When a consultant or contractor in Egypt asks for a 1000 GPM fire pump, the project is usually larger than a small warehouse: a mid-rise office or residential building with several standpipes, or a factory where sprinklers and hose cabinets share one network. 1000 is the rated flow in US gallons per minute (GPM). It does not select the set on its own, because the rated pressure decides how high the network can serve.
This article walks through the 3PUMP 1000 GPM at 10 bar set as shown in the datasheet published by AZEIDK Egypt: components, motor, diesel and jockey data, how to read the performance curve, and when the set fits a project. It is part of the fire pump systems AZEIDK Egypt supplies.
Key takeaways
- The set has an electric main pump and a diesel standby pump of the same model, 3P 5×4-10.2L, an RV10-12 jockey pump, and three separate LS controllers.
- Electric motor: 150 HP (110 kW) at 415 V. Diesel engine: POWER 6102BZQ, 150 HP. Jockey: 40 GPM at 10.5 bar, 4.0 kW.
- Datasheet curves: about 8 bar at 150% of rated flow and about 10.9 to 11.1 bar at shutoff, both inside the NFPA 20 limits.
- 1000 GPM is the maximum standpipe demand for a fully sprinklered building under NFPA 14 (2019 edition).
- Sets supplied in Egypt are Non-Listed. UL/FM-listed versions are manufactured and supplied on request.
In this article
- What is in the 3PUMP 1000 GPM at 10 bar set
- Electrical data for the 150 HP motor
- Reading the curve: 150% point and shutoff pressure
- When does a 1000 GPM fire pump fit the project?
- Jockey pump and controllers
- Non-Listed or UL/FM?
- Common mistakes when ordering a 1000 GPM pump
- Frequently asked questions
- Conclusion
What is in the 3PUMP 1000 GPM at 10 bar set
The datasheet is titled NON-UL TECHNICAL SUBMITTAL and describes an electric main pump, a diesel standby pump and a jockey pump. Both main pumps are end suction units of the same model, which keeps spare parts common and makes it easy to compare the two during testing. The table repeats the datasheet values.
| Item | Electric pump | Diesel pump | Jockey pump |
|---|---|---|---|
| Model | 3P 5×4-10.2L | 3P 5×4-10.2L | RV10-12 |
| Duty point | 1000 GPM at 10 bar | 1000 GPM at 10 bar | 40 GPM at 10.5 bar |
| Driver | INTEM 280S-2 motor, 415 V, 50 Hz, 3 phase | POWER 6102BZQ diesel engine, 12 V electrical system | 4.0 kW, 50 Hz |
| Power | 150 HP | 150 HP | 4.0 kW |
| Speed | 2960 rpm | 3000 rpm | Not stated in the datasheet |
| Materials | Cast iron casing, bronze impeller, stainless steel shaft, mechanical seal | Same | Stainless steel impeller and shaft |
The datasheet also lists a PACIFIC pressure switch, ONTOR/GALA valves and three individual LS controllers made in Korea. The motor has class F insulation and IP55 protection.
Electrical data for the 150 HP motor
The motor table attached to the datasheet gives the 280S-2 frame as 110 kW (150 HP) at 2960 rpm with 93.5% full-load efficiency. Full-load current is 201 A at 380 V, 191 A at 400 V and 184 A at 415 V. Locked rotor current in the table is 1330 A at 400 V, and the approximate motor weight is 800 kg.
At this size, starting current drives real design decisions: transformer capacity, standby generator rating if it feeds the pump room, cable size and the feeder breaker. Give the electrical engineer the full motor data page from day one. The weight of motor, pump and base also matters for the concrete plinth and for how the set gets into the pump room. If you want to see why this duty point needs 150 HP, our article on fire pump power calculation works through this same set.
Reading the curve: 150% point and shutoff pressure
The datasheet shows two curves for the 3P 5×4-10.2L, one at 2950 rpm and one at 3000 rpm. Each curve prints two results marked PASS. The datasheet does not say which curve belongs to the electric pump and which to the diesel pump, so we show them as printed.
| Curve | Pressure at 150% flow (1500 GPM) | Shutoff pressure (zero flow) |
|---|---|---|
| 2950 rpm | 8.00 bar | 10.90 bar |
| 3000 rpm | 7.96 bar | 11.06 bar |
| NFPA 20 limit for 10 bar rated | At least 65%, so 6.5 bar | No more than 140%, so 14 bar |
NFPA 20 requires a centrifugal fire pump to deliver at least 65% of rated pressure at 150% of rated flow, and its shutoff pressure must not exceed 140% of rated pressure. Both curves sit well inside these limits. A fairly flat curve like this one also helps in practice, because pressure does not climb much when actual demand is below rated flow.
Shutoff pressure is still a number that pipes, valves and hose cabinets must withstand. If the pump draws from a source with positive suction pressure, add it to the shutoff pressure when you check component pressure ratings. Acceptance testing on site is covered in fire pump testing in Egypt.
When does a 1000 GPM fire pump fit the project?
NFPA 14 (2019 edition) sets standpipe demand at 500 GPM for the hydraulically most remote standpipe plus 250 GPM for each additional standpipe, up to a maximum of 1000 GPM in a fully sprinklered building, with 100 psi (about 6.9 bar) residual at the most remote outlet. A sprinklered building with three or more standpipes therefore reaches 1000 GPM, which is exactly this set’s duty point. The set also suits a factory or warehouse where the sprinkler demand plus hose allowance comes to about 1000 GPM in the approved hydraulic calculation.
Height is limited by pressure. An illustrative example: an office building in New Cairo with three standpipes, the pump drawing from a ground tank with no added suction pressure.
- Required pressure at the most remote outlet: 6.9 bar.
- Highest outlet 20 m above the pump centreline: 20 ÷ 10.2 = about 2.0 bar.
- Friction losses: assumed 1.0 bar for this example only. The real figure comes from the consultant’s calculation.
- Total: about 9.9 bar, inside 10 bar with a thin margin.
With the highest outlet at 30 m the demand becomes about 10.8 bar. The set is then not enough, and the design needs higher pressure or pressure zones as approved. The other duty points are in choosing a 3PUMP fire pump set by flow and pressure. The binding reference in Egypt is the Egyptian Code for the Design and Implementation of Fire Protection for Buildings, 2026 edition (Ministerial Decree No. 355 of 2026), with drawings approved by the General Directorate of Civil Protection. NFPA 14 and NFPA 20 are technical references for design and testing.
Jockey pump and controllers
The RV10-12 jockey pump in this set is rated 40 GPM at 10.5 bar, slightly above the main pumps’ rated pressure. Its job is to hold network pressure and make up small leaks so the main pump does not start on every small drop. Its start and stop settings sit above the electric pump start, with the diesel start below both, as explained in jockey pump pressure settings.
Each pump has its own controller. At handover, check every signal each controller sends to the fire alarm panel, such as pump running, failure to start and loss of power, as the approved design requires.
Non-Listed or UL/FM?
The 3PUMP sets AZEIDK Egypt supplies at the listed duty points, including 1000 GPM at 10 bar, are Non-Listed. The words NFPA PERFORMANCE in the datasheet describe the shape of the performance curve. They do not mean the set is UL listed or FM approved. If the owner, insurer or consultant requires a listed set, UL/FM versions are manufactured and supplied on request, and this must be written into the specification and BOQ before pricing.
Common mistakes when ordering a 1000 GPM pump
- Adding up standpipe demand without the 1000 GPM cap for sprinklered buildings, then ordering a larger set than needed.
- Choosing 10 bar for a building taller than the hydraulic calculation allows.
- Designing the power supply on 150 HP alone, without the 1330 A starting current and the generator rating.
- Forgetting to add positive suction pressure to shutoff pressure when rating valves and pipes.
- Writing UL/FM in the BOQ, then accepting a Non-Listed set without changing the specification.
- Skipping the diesel tank calculation, covered in diesel fire pump fuel tank size.
Frequently asked questions
Which pump model is used in the 3PUMP 1000 GPM set?
The 3P 5×4-10.2L end suction model for both the electric and diesel pumps, with an RV10-12 jockey pump.
What are the motor and diesel engine ratings?
The motor is 150 HP (110 kW) at 415 V and 2960 rpm. The diesel engine is a POWER 6102BZQ rated 150 HP at 3000 rpm, per the datasheet.
What is the shutoff pressure of this set?
The datasheet gives 10.90 bar on the 2950 rpm curve and 11.06 bar on the 3000 rpm curve, both well below the NFPA 20 limit of 140%.
Is a 1000 GPM fire pump enough for a 15-storey building?
The flow may be enough, but 10 bar usually does not cover the elevation plus the pressure needed at the highest outlet at that height. The hydraulic calculation decides.
Is the set UL listed or FM approved?
No. The set supplied in Egypt is Non-Listed. UL/FM versions are manufactured and supplied on request.
Where can I get the datasheet?
It is published on the AZEIDK Egypt 3PUMP page and can be sent with the submittal file when you request a quotation.
Conclusion
The 3PUMP 1000 GPM at 10 bar set combines a 150 HP electric pump, a 150 HP diesel pump and a 40 GPM at 10.5 bar jockey, and its curve sits well inside the NFPA 20 limits. It suits sprinklered buildings with several standpipes and factories whose calculated demand is around 1000 GPM, provided 10 bar covers the highest outlet plus losses. Start with the hydraulic calculation, and bring in the electrical data early because starting current affects the transformer and generator.
Is your project demand around 1000 GPM, and do you need to know whether 10 bar reaches the highest outlet? Send us the required duty point and the network drawings. We will check them against the datasheet and propose the right set. Talk to the AZEIDK Egypt team
Related guides
- Museum Fire Protection in Egypt: Archives and Clean Agent Instead of Water
- Fire Pump for Residential Towers in Egypt: Estimating Flow and Pressure and Choosing a 3PUMP Set
- Sprinkler System Maintenance in Egypt: Sprinkler Heads, Alarm Valve, Main Drain and Water Motor Gong