Product Overview

Hood Safer CabinetSafer is an automatic fixed fire suppression system that protects the inside of electrical panels, control cabinets and server racks. Pressurised detection tubing runs inside the cabinet; when the temperature reaches about 100 °C or a flame touches it, the tube bursts at the fire and releases FK-5-1-12 directly onto the source, with no power supply or separate detectors needed.

SystemHood Safer CabinetSafer automatic fixed fire suppression system for electrical applications
AgentFK-5-1-12
Detection and actuationPressurised linear detection tubing that ruptures at about 100 °C or on flame contact and forms a diffuser; no external power source needed
System typeDirect Low Pressure
Cylinder pressure15 bar (nitrogen)
Detection tubeCS400, 6 mm, minimum bend radius 60 mm, optimum 150 mm
Maximum distance20 m from the cylinder to the furthest burst point
MonitoringCS300 volt-free pressure switch (NO/NC) that can signal the fire alarm panel
MountingVertical, never more than 45 degrees from vertical, in an area not above 60 °C
MaintenanceVisual inspection every 3 months and full service every 12 months per BS 5306-3

Applications

  • Main electrical panels and distribution boards
  • Control cabinets and motor control centres (MCC)
  • Server and network data racks
  • Several adjacent cabinets using tee connectors

Frequently asked questions

Does the system need power to work?

No. Detection and actuation are mechanical through the pressurised tubing. The CS300 pressure switch can be added to signal the fire alarm panel.

Can one cylinder protect more than one cabinet?

Yes. Adjacent cabinets can be covered with tee connectors, provided the distance from the cylinder to the furthest point does not exceed 20 m.

Specifications are taken from the official Hood Safer CabinetSafer Technical Manual. You can download the datasheet from AZEIDK. Supplied by AZEIDK with design, installation and maintenance.