Grundfos Fire Pumps: Fire DNF and Fire HSEF Sets and Vertical Turbine Fire Pumps

Grundfos Fire Pumps: Fire DNF and Fire HSEF Sets and Vertical Turbine Fire Pumps

Grundfos fire pumps are not only supplied as a bare pump but as a complete fire pump set on one base frame with the driver and the controller. This article covers the types Grundfos publishes officially, including the Fire DNF end-suction set, the Fire HSEF horizontal split-case set and vertical turbine fire pumps, and what each one includes according to the data sheets.

Grundfos is one of the suppliers AZEIDK works with on firefighting system projects, within technical selection of systems and equipment, technical supply and installation.

Key takeaways

  • Grundfos states that it supplies end-suction, horizontal split-case, vertical split-case, vertical in-line and vertical turbine fire pumps.
  • The electric (50 Hz) Fire DNF and Fire HSEF sets are FM approved according to NFPA 20 per the data booklet, and are built to order.
  • Grundfos vertical turbine fire pumps are UL listed and FM approved, with flows from 500 to 5000 GPM and pressures up to 350 psi.
  • A complete set includes the controller and a circulation relief valve, with a flowmeter available as an accessory.
In this article
  1. Fire DNF and Fire HSEF: what is the difference?
  2. Grundfos vertical turbine fire pumps
  3. Controllers and starting methods
  4. Approvals: look at the model, not the brand
  5. After supply: testing and commissioning
  6. Frequently asked questions

Fire DNF and Fire HSEF: what is the difference?

SetPump typeWhat Grundfos states
Fire DNFEnd-suctionDNF non-self-priming, single-stage centrifugal volute pump with dimensions and rated performance to DIN 24256 and ISO 2858, mounted with the motor on a base plate
Fire HSEFHorizontal split-caseHSEF horizontal split-case centrifugal pump with the motor on a base plate

End-suction pumps usually suit smaller flows, while horizontal split-case pumps cover higher flows and are easier to open for service. The choice starts from the duty point in the hydraulic calculations and from the water source, as explained in the fire pump types and selection guide.

Grundfos vertical turbine fire pumps

A vertical turbine pump is used when the water level is below the pump, such as deep underground tanks and wells. The Grundfos fire systems brochure lists:

  • Flows from 500 to 5000 GPM (114 to 1136 m³/h).
  • Pressure up to 350 psi (24.1 bar).
  • Engine or electric motor drive, no priming needed and a small floor space.
  • For the diesel version: a UL listed and FM approved engine with an industrial silencer, heat exchanger cooling, a fuel tank sized to NFPA 20 and an FM listed right angle gear.

Controllers and starting methods

Grundfos states that the controllers in its sets are UL-FM approved as standard and use microprocessor logic with a pressure and event recorder. Starting options for the electric controller include star delta, part winding, soft start, autotransformer and variable frequency drive. For selection criteria see fire pump controller selection, and for an example of standalone controllers see Tornatech GPx and GPD controllers.

Approvals: look at the model, not the brand

Grundfos lists a long set of approvals across its products, including UL, FM, NFPA 20, LPCB, VdS and EN 12845. Each approval, however, belongs to a specific model, size and driver; the Fire DNF and Fire HSEF data booklet, for example, covers FM approved 50 Hz versions. Ask for the approval reference of the exact model supplied and check it as in how to check a fire pump’s UL and FM approval. For the wider market picture, see fire pump brands in Saudi Arabia.

After supply: testing and commissioning

Every fire pump set needs an on-site acceptance test to NFPA 20 before handover, then weekly runs and periodic maintenance. See fire pump acceptance testing and commissioning and the NFPA 20 guide, and for diesel drivers see Clarke diesel fire pump engines.

Frequently asked questions

Are Grundfos fire pumps UL listed and FM approved?

Grundfos states that its electric and diesel systems are UL listed and FM approved, and that the 50 Hz Fire DNF and Fire HSEF sets are FM approved according to NFPA 20. Always check the exact model.

What comes with a Fire DNF or Fire HSEF set?

The pump and motor on a base plate, a controller and a circulation relief valve, with a flowmeter approved by FM or UL available as an accessory.

When should I choose a vertical turbine pump?

When the water source is below the pump, such as a deep underground tank or a well, because it needs no priming.

Does AZEIDK supply Grundfos fire pumps?

Grundfos is one of the suppliers AZEIDK works with, and the model is chosen to the project specification. See our fire pumps section.

Choosing a fire pump for your project? Send AZEIDK the required flow and pressure and the type of water source, and our team will compare the options and prepare the submittal. Request a quote from AZEIDK

Share this article