Fire hose cabinet locations decide how many cabinets go into the BOQ, and whether the hose actually reaches every point on the floor. The usual questions: how many cabinets per floor, how far apart, where relative to stairs and exits, and at what height?
This article gives a practical method, from hose length to a worked office floor example, using the components of the Falcon Gold cabinets supplied by AZEIDK Egypt: red single-door fire hose cabinets manufactured locally in Egypt with genuine Falcon Gold components, including the FG-1001S model shown on the brand page.
Key takeaways
- Coverage is measured along the actual path of travel from the cabinet, not with a circle drawn on the plan.
- The reel hose in the Falcon Gold component submittal is 25 mm x 30 m, and that length is the starting point for cabinet layout.
- NFPA 14 puts Class I outlets (2½ in.) in exit stairs, and its 2019 edition sets 130 ft (39.7 m) for Class II stations with 1½ in. hose and 120 ft (36.6 m) with smaller hose.
- NFPA 14 sets the hose valve height at 0.9 to 1.5 m above the floor, measured to the center of the valve.
- In Egypt the legal reference is the 2026 Egyptian fire code and the Civil Protection approved drawings; NFPA and EN are design references.
Who decides fire hose cabinet locations in Egypt?
Egyptian Building Law No. 119 of 2008 and its executive regulations require the permit applicant to apply fire protection requirements under the Egyptian code. The current edition is the Egyptian Code for the Design and Implementation of Fire Protection for Buildings, 2026 edition (Ministerial Decree No. 355 of 2026), prepared by the Housing and Building National Research Center (HBRC). The General Directorate of Civil Protection (Ministry of Interior) reviews and approves fire system drawings before work starts.
The consultant shows cabinet locations on the drawings under the Egyptian code and may draw on references such as NFPA 14, the EN 671 series or BS 5306-1 (design and installation of hose reels). These are not binding in Egypt on their own, but they explain the logic behind the distances. The approved drawing is the final reference.
A 30 m hose: what does it really cover?
EN 671-1:2012, the European standard for hose reels with semi-rigid hose, requires the hose to be one piece, recommends a maximum length of 30 m, and sets the inside diameter at 19, 25 or 33 mm. This matches the Falcon Gold component submittal published on the brand page: 25 mm x 30 m hose, 12 bar maximum working pressure, a jet/spray adjustable nozzle and a 1.5 x 1 in. angle valve.
But 30 m on paper is not 30 m in every direction. The hose runs through corridors and doors and around walls and furniture, so what matters is the walking path from the cabinet to the farthest point. NFPA 14 (2019 edition) measures Class II distances the same way, along a path of travel from the hose connection.
Water throw beyond the hose end counts only at the value the adopted reference accepts. For example, NFPA 14 (2019 edition, section 7.3.3.1 as quoted by QRFS) requires every part of the floor to be within 130 ft (39.7 m) of a hose connection with 1½ in. hose, or 120 ft (36.6 m) of one with smaller hose. If the consultant follows that logic, a 25 mm hose falls in the “less than 1½ in.” category, so the limit is 120 ft along the path of travel. Hose details are in our article on fire hose types, lengths and working pressure.
Fire hose cabinet locations next to stairs and exits
Firefighting equipment should sit on the escape route, so a person passes it on the way out and uses it with a safe retreat behind them. That is why Egyptian drawings usually show cabinets in the stair lobby or beside the stair door, in the lift lobby and along long corridors.
What the US references say about stairs
- Class I outlets (2½ in., for the fire service) are required in exit stairs. The 2019 edition of NFPA 14 places them at the main floor landing, and the authority having jurisdiction can require the intermediate landing instead. This location has switched between editions, and each edition allows the other location with approval.
- The International Building Code (IBC 2021, as summarized by Consulting-Specifying Engineer) adds outlets on each side of the wall next to a horizontal exit opening.
- The same code adds outlets where the farthest point on the floor is more than 150 ft from an outlet on an unsprinklered floor, or 200 ft on a sprinklered floor.
An occupant hose reel cabinet is not the same as a 2½ in. fire service outlet (see fire hose cabinets: components, types and selection), but placing it beside the stair door serves the same purpose: the user starts from a safe point and moves toward the fire.
Door conflicts
EN 671-1 requires the hose reel cabinet door to open at least 170 degrees so the hose runs out freely. Keep it out of the stair door swing and out of corners that block its own door. If the cabinet is lockable, the standard calls for an emergency opening device protected only by transparent frangible material.
Worked example: an office floor
This hypothetical example shows the method only. A rectangular office floor is 48 m long and 22 m wide, with a main corridor along its length, an exit stair at each end and a lift lobby in the middle. Offices about 9 m deep line both sides.
- Start at the stairs: one cabinet beside each stair door on the floor side, about 2 m from each end of the floor.
- Measure the farthest point: the far corner of the mid-floor office. The hose runs about 22 m along the corridor, then through the office door to the corner: about 33 to 34 m in total.
- Compare: the path is longer than the 30 m hose. Relying on water throw inside a furnished, partitioned office is a weak choice.
- Fix: add a third cabinet in the lift lobby. The longest path from any cabinet drops to about 23 m, well inside the hose length.
| Option | Cabinets per floor | Approx. longest walking path | Assessment |
|---|---|---|---|
| Two cabinets at the stairs only | 2 | 33 to 34 m | Beyond hose length, relies on throw |
| Two at the stairs + one in the lift lobby | 3 | About 23 m | Within hose length with margin |
| Two cabinets at the floor’s third points, away from stairs | 2 | About 26 m | Covers the area but moves cabinets off the escape route |
Many designers prefer the second option, which keeps cabinets on the escape route. The result goes straight into the cabinet line of the fire protection BOQ: 3 cabinets per typical floor, with the ground floor and basement checked separately.
Mounting height: surface or recessed
NFPA 14 sets the hose valve height between 3 and 5 ft (0.9 to 1.5 m) above the floor, measured to the center of the valve, and this stayed unchanged in the 2024 edition. It also added at least 3 in. (75 mm) of clearance around the valve handle for a gloved hand.
For a hose reel cabinet, height comes from the datasheet installation drawing and the approved drawing. A standing person should reach the valve and nozzle easily, and the hose should pull out freely. The Falcon Gold submittal gives a 600 mm reel diameter and 150 mm reel width, useful when checking wall space.
Mounting type:
- Surface-mounted: fixed on the wall face, easiest in existing buildings and warehouses. Check that it does not narrow the escape route.
- Recessed: set into the wall thickness so the corridor stays flush. It needs a thick enough wall, and the effect of the opening on the wall’s fire resistance must be checked if it is a stair or protected corridor wall.
The mounting type required for the FG-1001S cabinet is agreed with the AZEIDK Egypt team before supply, as part of the project submittal.
Common layout mistakes
- Drawing a 30 m radius circle on the plan instead of measuring the walking path. The circle crosses walls. The hose does not.
- Ignoring partitions added after handover. Recheck coverage after any layout change.
- Placing the cabinet behind the stair door or in its swing.
- Joining two hoses to make up a shortfall. The standard calls for a one-piece hose. The fix is an extra cabinet.
- Copying one floor’s layout to another without checking the ground floor and basement.
For extinguisher layout, see how many fire extinguishers you need. Fire hose cabinets are part of the fire fighting systems AZEIDK Egypt works with.
Frequently asked questions
What is the distance between fire hose cabinets?
There is no fixed distance. Every point must reach a cabinet along the walking path within the hose length, or the distance the adopted reference accepts. On partitioned floors, 30 m hoses mean cabinets end up closer together.
Where are fire hose cabinets placed in a residential building?
Usually in the stair lobby or beside the stair door on each floor, since apartments open onto that lobby. Check reach into the farthest apartment if the design requires it.
What is the mounting height of a fire hose cabinet?
For a hose valve, NFPA 14 sets 0.9 to 1.5 m to the center of the valve. For a hose reel cabinet, the height comes from the datasheet installation drawing and the approved drawing, so a standing user can reach the valve and nozzle easily.
Can the hose reel hose be longer than 30 m?
EN 671-1 recommends a maximum of 30 m in one piece. If the hose does not reach, the fix is an extra cabinet, not a longer hose.
Does water throw count toward coverage?
Only at the value the adopted reference accepts. In partitioned spaces, keep the farthest point within the hose length.
Is a recessed fire hose cabinet better than a surface-mounted one?
Not in itself. Recessed suits corridors but needs a thick enough wall and a fire resistance check. Surface is easier in existing buildings.
Conclusion
Start at the stairs and exits, measure the walking path from each cabinet to the farthest point, and add a cabinet wherever the hose does not reach. With the 25 mm x 30 m hose in the Falcon Gold components, a medium office floor often needs a third cabinet in the middle. The final reference is the 2026 Egyptian fire code and the drawing approved by Civil Protection.
Checking cabinet locations on your project drawings? Send us the floor plan and the mounting type you need, and we will send the datasheet and submittal for the Falcon Gold cabinets. Talk to the AZEIDK Egypt team