan deep fat fryer with drip board60 x 60 cmH2290 to 115 cm
Double pan deep fat fryer2 x (26 x 60) cmH2290 to 115 cm
Bratt pan60 x 60 cmH2290 to 115 cm
Wok70 cm diameter, 20 cm depthH1170 to 115 cm

The nozzle is best placed over the centre of the cooking surface, or inside its boundary aimed at the centre. An appliance larger than the maximum area gets more nozzles, as the manual’s examples for oversized fryers show.

The grill: open charcoal and a higher rated link

A charcoal grill in a kofta and kebab shop is usually longer than 70 cm. Following the table, a grill 140 cm long and 70 cm wide is two protection areas: two H1 nozzles and two flow points. So measure the real grill surface instead of just writing “grill” on the appliance list.

One point must be settled with the manufacturer. Table 1 and the equipment protection section (2.3) of the manual give an H1 nozzle for all grill types, while section 1.13, which describes the nozzle types, says the H2 nozzle is used for coal, wood and gas barbecues. This article follows Table 1 because it is the design table, but the grill nozzle type should be confirmed in writing by the manufacturer before design approval, since an H2 counts as two flow points and changes the total.

Detection also changes. The system uses three UL listed glass thermobulb links:

  • 141 °C (blue): appliances without an open flame.
  • 182 °C (purple): fryers, rangetops, skillets and woks.
  • 260 °C (black): barbecues and grills with an open flame.

A 141 °C or 182 °C link above a charcoal grill can cause an unwanted discharge during normal cooking. So state the fuel type on the design data: charcoal, wood, gas or electric.

The fryer: the most dangerous appliance in the shop

The manual names oil and animal fat appliances as the source of the most dangerous fires, so they get the H2 nozzle, counted as two flow points. One H2 covers a single fryer up to 60 x 60 cm, or a double fryer with pans up to 26 x 60 cm and a drip board no wider than 5 cm. A larger fryer needs two.

Oil fires cannot be put out with water. See our article on oil fires in commercial kitchens. The HoodSafer wet chemical agent is designed and tested for Class K fires (US classification) and Class F fires (European classification).

Shawarma and bakery ovens: what the manufacturer’s list does not include

The appliance table in the HoodSafer HS technical manual on the AZEIDK site does not list the vertical shawarma broiler (the rotating spit in front of a vertical heat source) or bakery ovens of any type, and the brand page does not name them either.

This does not mean the shop needs no protection. It means three practical things:

  • Do not assume a grill or grill plate nozzle protects the shawarma broiler. Its vertical shape and flame direction differ from the horizontal surfaces the table is built on.
  • If the shawarma broiler or oven sits under the same hood as other appliances, send its data and photos to the manufacturer through the supplier and ask for a written protection opinion before design approval.
  • If no written confirmation comes back, say so in the submittal instead of listing it as protected.

In a bakery the system usually covers listed appliances under the hood, such as a fryer, grill plate or rangetop, plus the duct and filters. Oven protection is for the manufacturer and designer to decide.

The long hood: how nozzles grow with length

Street-front grill shops often run one hood along the whole shopfront. The manual’s hood rules are separate from the appliances:

  • Hood filters: one H1 nozzle covers up to 3 m, then one more nozzle for every 2 m. A 4 m or 5 m hood needs two, a 6 m hood needs three.
  • V type filters up to 60 cm high with 120 cm spacing need two nozzles; one nozzle if the spacing is smaller.
  • Divided hood: one nozzle for each division up to 3 m.
  • Square duct up to 40 x 40 cm: one nozzle; up to 40 x 60 cm: two, plus one for every extra 20 cm. Round duct up to 40 cm diameter: one nozzle; up to 60 cm: two.

The manufacturer’s catalogue says HS-8 suits hoods up to about 2.4 m and HS-16 up to about 4.8 m, depending on hood features. When 16 flow points are not enough, the load is split over more than one cylinder: the smaller one protects the hood, the larger one protects the appliances, and the larger is the master system that carries the detection line and actuates the other. For step by step sizing, see sizing HoodSafer HS-4, HS-8 or HS-16.

A worked example for a grill shop

For illustration only, not an approved design: a 4 m undivided hood, one 40 x 40 cm duct, slanted 50 cm filters, and under it a 140 x 70 cm charcoal grill, a single pan fryer of 60 x 60 cm and a 60 x 120 cm grill plate.

ItemNozzlesFlow points
Duct 40 x 40 cm1 x H11
Filters, 4 m hood2 x H12
Charcoal grill 140 x 70 cm2 x H12
Single pan fryer 60 x 60 cm1 x H22
Grill plate 60 x 120 cm1 x H31
Total7 nozzles8

Eight flow points fit HS-8 by count, but a 4 m hood exceeds the HS-8 guide length, so the discharge line limits in the manual are checked. HS-16 is the likely choice, subject to the actual design. If the manufacturer confirms an H2 nozzle for the grill instead of H1, the grill becomes 4 flow points and the total 10, so HS-16 remains the choice.

Installation points for hot shops

  • The manual gives an operating temperature range of +5 °C to +49 °C. In summer next to a charcoal grill, the temperature around the cylinder can rise, so place it away from the heat with suitable ventilation.
  • Discharge piping is AISI 304 or 304L stainless steel, 3/8 inch, SCH40. No galvanised pipe, no Teflon tape on threads, and no paint on the pipes.
  • The HS series gas shut-off valve is a mechanical, normally closed type held open by the tension wire, and it closes when the system actuates. An electrical option exists. A microswitch comes as standard to send a signal to the fire alarm panel.
  • Put the pull station on the exit route, so staff can reach it without passing in front of the grill.
  • The detection line allows a maximum of 25 corner pulleys.

Common mistakes in grill shops and bakeries

  • Writing “grill” without the fuel type and size, so the wrong thermobulb or too few nozzles are selected.
  • Counting appliances but forgetting the duct and filters, where grease collects first.
  • Treating the shawarma broiler or the oven as protected because it sits under the hood, with no written confirmation from the manufacturer.
  • Adding a grill or moving the fryer without re-laying the nozzles.
  • Skipping hood cleaning. The system puts out fires; it does not remove the grease that feeds them.

Frequently asked questions

Does HoodSafer cover an open charcoal grill?

Yes. Charcoal and wood grills are both in the appliance table of the technical manual, with one H1 nozzle for each surface up to 70 x 70 cm under Table 1 and a 260 °C thermobulb link for open flame. Because another section of the manual gives H2 for these grills, confirm the nozzle type in writing with the manufacturer.

Does the system protect a vertical shawarma broiler?

It is not in the appliance table of the manual we reviewed. We do not assume coverage. We send its data to the manufacturer and ask for a written opinion before design approval.

Does a bakery oven need a kitchen suppression system?

Ovens are not on the HoodSafer list. Listed appliances under the hood are protected; oven protection is for the manufacturer, designer and authority to decide.

My hood is 6 m long. Is one system enough?

It depends on total flow points. A 6 m hood alone needs three filter nozzles plus duct nozzles, so with appliances the total may pass 16 and linked cylinders are used.

What data is needed to design a system for a grill shop?

Hood length and divisions, duct sizes, filter type, every appliance with fuel type and surface size, site photos and the gas line position.

Conclusion

A grill restaurant fire suppression system is calculated appliance by appliance. Grills, fryers, grill plates and rangetops are listed in the HoodSafer manual, and a long hood adds nozzles with length. The vertical shawarma broiler and bakery ovens are not on the manufacturer’s list. Ask for written confirmation before design instead of assuming coverage.

Running a grill shop or bakery and need the right system for your hood and appliances? Send us the hood dimensions, the appliance list and the fuel type for each one. Talk to the AZEIDK Egypt team

References: Material Submittal for Fire Suppression System Hood Safer (includes the HS series catalogue and technical manual, published on the AZEIDK site), HoodSafer page (AZEIDK Egypt, in Arabic), HoodSafer Global Case Study, BS EN 17446:2021 (BSI), Fire protection systems in restaurants, NFPA 96 Table 11.4 (Markel), NFPA 96 Standard (NFPA)
Share this article