Owners of server rooms, archives and electrical rooms usually ask about the Novec 1230 system cost first, but a single figure tells them very little. A clean agent system using FK-5-1-12 (sold commercially as Novec 1230) is engineered to the room volume and the hazard, so its cost changes from one room to another even when floor areas look similar. This guide explains what drives the cost, what the bill of quantities (BOQ) should show, and how to compare quotations before you send your request.
Key points
- Cost is driven first by the protected volume and design concentration, then by the number of cylinders, pipe length and nozzle count.
- Room integrity affects the agent quantity and the test result, and may add sealing work.
- The detection and release control panel and detectors are part of the system and need their own BOQ line.
- Ask the quotation to state listings (UL or FM), NFPA 2001, testing and handover.
- Only compare quotations built on the same volume, concentration and scope.
What drives the cost of a Novec 1230 system?
| Factor | Why it changes the cost |
|---|---|
| Protected volume | Agent quantity is calculated on the full room volume, plus the ceiling void and raised floor when the design covers them. |
| Design concentration and hazard | The required concentration comes from the listed system manual for the expected fire class; a higher value means more agent and larger cylinders. |
| Cylinder size and count | The SFFECO 1230 system supplied by AZEIDK uses cylinders from 38 to 850 lbs; one cylinder or several on a manifold changes the cost. |
| Piping and nozzles | Route length, nozzle count, ceiling height and the number of zones set the quantity of pipe and fittings. |
| Detection and control | Release control panel, smoke detectors, manual release, abort switch and sounders and strobes. |
| Actuation method | Electrical, pneumatic or mechanical release, and the optional liquid level indicator on larger cylinders. |
| Room condition | Unsealed openings and HVAC penetrations need treatment before the integrity test, work that may sit outside the supplier’s scope. |
| Reserve cylinders | Some projects require main and reserve cylinders, which doubles a large part of the cost. |
To see how the quantity itself is worked out, read Novec 1230 quantity calculation, and for the differences between agents see clean agent suppression comparison.
What the BOQ should show
- Cylinder or cylinders with valve and the actual agent weight per cylinder.
- Brackets, manifold, discharge and actuation hoses where there are several cylinders.
- Pipe, fittings and discharge nozzles with quantities and sizes.
- Release control panel, detectors, manual release and abort switches.
- Sounders, strobes and warning signs at the room entrances.
- Hydraulic calculations and shop drawings.
- Room integrity test, commissioning, handover and training.
- Warranty and any free maintenance period.
A BOQ at this level makes quotations comparable and reduces variation orders after award.
How to compare Novec 1230 quotations
- Check that all quotations use the same dimensions and design concentration, and ask each supplier to state the calculated quantity in kilograms.
- Compare the listings stated for the system itself; the AZEIDK page for SFFECO 1230 states UL 2166 and FM 5600 and compliance with NFPA 2001.
- Check whether the control panel and detectors are included, or assumed to come from the existing fire alarm system.
- Ask about the room integrity test: is it included, and who pays for sealing work if it fails.
- Ask about the cost, location and lead time of recharging after any discharge.
For more on reading offers, see how to compare fire system quotations, and if the room could also take FM200, see what drives the cost of an FM200 system.
Costs after handover
The system needs periodic checks of agent quantity, cylinder pressure, detectors and the control panel in line with NFPA 2001 and the manufacturer’s manual, and the room integrity test should be repeated when walls, doors or HVAC openings change. Put these items in the annual maintenance contract from the start.
How AZEIDK helps
AZEIDK supplies the SFFECO 1230 clean agent fire suppression system as part of its special fire suppression systems, with engineering design and calculations, installation, testing, commissioning and handover and maintenance across Saudi Arabia. For a general introduction see Novec fire suppression systems in Saudi Arabia.
Frequently asked questions
How much does a Novec 1230 system cost for a server room?
There is no fixed price. It depends on room volume, design concentration, cylinder count, pipe length and the room’s condition. Send the room dimensions, layout and contents to receive a quotation based on an actual calculation.
Is the floor area enough to request a quotation?
No. The calculation uses volume, so ceiling height, ceiling voids and raised floors change the quantity. Include length, width, height and any hidden spaces.
Is the room integrity test included in the price?
It varies between offers, so ask for it to be stated. The test shows that the room holds the required concentration; a failed test means sealing work before a retest.
What should I send with the request?
Room dimensions and layout, the type of equipment or contents, whether there is a ceiling void or raised floor, the existing fire alarm system, the city and the planned start date. See what to send with a quote request.
Summary
The cost of a Novec 1230 system is the result of a calculation, not a general figure. Define the volume, hazard and room condition, ask for a detailed BOQ, and compare quotations on the same basis. Send your drawings and room data through the quote request form and the AZEIDK team will prepare a clear quotation.
Related guides
- CCTV Maintenance Contract Template: Visits, Response Times, Spare Parts and Exclusions
- Construction Equipment Rental Shop Requirements in Saudi Arabia: Fire Safety and Civil Defense
- Jack Pump Fire Pump Types: End-Suction, Split Case and Vertical Turbine
- Fire Protection in University Student Housing: Room Detectors, Sprinklers and Shared Kitchens