Helipad Fire Protection: Foam Systems, Monitors and NFPA 418 Requirements

Helipad Fire Protection: Foam Systems, Monitors and NFPA 418 Requirements

Helipad fire protection on hospital, tower and hotel rooftops relies mainly on foam, because the main hazard is aircraft fuel spilling and igniting on the landing pad. In Saudi Arabia the binding requirements are the Saudi Building Code (SBC) and Civil Defense; the US standard NFPA 418 for heliports is used as a reference for foam application rate, discharge duration and distribution methods, from which the designer sizes the foam quantity, pump and tank unless the authority specifies otherwise.

This guide covers the elements of a rooftop helipad foam system, how quantities are calculated, and the related fire fighting system components AZEIDK supplies, such as AFFF foam, foam tanks and foam monitors.

Key points

  • NFPA 418, as quoted in Transport Canada guidance, sets an AFFF application rate of 0.10 gpm/ft² (4.1 L/min per m²).
  • Discharge duration for a fixed system is 10 minutes in NFPA 418, per the same source.
  • Fixed distribution options: perimeter nozzles, two or more oscillating monitors, or nozzles built into the deck.
  • Acceptance testing requires foam to cover 95% of the rooftop landing pad during the test.
  • NFPA 418 refers foam system design to NFPA 11, NFPA 16 or an equivalent standard; the SBC and Civil Defense requirements remain binding for the project.
In this article
  1. Why do helipads need foam?
  2. NFPA 418 requirements for helipad fire protection
  3. Foam distribution methods on the pad
  4. How is helipad foam quantity calculated?
  5. Components of a helipad foam system
  6. Choosing foam concentration and type
  7. Hospital, hotel and tower helipads
  8. Testing and routine maintenance
  9. What consultants ask for in a helipad foam submittal
  10. Frequently asked questions
  11. Summary

Why do helipads need foam?

The typical helipad incident is fuel spilling from the aircraft tank after a hard landing or leak and igniting on the deck. Water alone does not reliably extinguish flammable liquid fires over a wide area; AFFF forms a film over the fuel surface and suppresses vapour. NFPA 418 therefore focuses on foam: how much is applied, for how long, and how it reaches every part of the pad.

On elevated rooftop pads the risk is higher, since access is limited, the building below is occupied and roof escape routes are short. This is why hospitals and towers address the system from the design stage.

NFPA 418 requirements for helipad fire protection

Transport Canada guidance quotes these NFPA 418 (2016 edition) provisions for rooftop heliports. They are reference values and do not replace the SBC or Civil Defense requirements:

  • Application rate: 0.10 gpm/ft² (4.1 L/min/m²) for AFFF.
  • Fixed system discharge duration: 10 minutes.
  • Design standard: NFPA 11, NFPA 16 or equivalent.
  • Distribution: perimeter fixed nozzles, two or more oscillating monitors, or in-deck nozzles.
  • Acceptance test: coverage of 95% of the rooftop landing pad during the test.

A checklist from California’s hospital authority (HCAI) uses broadly the same values. Clause numbers differ between NFPA 418 editions, so refer to the edition named in the project documents.

Foam distribution methods on the pad

MethodHow it worksWhat to check
Perimeter fixed nozzles (ring main)Several nozzles on the edges of the landing area, fed by a pipe ringThat nozzle reach covers the centre of the pad
Oscillating foam monitorsTwo or more monitors on opposite sides, some remotely operatedOscillation angles that keep access and egress clear
Deck-integrated nozzles (DIFFS)Pop-up nozzles across the landing areaCompatibility with the deck surface

Transport Canada notes that a single monitor cannot deliver the required flow or coverage, and that monitors are placed on opposite sides. For monitor types, see foam monitors and SFFECO foam monitors.

How is helipad foam quantity calculated?

  1. Solution flow = whole landing pad area × 4.1 L/min/m².
  2. Solution quantity = solution flow × discharge duration (10 minutes for a fixed system).
  3. Concentrate quantity = solution quantity × proportioning rate (3% or 6%, depending on the foam).

Illustrative example: a 400 m² landing area needs 1,640 L/min of solution, or 16,400 L over 10 minutes. With 3% foam that is 492 L of concentrate; with 6% foam, 984 L. These figures are for illustration only; the final quantity is set by the designer after adding whatever the adopted standard, the authority and the network require.

Components of a helipad foam system

  • Foam concentrate: AZEIDK supplies Safe Guard 3% AFFF and 6% AFFF in 20 L and 200 L packs. See SafeGuard in Saudi Arabia.
  • Foam tank and proportioner: bladder tanks with a ratio controller, such as the WATEX UL-listed foam bladder tank and SFFECO and Falcon Gold tanks. Proportioning is explained in foam proportioning and bladder tanks.
  • Discharge devices: monitors or fixed nozzles, per the design.
  • Water supply and pump: sized for the required solution flow and the operating pressure of the discharge devices at roof level.
  • Operating points: in safe positions the operator can reach without approaching the fire zone.

Choosing foam concentration and type

A 3% foam means a smaller tank for the same solution quantity; 6% needs twice the concentrate. More important is that the foam suits the proportioning and discharge equipment in the design, and that it is not mixed with another type or brand at refill without confirmed compatibility. Canadian regulation CAR 325.47, as quoted in Transport Canada guidance, states that foam concentrates of different types or manufacturers are not mixed unless shown to be compatible and interchangeable.

For the concentrations available on the market, see foam fire suppression systems in Saudi industrial facilities.

Hospital, hotel and tower helipads

Buildings that may have rooftop helipads include major hospitals and some hotels and commercial towers. In healthcare facilities the pad links to the patient route to the emergency department, so the foam system is coordinated with fire alarm and roof escape routes. In hotels and commercial buildings, the pad sits above spaces occupied at all hours.

Testing and routine maintenance

  • Acceptance test proving 95% coverage of the landing pad.
  • Periodic inspection of the foam tank, bladder and ratio controller.
  • Periodic concentrate sample testing per the manufacturer’s instructions.
  • Operation of monitors or nozzles, checking for blockage by dust or sand.

These items fall under preventive and scheduled maintenance contracts for fire systems.

What consultants ask for in a helipad foam submittal

The approval file for a helipad foam system brings calculations, equipment and drawings together so the consultant can review them in one pass. It usually includes:

  • a calculation sheet showing protected area, application rate, duration, and solution and concentrate quantities;
  • datasheets for the foam concentrate, foam tank, ratio controller and discharge devices, with available listing or approval certificates;
  • a drawing showing monitor or nozzle positions and their coverage of the landing area and access points;
  • the pump curve or water supply data and available pressure at roof level;
  • operating point locations and access routes;
  • the acceptance test procedure and pass criteria;
  • operation and maintenance manuals for the main components.

Preparing this file early shortens comment cycles and exposes clashes with structural and electrical work before installation.

Frequently asked questions

What foam application rate does a helipad need?

NFPA 418, as quoted in Transport Canada guidance, sets 0.10 gpm per square foot, or 4.1 L/min per square metre, for AFFF.

How long must a fixed helipad foam system discharge?

10 minutes in NFPA 418, per the same source. Confirm the edition adopted for the project.

Is one foam monitor enough for a helipad?

No. Transport Canada guidance states a single monitor cannot provide the required flow or coverage, and monitors go on opposite sides.

Which foam concentration suits a rooftop pad?

AFFF at 3% or 6%, matched to the proportioning equipment in the design. 3% reduces tank size for the same solution quantity.

How is helipad foam coverage tested?

The NFPA 418 acceptance test requires coverage of 95% of the rooftop landing pad during the test.

Can two foam brands be mixed in a helipad tank?

Not advisable unless compatibility is confirmed by the manufacturer and accepted by the authority.

Summary

Helipad fire protection starts from two numbers, application rate and discharge duration, which drive the solution, concentrate, pump and tank sizes. The distribution method is then chosen to give the required coverage without blocking movement on the pad, proven at acceptance and kept up through maintenance.