Fire Suppression Gases: CO2, FM-200, Novec 1230 and Inert Gases Compared

Fire Suppression Gases: CO2, FM-200, Novec 1230 and Inert Gases Compared

There is no single gas for fighting fire. Fire suppression gases fall into four families: carbon dioxide (CO2), HFC-227ea sold as FM-200, FK-5-1-12 known as Novec 1230, and inert gases such as nitrogen, argon and their blends. All extinguish without water or residue, but they differ in how they work, how safe they are for people and where they fit.

AZEIDK supplies and installs gas systems under special fire suppression systems, including Context Plus 227 (HFC-227ea), the SFFECO 1230 system and the SFFECO CO2 system.

Key points

  • CO2 works by reducing oxygen and is dangerous to people at extinguishing concentration, so it is used in normally unoccupied spaces.
  • HFC-227ea and FK-5-1-12 are clean agents that absorb heat and suit server and electrical rooms.
  • Inert gases (IG-100, IG-01, IG-55, IG-541) reduce oxygen and need more cylinders.
  • Every system needs a tight room and a quantity calculation under NFPA 2001 or NFPA 12.
In this article
  1. How fire suppression gases work
  2. Carbon dioxide (CO2)
  3. HFC-227ea (FM-200)
  4. FK-5-1-12 (Novec 1230)
  5. Inert gases
  6. Comparison
  7. Frequently asked questions

How fire suppression gases work

Gases extinguish in two ways: lowering oxygen until combustion stops (CO2 and inert gases), or absorbing heat from the flame (HFC-227ea and FK-5-1-12). Because the gas fills the whole room, it reaches inside racks and panels where spray cannot.

Carbon dioxide (CO2)

The oldest and cheapest agent. Its extinguishing concentration is dangerous to people, so systems are designed for normally unoccupied areas such as generator rooms, paint booths and some industrial equipment, with safeguards such as a pre-discharge delay and a lockout valve. The reference standard is NFPA 12. See CO2 system maintenance.

HFC-227ea (FM-200)

A clean agent stored as a pressurised liquid that vaporises on discharge, extinguishing mainly by heat absorption at a design concentration kept within the safety limits of NFPA 2001. It is common in server rooms, data centres, telecom rooms and archives. AZEIDK supplies it in Context Plus 227 and the American Fire Control FM-200 system.

FK-5-1-12 (Novec 1230)

A fluid that evaporates quickly on discharge and absorbs heat. Novec 1230 was 3M’s trade name; in December 2022 3M announced it would exit PFAS manufacturing, including fluorinated fluids, by the end of 2025. FK-5-1-12 itself is made by other manufacturers, such as the SFFECO 1230 system AZEIDK supplies, so specifications should name the agent, not the trade name.

Inert gases

IG-100 is pure nitrogen, IG-01 pure argon, IG-55 a nitrogen and argon blend, and IG-541 a blend of nitrogen, argon and CO2. They lower oxygen to stop combustion while still allowing brief breathing during egress, leave no residue and do not break down in flame. Stored as compressed gas, they need more cylinders, more storage space and pressure relief venting.

Comparison

GasMechanismOccupied spacesTypical use
CO2Oxygen reductionNo, normally unoccupied areasGenerators, industrial equipment
HFC-227eaHeat absorptionYes, at safe design concentrationServers, telecom, archives
FK-5-1-12Heat absorptionYes, at safe design concentrationServers, control rooms
Inert gasesOxygen reductionYes, at calculated concentrationsLarge data centres, archives

See clean agent suppression for equipment rooms, the NFPA 2001 guide and the room integrity test.

Frequently asked questions

Which gas is used to extinguish fires?

Mainly CO2, HFC-227ea (FM-200), FK-5-1-12 (Novec 1230) and inert gases such as nitrogen and argon.

Is FM-200 dangerous to people?

It is designed at a concentration within NFPA 2001 safety limits, but the room should still be evacuated on alarm.

Why is CO2 not used in offices?

Its extinguishing concentration is dangerous to people, so it is used in normally unoccupied areas with safeguards.

Has Novec 1230 been discontinued?

3M announced its exit from PFAS manufacturing by the end of 2025; FK-5-1-12 is produced by other makers such as SFFECO.

Does AZEIDK supply gas suppression systems?

Yes, HFC-227ea, FK-5-1-12 and CO2 systems, with design and installation.

Protecting a server or electrical room? Send us the room size and occupancy, and AZEIDK will propose the agent and calculate the quantity. Contact AZEIDK

Share this article
This site is registered on wpml.org as a development site. Switch to a production site key to remove this banner.