Restaurant Fire Suppression: Sizing HoodSafer HS-4, HS-8 or HS-16

Restaurant Fire Suppression: Sizing HoodSafer HS-4, HS-8 or HS-16

Choosing a restaurant fire suppression system starts with one practical question: what exactly sits under the hood? Hood length, ducts, filters and cooking appliances decide the size.

This article shows how to count flow points for a HoodSafer HS series system, how to choose between the HS-4, HS-8 and HS-16, and when two cylinders must be linked. All figures come from the AZEIDK Egypt HoodSafer page and the manufacturer’s technical manual and catalogue.

Key takeaways

  • The HS-4, HS-8 and HS-16 differ in flow capacity: 4, 8 and 16 flow points.
  • Each nozzle uses one or two flow points depending on its type. The total for all nozzles sets the model.
  • Fryers and bratt pans need an H2 nozzle worth two points. Most other items need one.
  • Above 16 points, the load is split between two linked systems: the smaller one for the hood, the larger one for the appliances.
  • After choosing a model, check the maximum discharge line length: 8, 16 or 24 m equivalent, by model.
  • The manual gives an operating range of +5 to +49 °C. Check it in hot kitchens.
In this article
  1. The framework: Egyptian code, standards and product certification
  2. What to collect before sizing a restaurant fire suppression system
  3. How flow points are counted
  4. HS-4 vs HS-8 vs HS-16
  5. Worked selection examples
  6. When 16 points are not enough: linking cylinders
  7. Other factors that affect the choice
  8. Common mistakes when choosing a kitchen system
  9. Frequently asked questions
  10. Conclusion

The framework: Egyptian code, standards and product certification

The legally binding fire protection reference in Egypt is the Egyptian Code for the Design and Implementation of Fire Protection for Buildings, 2026 edition (Ministerial Decree No. 355 of 2026). The General Directorate of Civil Protection (Ministry of Interior) approves project drawings and systems. Kitchen system design details come from technical references: EN 17446:2021 for fire extinguishing systems in commercial kitchens, NFPA 17A (2024 edition) for wet chemical systems, and NFPA 96 for ventilation and fire protection of commercial cooking.

EN 17446 covers protection of cooking appliances, the hood, the plenum (the space behind the filters) and the extract ducts. UL 300, mentioned for context only, is the US fire test standard for commercial cooking protection systems. The AZEIDK Egypt HoodSafer page states that the HoodSafer HS system is certified to EN 17446:2021 with BSI Kitemark (certificate KM 767382) and approved by the General Administration of Civil Protection. These approvals belong to the product, not to the supplier. The BSI client directory lists the certificate against BS EN 17446:2021+A1:2024, the current amended version.

For how these systems work, see our commercial kitchen fire suppression guide. This article covers sizing only.

What to collect before sizing a restaurant fire suppression system

The manufacturer’s manual says the system is designed around the hood type, dimensions, divisions and height, the number and size of ducts, and the type and size of each appliance. In practice the supplier needs:

  1. Total hood length, and whether it is one piece or divided into sections.
  2. The number of exhaust ducts and the shape of each: round (diameter) or square (dimensions).
  3. Filter type: a single slanted row or a V arrangement, and the filter height.
  4. The appliances under the hood with the cooking surface size of each: single or double fryer, griddle (grill plate), range top, charcoal or gas grill, wok.
  5. The gas type and the diameter of the gas line into the kitchen, to select the gas shut-off valve.
  6. A proposed location for the cylinder and for the manual pull station.

How flow points are counted

A flow point is the capacity unit of the HS series. The manufacturer uses three nozzle types. H1 and H3 each use one point. H2 uses two points because it protects appliances that hold deep oil. Add up the points for every nozzle needed to protect the hood and appliances, then choose the smallest model that covers the total. The counting rules in the manual:

Protected itemLimit per nozzle (manual)Nozzle typePoints
Round ductUp to 40 cm diameter (two nozzles up to 60 cm)H11 per nozzle
Square ductUp to 40 × 40 cm (two nozzles up to 40 × 60 cm)H11 per nozzle
Hood filters and plenumOne nozzle for a hood up to 3 m, then one per extra 2 m, and one per section of a divided hoodH11 per nozzle
Range top70 × 70 cmH31
Griddle (grill plate)60 × 120 cmH31
Charcoal, gas, stone and electric grills70 × 70 cmH11
WokUp to 70 cm diameter, 20 cm deepH11
Single deep fat fryer60 × 60 cmH22
Double deep fat fryerTwo pans of 26 × 60 cmH22
Bratt pan60 × 60 cmH22

An appliance larger than the limit needs more than one nozzle, and its points are added. For a duct larger than the limit, the manual adds one nozzle for every extra 20 cm. Nozzle heights and positions are installation details, covered in our article on HoodSafer installation and acceptance.

HS-4 vs HS-8 vs HS-16

All three models work the same way. Actuation is fully mechanical and needs no cartridge or other pressurised auxiliary component. The system operates automatically when a glass heat detector (thermobulb) bursts, or manually from the pull station, and a gas shut-off valve cuts the gas. The differences are capacity and piping limits:

ItemHS-4HS-8HS-16
Flow points4816
Wet chemical fill (technical manual)6 L9.5 L20 L
Maximum discharge line (straight equivalent)8 m16 m24 m
Indicative hood length in manufacturer catalogueNot statedUp to 2.4 mUp to 4.8 m
Example use (illustrative)Café or kiosk with a short hood and one or two appliancesRestaurant with one cooking line including a fryerLong cooking line with several fryers

The catalogue notes that the indicative hood length can change with hood features. The deciding factors are the total flow points and the discharge line length. Cylinders are pressurised with nitrogen to 15 bar at 21 °C.

Worked selection examples

The first example is our illustration using the manual’s rules. The others come from the manual. None is a completed project.

Café with a 1.5 m hood

One round duct of 35 cm (1 point), slanted filters (1 point) and a 60 × 120 cm griddle (1 point). Total: 3 points. An HS-4 is enough with one spare point, if the discharge line stays within 8 m equivalent.

Restaurant with a 3 m hood and one fryer

One 40 × 40 cm duct (1), filters (1), a single fryer (2), a range top (1) and a griddle (1). Total: 6 points. The manual states that an HS-8 suits this example.

Restaurant with a 4 m hood and two ducts

Two ducts (2), V filters on a hood longer than 3 m (4), a double fryer larger than the limit that needs two nozzles (4), a single fryer (2), and a range top and griddle (2). Total: 14 points, so an HS-16 fits.

Kitchen with a 6 m hood in three sections

The manual’s example totals 21 points, more than an HS-16 can cover. Its solution is to split the load: 6 points for ducts and filters on an HS-8, and 15 points for appliances on an HS-16, with the two systems linked.

When 16 points are not enough: linking cylinders

The technical manual sets clear rules for multi-cylinder applications. The smaller system protects the hood and ducts. The larger system protects the appliances and is called the master. The detection line, pull station, microswitch and gas valve line connect to the master only. When the master operates, it releases the slave system’s mechanism through a linking cable. The manufacturer’s catalogue states that the HS series accepts up to 5 linked cylinders.

Other factors that affect the choice

Heat detector rating by appliance

The manual lists three glass detector ratings: 141 °C for appliances without open flame, 182 °C for fryers, range tops and woks, and 260 °C for open-flame grills. Name charcoal or wood grills in the appliance list so the right detector is fitted.

Gas shut-off valve and microswitch

The gas shut-off valve datasheet gives a 1 inch BSPP size, with other diameters available. It works mechanically via the actuation lever. The manufacturer recommends wiring the microswitch to stop the exhaust fans in a fire, because this improves suppression performance.

HS or HSP

The HS series is fully mechanical. The HSP series uses pneumatic detection and an electrical gas shut-off valve. The catalogue states that HSP accepts a maximum of two linked cylinders.

Ambient temperature at the cylinder

The manual gives an operating range of +5 to +49 °C. Above that, ventilation or cooling is required. The manual also requires mounting the cylinder at least 1 m from the hood, away from direct heat.

Common mistakes when choosing a kitchen system

  • Choosing the model by hood length without counting flow points for each appliance and duct.
  • Counting a fryer as one point, although it needs a two-point H2 nozzle.
  • Matching the count exactly, then adding an appliance after commissioning. The manual requires the system to be reviewed whenever appliances or their positions change.
  • Ignoring the equivalent discharge line length for a cylinder far from the hood.
  • Not mentioning open-flame grills, so a detector with the wrong rating is fitted.

Frequently asked questions

Is an HS-4 enough for a small café?

Yes, if the total is 4 points or fewer, such as a short hood with one duct, filters and one or two appliances without a fryer. A fryer alone uses two points.

Should I choose a model larger than needed?

A margin helps if more appliances are planned, but the count and the discharge line length decide. Review both after any appliance change.

What certifications are stated for HoodSafer?

The AZEIDK Egypt HoodSafer page states that the system is certified to EN 17446:2021 with BSI Kitemark (certificate KM 767382) and approved by the General Administration of Civil Protection.

What should I send to get an accurate quote?

Hood length and sections, the number and size of ducts, filter type, the appliance list with sizes, the gas line diameter, and photos or a sketch of the kitchen.

Conclusion

Sizing a restaurant fire suppression system is an orderly count: one point per duct, per filter group and for most appliances, two per fryer, then the smallest model that covers the total. Then check the discharge line, cylinder location and gas line size. Above 16 points, linking two systems is the manufacturer’s solution. AZEIDK Egypt supplies HoodSafer as part of its kitchen fire suppression solutions, with supply, installation, testing, and maintenance and technical support. Technical documents can be requested through the documents page.

Not sure which model fits your kitchen? Send us the hood dimensions, the appliance list and the gas line size, and we will send you the flow point count and the recommended HoodSafer model. Talk to the AZEIDK Egypt team