Select Fire Plus (SFP) in Saudi Arabia: Conventional Detectors and the Explosion-Proof IR3 Flame Detector

Select Fire Plus (SFP) in Saudi Arabia: Conventional Detectors and the Explosion-Proof IR3 Flame Detector

Select Fire Plus (SFP) is a fire detection brand, and AZEIDK supplies four of its products in Saudi Arabia: a conventional optical smoke detector, a reflective beam smoke detector, a sounder strobe and an explosion-proof triple-infrared (IR3) flame detector. The first three run on a conventional zone at 16 to 28 V DC. The SFP-IR3-EXD flame detector is built for hazardous areas such as fuel loading bays, pump rooms and gas stations, and is usually installed as part of an integrated fire and gas system. This guide explains where each product fits and what to check in the datasheet before approval. The full product list is on the Select Fire Plus brand page.

Key takeaways

  • AZEIDK supplies four Select Fire Plus products in Saudi Arabia: SFP-CSD-001, SFP-CBM-100M, SFP-CSS-004 and SFP-IR3-EXD.
  • The SFP-CSD-001 smoke detector is approved to EN54-7:2018 by TUV Rheinland; the SFP-CSS-004 sounder strobe is approved to EN54-3 and EN54-23.
  • The SFP-CBM-100M beam detector covers an optical path of 10 to 100 m with automatic alignment, for high ceilings and large open spaces.
  • The SFP-IR3-EXD carries ATEX and IECEx marking Ex db IIC T6 Gb and Ex tb IIIC T80°C Db, with detection up to 60 m for a 0.3 × 0.3 m n-heptane fire.
  • The flame detector offers a 4–20 mA output, RS-485 and three relays, so it connects easily to a fire alarm panel or a fire and gas controller.
In this article
  1. What is Select Fire Plus (SFP) and what does AZEIDK supply?
  2. SFP-CSD-001 conventional smoke detector
  3. SFP-CBM-100M beam detector for large spaces
  4. SFP-CSS-004 sounder strobe
  5. SFP-IR3-EXD explosion-proof flame detector
  6. Where does the IR3 explosion-proof detector go?
  7. What to check before approving SFP devices
  8. How AZEIDK supports SFP projects
  9. Frequently asked questions
  10. Conclusion

What is Select Fire Plus (SFP) and what does AZEIDK supply?

The datasheets use the name SelectFire Plus, shortened to SFP in the model numbers. In the AZEIDK catalogue these products sit under conventional fire alarm systems, next to the Context Plus and FG ranges. In practice, SFP is not supplied by us as a complete system with its own panel. It comes as field devices that connect to the zones of a conventional panel, plus an industrial flame detector that works with a conventional panel or an industrial controller.

So the selection starts with two questions. What is the hazard in the area you are protecting? And which panel will receive the signal? The first answer sets the detector type. The second sets the wiring, the end-of-line device and the current limits on each zone.

ModelTypeKey datasheet pointsTypical use
SFP-CSD-001Conventional optical smoke detectorEN54-7:2018, dual emitter with two wavelengths, drift compensation, 16–28 V, IP30Offices, corridors, dry plant rooms
SFP-CBM-100MReflective beam smoke detector10–100 m path, motorised auto-alignment, IP65, fire and fault outputsWarehouses, halls, high-bay factories
SFP-CSS-004Sounder strobe110 dB(A) at 3 m, EN54-3 and EN54-23, W-2.75-9 coverageAudible and visual alarm in corridors and work areas
SFP-IR3-EXDExplosion-proof IR3 flame detectorATEX and IECEx, 110° horizontal field of view, IP66, 4–20 mA and RS-485Fuel bays, pump rooms, solvent stores, gas stations

SFP-CSD-001 conventional smoke detector

The detector works on light scattering. Smoke particles entering the chamber scatter light onto a photodiode, and the detector alarms once the signal passes a set threshold. The datasheet describes a dual emitter with two wavelengths and multiple light paths, and a design that is less sensitive to steam and small fast-burning particles, which helps cut nuisance alarms. It also adjusts its sensitivity automatically as dust builds up and the detector ages.

Electrically, it runs on 16 to 28 V DC, with a quiescent current of no more than 60 µA at 24 V and an alarm current of no more than 25 mA. The zone terminals are polarity insensitive, there are dedicated terminals for a remote LED, and it mounts on the SFP-BSH-012 base. These figures matter when you count detectors per zone and size the standby batteries, because the quiescent current of every detector goes into the battery calculation.

The ingress rating is IP30, so it is not suited to humid or very dusty areas or kitchens. Those areas normally take a heat detector; see our guide to heat detector types and installation before you lay out devices on the drawing.

SFP-CBM-100M beam detector for large spaces

In warehouses and halls with high ceilings, a large number of point detectors becomes expensive and hard to maintain. A reflective beam detector sends an infrared beam to a reflector at the far end and measures the light that comes back. When smoke reduces the returned signal to the set threshold, it raises an alarm.

What stands out in the SFP-CBM-100M datasheet is automatic setup. A laser aid helps with positioning and a stepper motor calibrates the detector angle, so the technician does not need to fine-tune it by hand after installation. The path length is 10 to 100 m, supply is 16 to 28 V DC, the rating is IP65 and the maximum angular misalignment is ±0.5°. Six rear terminals cover power, the fire output and the fault output.

One point to watch: the product page lists CE, EMC and electrical safety testing, but it does not list EN54-12, the standard for line-type beam detectors. If your specification requires EN54-12 or a specific UL listing, ask the supplier for the approval certificate before you submit, and do not assume it from the datasheet.

SFP-CSS-004 sounder strobe

This unit combines a sounder and a white LED strobe. According to the datasheet, the sounder is approved to EN54-3:2014+A1:2019 and the visual alarm device to EN54-23:2010, both by TUV Rheinland. Sound output is 110 dB(A) at 3 m and the flash rate is 1.5 to 2 Hz.

The W-2.75-9 rating under EN54-23 means the wall-mounted category with a maximum mounting height of 2.75 m and a coverage width of 9 m, with at least 0.4 lux inside the coverage volume. That is the figure to use when spacing strobes on the drawing, not how bright the flash looks. Alarm current is no more than 8 mA, which lets you put more devices on a sounder circuit than higher-draw units, as long as you check the panel output limit. The IP21C rating means indoor use.

SFP-IR3-EXD explosion-proof flame detector

This is the industrial product in the SFP range; see the SFP-IR3-EXD explosion-proof triple-IR flame detector page. It uses three pyroelectric sensors at 3.8, 4.4 and 5.3 µm. The detector compares signal strength and ratios across the three bands and analyses the low-frequency flicker of a flame, which is how it separates a real fire from sunlight, lighting and hot surfaces.

Detection ranges in the datasheet for a 0.3 × 0.3 m fire are up to 60 m for n-heptane, 55 m for gasoline and 50 m for alcohol. The horizontal field of view is 110°, with five sensitivity levels. The datasheet states it detects hydrocarbon fires and some non-carbon fires such as hydrogen, and keeps working with oil, dust, water or ice on the window.

Outputs are three relays (fire, fault, auxiliary) rated 1 A at 30 V DC, a 4–20 mA output, RS-485 and a fire bus output. Supply is 24 V DC and consumption is under 1 W. The enclosure is ADC12 aluminium alloy with an M20 conduit entry, weight is 1.55 kg without the bracket, and the operating range of -25°C to +75°C suits outdoor sites in a Saudi summer.

Where does the IR3 explosion-proof detector go?

The detector carries two markings: Ex db IIC T6 Gb for gas atmospheres and Ex tb IIIC T80°C Db for combustible dust. The “d” means a flameproof enclosure, IIC is the most demanding gas group, and T6 means the surface temperature stays at or below 85°C. Equipment protection level Gb corresponds to Zone 1 and is normally also accepted in Zone 2, and Db corresponds to Zone 21 and is normally also accepted in Zone 22, per the FM Approvals equipment protection level tables. The final decision comes from the site hazardous area classification, not from the datasheet alone.

Typical applications on Saudi industrial projects:

  • Fuel filling bays and loading and unloading stations.
  • Fuel and solvent pump rooms and metering skids.
  • Paint, solvent and petroleum product stores.
  • Gas stations and compressor areas in industrial facilities.
  • Aircraft hangars and their fuel areas, where flame detection is often linked to a foam system.

On these sites the detector usually sits in a fire and gas (F&G) system: flame detectors and flammable gas detectors read by a controller that runs the cause and effect matrix, for example raising the alarm, stopping pumps and opening a deluge valve. The 4–20 mA and RS-485 outputs make this link simple. On smaller jobs, such as a fuel pump room in a small factory, the fire relay can go to a zone on a conventional panel such as the FP conventional panels, with the panel itself installed outside the hazardous area.

If the site runs a fully addressable system, our catalogue also has the Context Plus intelligent IR3 flame detectors; the choice between the two depends on the area classification and the panel type.

What to check before approving SFP devices

  • Required standard: does the consultant call for EN54 or UL? The SFP devices here carry European approvals, so confirm this is acceptable under the project specification and Civil Defense requirements.
  • Panel compatibility: check zone voltage, end-of-line device and maximum zone current in the panel datasheet, then count detectors.
  • Hazardous area class: for the IR3 detector, ask for the area classification and match the Ex marking to the gas group and temperature class.
  • Cables and glands: the entry is M20, and in hazardous areas the cable glands must carry the same type of protection.
  • Certificates: request copies of the ATEX, IECEx and EN54 certificates with the submittal, not just the datasheet mention.

How AZEIDK supports SFP projects

We supply the four Select Fire Plus devices through our technical supply service, help select the right device for each area, and install, program and test them as part of a fire alarm or fire and gas project. The official datasheet for each product comes with our quotation.

Frequently asked questions

Does SFP have its own fire alarm panel?

The SFP products available from AZEIDK are detectors, a sounder strobe and a flame detector only. The conventional devices connect to the zones of a compatible conventional panel, and we check compatibility against the panel datasheet before supply.

What is the difference between an IR3 and a UV/IR flame detector?

An IR3 detector compares three infrared bands and analyses flame flicker, which cuts false alarms from sunlight and hot surfaces and usually gives longer range. The final choice depends on the fuel, detection distance and site conditions.

Can the SFP-IR3-EXD be installed in Zone 1?

It is marked Ex db IIC T6 Gb, and protection level Gb corresponds to Zone 1. The area classification must still confirm the gas group and temperature class, and cables and glands must carry the same protection level.

What is the detection range of the SFP-IR3-EXD?

Per the datasheet: up to 60 m for a 0.3 × 0.3 m n-heptane fire, 55 m for gasoline and 50 m for alcohol, with a 110° horizontal field of view.

How far does the SFP-CBM-100M beam detector reach?

The optical path between detector and reflector is 10 to 100 m. Coverage width and distance below the ceiling come from the design standard used on the project, not from the datasheet alone.

Can the SFP-CSD-001 go in a kitchen or bathroom?

It is not recommended. Its rating is IP30, and steam and cooking fumes cause false alarms. A heat detector is the usual choice there.

Conclusion

In the AZEIDK catalogue, Select Fire Plus means four specific devices: a smoke detector, a beam detector and a sounder strobe for conventional systems, and an explosion-proof IR3 flame detector for hazardous industrial sites. Choose by hazard, panel type and area classification, and ask for the original certificates with the submittal.

Have a hazardous area or a high-bay warehouse and need the right detector? Send the drawing and the area classification if you have it, and our engineers will review it with you. Talk to the AZEIDK team

References: SFP-IR3-EXD official datasheet; SFP-CBM-100M official brochure; SFP-CSD-001 official brochure; AZEIDK SFP-CSS-004 product page; FM Approvals: Guide to Hazardous Locations (EPLs, zones and temperature classes).
Share this article