A hood suppression submittal reaching a Cairo restaurant owner or kitchen contractor is full of part codes: P4000, HP2851, P300, P900. These are the kitchen suppression system components, and each has a set job and a set place on the cooking line. Knowing them makes the submittal easier to review and exposes installation mistakes before a fire does.
Below are the HoodSafer HS components as listed in the submittal on the HoodSafer brand page. For the solution overview, see AZEIDK Egypt’s kitchen fire suppression page.
Key takeaways
- HoodSafer HS is fully mechanical: when a thermobulb link breaks, agent flows to the nozzles and the gas valve closes.
- There are three hood nozzle types: H1 for the duct and filters, H2 for fryers, H3 for range tops and grill plates. Each is identified by the lines marked on it.
- Thermobulb links come in three ratings: 141, 182 and 260 °C. The colour is chosen to suit the appliance below.
- The detection line is limited to 40 m in length and 20 bends.
- Cylinders are 6, 9.5 and 20 L, pressurised with nitrogen to 15 bar at 21 °C, filled with a potassium carbonate based wet chemical agent.
In this article
- How kitchen suppression system components work together
- Hood suppression nozzles: H1, H2 and H3
- Thermobulb links for the kitchen system
- Detection line and corner pulleys
- Manual pull station P300
- Mechanical gas shut-off valve
- Agent cylinder and activation mechanism
- Distribution pipe
- Component checklist: submittal and site
- Common mistakes with kitchen suppression components
- Frequently asked questions
- Summary
How kitchen suppression system components work together
The system has three groups: detection (thermobulb links on a stainless steel tension wire inside the hood), actuation and storage (an activation mechanism on the agent cylinder), and distribution and shut-off (stainless steel pipe to the nozzles, plus a cable-operated gas valve).
When a link breaks from heat, the wire loses tension and trips the mechanism. Nitrogen drives the agent to the nozzles while the lever pulls the gas valve shut. The pull station at the end of the line does the same by hand. The HSP series, by contrast, uses pneumatic detection.
On the legal side, the reference in Egypt is the Egyptian Code for the Design and Implementation of Fire Protection for Buildings (2026 edition), together with what the General Directorate of Civil Protection approves on the project drawings. EN 17446 is the European product test standard; the system was tested to it and holds BSI Kitemark certificate KM 767382.
Hood suppression nozzles: H1, H2 and H3
The nozzle type sets the spray angle over the cooking surface. All three are full cone nozzles, marked with lines on the body because they look alike.
| Nozzle | Code | Spray angle | Marking | Use per the manual |
|---|---|---|---|---|
| H1 | P4000 | 40 to 60° | One line | Exhaust duct, filter plenum and hood filters |
| H2 | P5000 | 20 to 35° | Two lines | Deep fat fryers and bratt pans |
| H3 | P6000 | 70 to 90° | Three lines | Gas range tops and grill plates |
A fryer needs a narrow, concentrated spray onto the oil (H2); a wide range top or grill plate needs a wide cone (H3). The duct nozzle is aimed at the centre of the duct opening within about 3 cm, and the filter nozzle sits at the centre of the plenum within 5 cm, no more than 45 cm from the filter face for V-type filters. The design table in the manual names the nozzle type for each appliance, so check against that table rather than the general description alone.
Nozzle height above the appliance
The manual gives appliance nozzle heights of typically 90 to 115 cm above the cooking surface, with some appliances listed differently in its table. Each nozzle has a cap (P602) that keeps grease out of the orifice, and every cap should be checked.
What to check: the drawing names a nozzle type for every appliance, the installed nozzle carries the matching number of lines, and height and aim match the drawing.
Thermobulb links for the kitchen system
The thermobulb link is the detector in the HS system: a heat-sensitive element that breaks at a set temperature, hung on the tension wire inside the hood. Its colour tells you its rating:
| Rating | Colour | Code | Use per the manual |
|---|---|---|---|
| 141 °C | Blue | HP2751 | Appliances without open flame |
| 182 °C | Purple | HP2851 | Fryers, range tops, skillets and woks |
| 260 °C | Black | HP2951 | Barbecues and open-flame grills |
Links are mounted 125 to 160 cm above the highest appliance surface. On hoods longer than 120 cm, the manual adds a detector roughly every 137 cm. Above a charcoal grill in a kebab restaurant, normal working heat can break a 141 °C link with no fire and cause a false discharge, while a 260 °C link over an electric appliance may respond late.
What to check: the colour of each link against the appliance below it, its height, and that it is not coated in grease. Periodic link replacement is covered in our HoodSafer maintenance article.
Detection line and corner pulleys
The detection line is a stainless steel tension wire that carries the links and connects the hood, the activation mechanism and the manual pull station. Inside the hood the wire runs bare so the links see the heat directly. Outside the hood it runs inside 18 mm aluminium conduit clamped every metre. At every change of direction, and where the line enters and leaves the hood, corner pulleys (P900) let the wire move freely.
The line is limited to 40 m and 20 bends. Each bend adds friction that can stop the mechanism from tripping, which matters in tightly packed cloud kitchens and in hotel kitchens with the cylinder in another room.
Manual pull station P300
The pull station lets any kitchen worker fire the system if they see the fire before a link breaks. It is fitted at the end of the detection line, at least 140 cm above the floor and at least 2 m from the hood.
Whoever pulls it should not be standing under a burning hood. As good practice, put it on the staff exit route, in plain view.
What to check: height, distance and a clear path, and that every shift knows where it is.
Mechanical gas shut-off valve
Cutting the gas removes the ignition source, so the system includes a brass gas shut-off valve, 1 inch BSPP, normally closed and fully mechanical. It is linked to the activation mechanism lever by a cable in 18 mm aluminium conduit, so it closes with the discharge without any power. The submittal notes other sizes are available on request.
The manual also recommends a microswitch to stop the exhaust fans on activation, a point to coordinate with the ventilation contractor.
What to check: the valve size matches the kitchen gas supply line, it sits on the line feeding all appliances under the hood, and its cable runs without sharp bends.
Agent cylinder and activation mechanism
The cylinder stores the wet chemical agent, pressurised with nitrogen to 15 bar at 21 °C. The agent is a potassium carbonate based solution, heavier than water. It reacts with hot oil to form a soap-like layer that seals the surface from air and helps cool it. The activation mechanism on top of the cylinder carries a pressure gauge, an activation indicator and a microswitch (P200).
| Model | Cylinder | Agent weight | Dimensions |
|---|---|---|---|
| HS-4 | 6 L | 8.6 kg | 150 × 470 mm |
| HS-8 | 9.5 L (product sheet states 10 L) | 13.6 kg | 190 × 520 mm |
| HS-16 | 20 L | 28.8 kg | 242 × 653 mm |
The operating range is +5 to +49 °C; hotter spots, such as Red Sea hotel kitchens in summer or rooftop kitchens, need ventilation or cooling. Mount the cylinder at least 1 m from the hood, on a bracket fixed to a solid surface.
What to check: the gauge needle is in the green zone, the activation indicator shows normal, and the cylinder bracket is fixed to a solid surface and the cylinder is secured in it.
Distribution pipe
The submittal specifies AISI 304 or 304L stainless steel pipe, SCH40, 3/8 inch, with a minimum wall of 2.30 mm. Galvanised pipe is not allowed, and threads are sealed with a chemical thread sealant, not PTFE tape. Pipe is clamped every 1.5 m outside the hood and every metre inside it, and each model has a maximum pipe length that includes the equivalent lengths of elbows and tees. The installation steps themselves are covered in our HoodSafer installation article.
Component checklist: submittal and site
| Component | In the submittal | On site |
|---|---|---|
| Nozzles | Nozzle type for each appliance on the drawing | Number of lines, height, aim and cap |
| Thermobulb links | Rating and colour for each position | Colour over each appliance, height, cleanliness |
| Detection line | Length and number of bends | Pulleys, aluminium conduit outside the hood |
| Pull station | Location on the drawing | At least 140 cm high and 2 m from the hood |
| Gas valve | Size and thread type | Matches the gas line, cable route |
| Cylinder | Capacity for the model | Gauge pressure, bracket, at least 1 m from the hood |
| Pipe | SS304 SCH40, 3/8 inch | No galvanised pipe, no PTFE tape |
Choosing the model for a given hood and appliance line-up is covered in our restaurant fire suppression sizing article.
Common mistakes with kitchen suppression components
- Fitting a wide H3 nozzle over a deep fryer, or the reverse, because the nozzles look alike.
- Using 141 °C links above a charcoal grill, leading to a discharge with no fire.
- Going past 20 bends on the detection line, or running the wire outside the hood without aluminium conduit.
- Mounting the pull station right next to the hood or behind the kitchen door.
- Placing the cylinder beside an oven or anywhere above 49 °C.
Frequently asked questions
What is the difference between H1, H2 and H3 hood nozzles?
Spray angle and use. H1 sprays 40 to 60° for the duct and filters, H2 sprays 20 to 35° for fryers, and H3 sprays 70 to 90° for range tops and grill plates. They are marked with one, two or three lines.
How do I choose the thermobulb link colour?
By appliance: blue 141 °C for appliances without open flame, purple 182 °C for fryers and range tops, and black 260 °C for barbecues and open-flame grills, always following the designer’s drawing.
Does HoodSafer HS need electricity to work?
No. The HS series is fully mechanical, from detection to closing the gas valve. The manual recommends wiring the microswitch on the activation mechanism to stop the exhaust fans in a fire.
Where does the manual pull station go?
At the end of the detection line, at least 140 cm above the floor and at least 2 m from the hood, ideally on the staff exit route.
Summary
Each HoodSafer component is tied to what it protects: nozzle angle, link rating, gas valve size, cylinder location. Check them in the submittal and again on site.
Reviewing a kitchen system submittal for a restaurant or hotel? Send us the hood drawing and the list of appliances under it, and we will go through nozzle and link selection and cylinder location with you. Talk to the AZEIDK Egypt team
Related guides
- Fire System Maintenance on the North Coast and Ain Sokhna Before Summer: Salt Air, Seasonal Shutdown, Pumps, Alarms and Extinguishers
- FM-200 System Maintenance: Semi-Annual Checks, Cylinder Weighing, Room Integrity
- Fire Extinguisher for an Apartment: Type, Size and Where to Hang It
- AFC A-3150 Flanged and A-3500 Grooved Check Valves: Pressure, Sizes and Installation







