Lift shaft pressurization (elevator hoistway pressurization) pushes clean air into the lift shaft during a fire, so the shaft is at a slightly higher pressure than the floors around it. Smoke then cannot enter the shaft through the landing doors and travel between floors. It is typically required in high-rise buildings and for firefighter and evacuation lifts, depending on project requirements.
This guide covers how the system works, the pressure limits as stated in the US IBC, its components, how it ties into the fire alarm and how it is tested before handover. AZEIDK delivers these systems under its smoke extraction and emergency ventilation systems.
Key takeaways
- A lift shaft is an open vertical path between floors; smoke that gets in spreads quickly.
- IBC Section 909.21 (as quoted by ICC from the 2012 edition) sets a pressure difference of at least 0.10 in. of water (25 Pa) and no more than 0.25 in. of water (67 Pa).
- The upper limit matters as much as the lower one, because excess pressure can stop the lift doors from working.
- Each shaft has its own fan system, and a smoke detector stops the fan if it draws in smoke.
- Shaft fans are controlled from the firefighter’s smoke control panel.
In this article
- Why does a lift shaft need positive pressure?
- Required pressure difference for lift shaft pressurization
- Components of a lift shaft pressurization system
- Connecting lift shaft pressurization to the fire alarm
- How is lift shaft pressurization tested before handover?
- Common mistakes
- Lift shaft pressurization with AZEIDK
- Frequently asked questions
- Conclusion
Why does a lift shaft need positive pressure?
In multi-storey buildings a lift shaft acts like a chimney. Stack effect, HVAC air movement and open doors all push smoke towards vertical openings. Smoke that enters the shaft on the fire floor can come out on floors far from the fire.
Pressurization reverses the leakage: air flows out of the shaft into the floors through door gaps instead of smoke flowing in. The principle is the same as stair pressurization for escape routes, but shafts have their own issues: power-operated doors, lift recall during a fire, and sometimes a connected machine room.
Required pressure difference for lift shaft pressurization
In Saudi Arabia the Saudi Building Code, Civil Defense requirements and the approved project design govern. The values below are from US IBC Section 909.21, a common technical reference for these systems; the designer confirms the corresponding clause in the edition adopted in the Kingdom.
| Item | Value as quoted by ICC from IBC 2012 Section 909.21 |
|---|---|
| Minimum pressure difference | 0.10 in. of water (25 Pa) positive relative to adjacent occupied space on all floors |
| Maximum pressure difference | 0.25 in. of water (67 Pa) |
| Measurement point | Midpoint of each hoistway door |
| Door condition during measurement | All hoistway doors on the recall floor open, all other hoistway doors closed |
| Door operation | Doors shown to open and close at each level with the system running |
Why a maximum? Lift doors are driven by small operators, and excess pressure can stop them closing or slow them down, taking the lift out of service just when firefighters need it. The system is therefore designed to stay inside a band however many doors are open.
Components of a lift shaft pressurization system
- Dedicated supply fan per shaft: the same ICC document quotes a separate fan system for each hoistway.
- Outdoor air intake: placed away from exhaust and smoke outlets so the fan does not draw smoke into the shaft.
- Smoke detector at the intake or in the supply path: shuts the fan down if smoke is detected in incoming air.
- Ducts and fans with the shaft’s fire-resistance rating: as quoted from the IBC.
- Pressure regulation: for example fan speed control with a VFD driven by a pressure sensor, keeping pressure inside the band as doors open and close.
- Standby power and fire-resistant cabling: the system must keep running during a fire.
Is shaft venting still needed?
Some codes required a vent at the top of the lift shaft to release smoke. In Washington State’s amendments to Section 909, for example, hoistway venting is not needed for pressurized shafts, and machine rooms are pressurized unless separated from the shaft by fire-rated construction. Each project settles this under the adopted code and the authority’s requirements.
Connecting lift shaft pressurization to the fire alarm
The system usually starts on a signal from the fire alarm panel through an output module, written in the cause and effect matrix alongside lift recall, stair pressurization and AHU shutdown. Points to agree early between the fire engineer, mechanical engineer and lift supplier:
- Which signals start the system: any detector in the building or specific zones.
- Order of commands between lift recall and fan start, so door movement is not affected during recall.
- Fault signals from the fan and intake detector, and how they show on the fire alarm panel.
- Manual control: IBC 909.16 (as adopted in the Massachusetts code) requires the firefighter’s smoke control panel to give ON-AUTO-OFF control over each piece of smoke control equipment, including elevator shaft fans.
For interfacing signals on addressable systems, see fire alarm input/output modules.
How is lift shaft pressurization tested before handover?
- Check the shaft is complete: doors installed and adjusted, gaps around doors and cables sealed as drawn.
- Start the system from a real alarm signal and check fan start and response time.
- Measure the pressure difference at the midpoint of each door on every floor, with doors set as the code and design require.
- Open and close the doors on each floor with the system running.
- Simulate smoke at the intake or trigger its detector, and confirm the fan stops and the signal appears.
- Test manual control from the firefighter’s panel.
This test belongs to integrated fire and life safety systems testing, as it brings together the alarm, lifts and ventilation. Pressure measurement details are in smoke control system testing.
Common mistakes
- Air intake near a smoke exhaust or generator exhaust outlet, so the system pulls smoke into the shaft.
- Fixed-speed fan with no regulation, so pressure exceeds the maximum when doors close.
- Unsealed openings in shaft walls or around landing doors, so the minimum is never reached however big the fan.
- No coordination with the lift supplier on door closing force and recall sequence.
- Ordinary cabling or a non-standby power source for the fan.
Lift shaft pressurization with AZEIDK
Under its smoke extraction and emergency ventilation systems, AZEIDK handles site study, supply and installation of fans and control components, connection to the fire alarm and testing. Fan capacities and positions follow the approved design for each project, and our engineering design and calculations service can review the design and coordination with HVAC and lifts.
Frequently asked questions
What is lift shaft pressurization?
A system that supplies clean air into the lift shaft during a fire so it stays at higher pressure than the floors, keeping smoke out of the shaft.
What pressure difference is required?
ICC quotes IBC 2012 at a minimum of 0.10 in. of water (25 Pa) and a maximum of 0.25 in. of water (67 Pa); each project follows its adopted code and authority.
How is it different from stair pressurization?
Same principle, but lift shafts must allow for power-operated doors and lift recall, so the upper pressure limit is tighter.
Does each lift shaft need its own fan?
According to the IBC text quoted by ICC, yes: a separate fan system for each hoistway.
When does the system start?
On a fire signal from the alarm panel under the cause and effect matrix, with manual control from the firefighter smoke control panel.
What if smoke enters the air intake?
The intake smoke detector stops the fan so it does not push smoke into the shaft, and the signal shows on the fire alarm panel.
Conclusion
Lift shaft pressurization works between two limits: enough pressure to keep smoke out, and not so much that lift doors fail. That takes a dedicated fan per shaft, a clean air intake, pressure regulation, a planned interface with the alarm and lifts, and a floor-by-floor test before handover.
Does your project include firefighter lifts or shafts that need pressurization? Send us the drawings and Civil Defense requirements, and we will review supply, installation, interfacing and testing with you. Talk to the AZEIDK team
AZEIDK supplies, installs and maintains fire alarm systems in Saudi Arabia.
Related guides
- Wheeled Fire Extinguisher (50 kg Unit): When You Need One Instead of a Portable, 25 to 150 kg Sizes, Hose Length and Placement
- Outdoor Fire Alarm Sounder IP65: Weatherproof Context Plus Sounders and Beacons for Roofs, Car Parks and Yards
- Fire Hose Cabinet Valve (Angle Hose Valve): Sizes, Pressure and the Giacomini A55E
- SFFECO 1230 Fire Suppression System with FK-5-1-12 Clean Agent: Models, Cylinder Sizes, UL Listing and When to Choose It