The first question a fuel station owner asks before the civil protection inspection is how many fuel station fire extinguishers are needed, which types, and where they go. In Egypt the answer depends on the number of dispensing pumps at the station, not on plot area or staff numbers.
This article collects what has been published about the special requirements for car fuelling stations under the Public Shops Law: the table of 12 kg dry powder and 45 L foam extinguishers by number of pumps, the two CO2 units beside the main electrical panel, and one extinguisher per EV charging outlet, with a worked example for a 6-pump station. You can review the available types and sizes on the AZEIDK Egypt fire extinguishers page.
Key takeaways
- According to the published requirements, the count rises from 3 x 12 kg powder and 1 x 45 L foam for a 1 to 3 pump station, up to 20 powder and 5 foam for a 16 to 20 pump station.
- Add two 6 kg CO2 units beside the main electrical distribution panel and at least 3 buckets of fine sand.
- Each EV charging outlet needs one 6 kg portable extinguisher, and the outlet must be at least 5 m from the hazard source.
- The published requirements also call for a fire water network with at least two hose points and no less than 4.5 bar at the farthest point.
- We could not find the official published text of these requirements. The figures here are attributed to the Egyptian press, so confirm the final count with civil protection before buying.
In this article
- Where do fuel station extinguisher requirements come from in Egypt?
- Fuel station fire extinguishers by number of pumps
- Items outside the pump table
- Worked example: 6 pumps and two EV chargers
- Matching PYRAMID extinguishers to each item
- Fire water network and fire pumps at the station
- Common mistakes
- Frequently asked questions
- Summary
Where do fuel station extinguisher requirements come from in Egypt?
A car fuelling station is a public shop licensed under Public Shops Law No. 154 of 2019. The Higher Committee for Licensing Public Shops issues general requirements for all shops and special requirements for each activity. In December 2022 and January 2023, Egyptian outlets including El Watan and Parlmany published a summary of the special requirements for fuel stations. It covered the extinguisher table, the fire water network and EV charging.
We searched for the official text in Al-Waqa’i al-Masriya (the official gazette) and in published committee decisions, and did not find it online. So the figures below are given according to the requirements as published by El Watan (17 December 2022) and Parlmany (20 January 2023), with both cited at the end. In practice, what the governorate civil protection department asks for at inspection is final.
Two more points apply. Higher Committee Decision No. 68 of 2022 lists fuel stations, including EV charging stations, among activities that need approval from the competent security authority before licensing. Ministry of Housing Decree No. 25 of 2012 amended some general requirements for petroleum stores and car fuelling stations. The design of fire systems themselves follows the Egyptian Code for the Design and Implementation of Fire Protection for Buildings, 2026 edition (Ministerial Decree No. 355 of 2026).
If your premises is an ordinary shop rather than a station, see civil protection requirements for shops in Egypt.
Fuel station fire extinguishers by number of pumps
This is the table published in the press summaries. Powder means dry chemical powder; foam means a 45 L foam unit.
| Pumps at the station | 12 kg dry powder | 45 L foam |
|---|---|---|
| 1 to 3 | 3 | 1 |
| 4 to 7 | 9 | 2 |
| 8 to 11 | 13 | 3 |
| 12 to 15 | 17 | 4 |
| 16 to 20 | 20 | 5 |
The published table stops at 20 pumps. Larger stations, and highway sites that combine petrol, diesel and gas, should agree the count with civil protection. The summary also does not say whether “pumps” means dispensers or nozzles. Ask the department before inspection, because the answer can move a station into the next band.
Items outside the pump table
CO2 beside the main electrical panel
According to El Watan, two 6 kg CO2 extinguishers are required beside the station’s main electrical distribution panel. CO2 is used here because it does not conduct electricity and leaves no residue. The Parlmany summary also says electrical rooms, where present, need a suppression method using a suitable smothering gas. For CO2 sizes and use in electrical rooms, see PYRAMID CO2 extinguishers.
EV charging
Many new stations add EV chargers. The published requirements place the charging outlet at least 5 m from the hazard source and require one 6 kg portable extinguisher per outlet. The summary does not name the agent, so agree it with civil protection and the charger manufacturer’s instructions.
Sand buckets and alarm
The published summary asks for at least 3 buckets of fine sand per station, and an automatic fire alarm in enclosed areas such as offices, the store and the mini market.
Worked example: 6 pumps and two EV chargers
A station on a road in a new city has 6 pumps, one main electrical panel, a mini market and two EV chargers. Under the published requirements the list is:
| Item | Qty | Basis |
|---|---|---|
| 12 kg dry chemical powder extinguisher | 9 | 4 to 7 pump band |
| 45 L foam extinguisher | 2 | 4 to 7 pump band |
| 6 kg CO2 extinguisher | 2 | Beside the main electrical panel |
| 6 kg portable extinguisher | 2 | One per charging outlet |
| Fine sand bucket | 3 | Minimum per station |
That is 15 extinguishers and 3 sand buckets. If the station adds two pumps to reach 8, it moves to the 13 powder and 3 foam band: 4 more powder units and one more foam unit. So base the count on the final number of pumps in the drawings, not on phase one.
Matching PYRAMID extinguishers to each item
Every item above has a match in the PYRAMID range supplied by AZEIDK Egypt:
- 12 kg powder: stored-pressure ABC powder extinguisher to EN3 and Egyptian standard ES 8442/2021, with powder to EN 615 and ES 4833, carrying the Egyptian quality mark.
- 45 L foam: wheeled AFFF foam unit in 25 and 45 L sizes, intended for fuel and flammable liquid storage areas. It forms a foam blanket that limits re-ignition. Details in PYRAMID AFFF foam extinguishers.
- 6 kg CO2: to EN3 and Egyptian standard ES 735.
A 45 L foam unit is not wall-mounted. It stands on level ground near the pump islands or the tank fill points, with a clear path so it can be wheeled out fast. The 12 kg units are spread between islands so an attendant can reach one without crossing the spill area. The published summary gives no spacing distances, so follow the approved drawings and use NFPA 10 (2026 edition) as a technical reference, which is not legally binding on its own.
Fire water network and fire pumps at the station
Extinguishers are only part of it. According to the requirements published by El Watan, a car fuelling station needs a fire water network fed from the public mains, with at least two hose points. Each point is a hose cabinet, hose and 1.5 inch multi-purpose nozzle, with at least 4.5 bar at the farthest point. Pressure is boosted by an electric pump with a standby power source or by a diesel pump.
Where there is no city water, as on desert highway sites, a dedicated firefighting tank of at least 30 m3 is required, plus two fire pumps, one electric and one diesel, each rated at no less than 250 GPM. The actual pump selection comes from the designer’s hydraulic calculation, because the published minimum does not account for pipe friction losses.
Common mistakes
- Counting for 3 pumps and adding pumps later: inspection checks what is built. Moving from the 1 to 3 band to the 4 to 7 band takes powder from 3 to 9 units.
- Replacing the 45 L foam with small foam units: the published requirement names a 45 L capacity. Several 9 L foam units are not a stated alternative.
- Putting a powder unit at the electrical panel instead of CO2: the published requirement specifies 6 kg CO2 for the main panel.
- Forgetting the EV chargers: each outlet has its own extinguisher, counted separately from the pump table.
- Buying units without a clear label: each extinguisher should show the manufacturer, standard and fill date, and its certificates should be ready for inspection.
- Neglecting upkeep after licensing: extinguishers exposed to sun and dust at a station need periodic inspection and refilling per the manufacturer’s instructions, which AZEIDK Egypt maintenance and refill services cover.
Frequently asked questions
How many extinguishers does a 4-pump fuel station need?
Under the published requirements it falls in the 4 to 7 band: 9 x 12 kg powder and 2 x 45 L foam, plus two 6 kg CO2 units beside the main electrical panel and 3 sand buckets.
Are these figures from an official text?
El Watan and Parlmany published them as the special requirements for fuel stations under the Public Shops Law. We did not find the official text online, so confirm the count with the governorate civil protection department.
Is dry powder alone enough for a fuel station?
No. The published requirements combine 12 kg powder, 45 L foam and CO2 for the electrical panel, because each agent has a different role in fuel and electrical fires.
What about a station with more than 20 pumps?
The published table stops at 20 pumps. For larger stations the count is set with civil protection and on the approved drawings.
Does a natural gas station follow the same table?
The published summary covers fuel stations. Natural gas stations have their own siting requirements, so check them with the competent authorities before choosing extinguishers.
Summary
Fuel station extinguishers in Egypt start from the pump count. Then add two CO2 units for the main electrical panel, one unit per EV charging outlet, the sand buckets, and the fire water network. Count on the final number of pumps, ask civil protection how pumps are counted, and keep extinguisher labels and certificates ready for inspection.
Building a new station or renewing a licence? Send us the number of pumps, charging outlets and the main panel location, and we will prepare the PYRAMID extinguisher list with datasheets and a maintenance schedule. Talk to the AZEIDK Egypt team