1500 GPM Fire Pump from 3PUMP at 10 bar: Large Projects and Pump Rooms

1500 GPM Fire Pump from 3PUMP at 10 bar: Large Projects and Pump Rooms

In large factories, wide warehouses and projects that combine an extensive sprinkler network with hose cabinets, the calculated demand can go above 1000 GPM. That is where the 1500 GPM fire pump question comes up. Moving to this size changes more than the pump. It changes the whole pump room: power supply, diesel engine and fuel tank, test line and suction piping.

This article covers the 3PUMP 1500 GPM at 10 bar set as shown in the datasheet published by AZEIDK Egypt, when it fits a project, and what the pump room needs before delivery. It is part of the fire pump systems AZEIDK Egypt supplies.

Key takeaways

  • The set has an electric main pump and a diesel standby pump of the same end suction model, 3P 6×5-12.4, a jockey pump and separate controllers.
  • Electric motor: 250 HP. Diesel engine: 6120Ti, 240 HP, per the datasheet.
  • Pressure at 150% flow is 8.50 bar and shutoff pressure is 10.88 bar, both inside the NFPA 20 limits for a 10 bar rating.
  • Testing at 150% means flowing about 2250 GPM, so the test header or flow meter and the water discharge route must be designed for that figure.
  • Sets supplied in Egypt are Non-Listed. UL/FM-listed versions are manufactured and supplied on request.
In this article
  1. When does a project need a 1500 GPM fire pump?
  2. What is in the 3PUMP 1500 GPM at 10 bar set
  3. The pump room: what changes at 1500 GPM
  4. Jockey pump and controllers
  5. 1500 GPM at 10 bar or at 12 bar?
  6. Non-Listed or UL/FM?
  7. Common mistakes on 1500 GPM projects
  8. Frequently asked questions
  9. Conclusion

When does a project need a 1500 GPM fire pump?

Under NFPA 14 (2019 edition), standpipe demand in a fully sprinklered building is capped at 1000 GPM. Demand above 1000 GPM therefore usually comes from the sprinkler system itself plus the hose allowance, as in high-piled storage or large production halls. The approved hydraulic calculation for each project sets this figure, not the floor area alone.

An illustrative example: a factory in Sadat City where the consultant calculates 1300 GPM at 9 bar at the pump discharge. A 1000 GPM set is not enough, because 1300 GPM sits at 130% of its rated flow and its pressure drops at that point. On the 1500 GPM at 10 bar set, the point falls between rated flow and the 150% point, so you read the pressure at 1300 GPM from the datasheet curve and compare it with the requirement. That curve reading is the deciding step, not the figure on the nameplate.

The binding reference in Egypt is the Egyptian Code for the Design and Implementation of Fire Protection for Buildings, 2026 edition (Ministerial Decree No. 355 of 2026), with drawings approved by the General Directorate of Civil Protection. NFPA 20 and NFPA 14 are technical references for design and testing.

What is in the 3PUMP 1500 GPM at 10 bar set

The table brings together the main set data from the datasheet. The datasheet also lists an RV10-12 jockey pump (40 GPM, 10 bar, 4.0 kW), a PACIFIC pressure switch, ONTOR/GALA valves and three individual LS controllers made in Korea. More than one electric motor option is listed (INTEM, MARATHON, TECHTOP and OMEC) at 2960 to 2975 rpm. The motor data table for 250 HP (186 kW) gives 94.0% full-load efficiency, full-load current of 351 A at 380 V, 334 A at 400 V and 322 A at 415 V, locked-rotor current of 2500 A at 400 V, and an approximate weight of 1100 kg. The published performance curve is drawn at 2950 rpm.

ItemElectric pumpDiesel pump
Model3P 6×5-12.4, end suction3P 6×5-12.4, end suction
Duty point1500 GPM at 10 bar1500 GPM at 10 bar
Approximate metric flowAbout 341 m³/hAbout 341 m³/h
Driver250 HP electric motor6120Ti diesel engine, 240 HP
Pressure at 150% flow8.50 bar
Shutoff pressure10.88 bar

NFPA 20 requires at least 65% of rated pressure at 150% of rated flow, here 6.5 bar, and a shutoff pressure no higher than 140%, here 14 bar. 8.50 bar is about 85% of rated pressure and 10.88 bar about 109%. That is a fairly flat curve, so pressure does not climb much at low demand. To compare this set with the other duty points, see choosing a 3PUMP fire pump set by flow and pressure.

The pump room: what changes at 1500 GPM

Power supply

A 250 HP motor needs early coordination with the electrical engineer: transformer capacity, generator rating if it feeds the pump room, cable size and the starting method shown in the controller. Hand over the complete motor data page from the datasheet, not just the horsepower. Our article on fire pump power calculation explains how flow, pressure and power relate.

Diesel engine and fuel tank

The 240 HP engine is the largest among the 3PUMP sets documented in Egypt, so its tank is the largest too. NFPA 20 sizes the tank on run hours at rated power plus allowances for sump and expansion. The full method, with a figure for each set, is in diesel fire pump fuel tank size. The engine also needs enough pump room ventilation and an exhaust line that discharges to a safe place.

Test line and water discharge

The performance test runs at three points: shutoff, rated flow and 150% of rated flow. At 1500 GPM the last point means about 2250 GPM. The test header or flow meter must handle that flow, and the water needs a discharge route or return to the tank that does not flood the site. Testing is covered in fire pump testing in Egypt.

Suction and tank

The higher the flow, the more the suction pipe diameter, length and number of bends matter, because any extra loss reduces the pressure available at the pump inlet. Check the water tank volume against the required duration in the approved design.

Jockey pump and controllers

The set comes with a jockey pump that holds network pressure and makes up small leaks, and with a separate controller for each pump. The jockey start and stop settings sit above the electric pump start, with the diesel start below both, as explained in jockey pump pressure settings. At handover, check each controller’s signals to the fire alarm panel as the approved design requires.

1500 GPM at 10 bar or at 12 bar?

AZEIDK Egypt also offers a 1500 GPM at 12 bar duty point. Its datasheet has not been published yet, so we give no data for it here. The selection rule is the same: if the pressure needed at the pump discharge at the design flow is higher than the 10 bar set’s curve delivers, ask the AZEIDK Egypt team for the 12 bar data with the quotation. Do not rely on an approximate figure.

Non-Listed or UL/FM?

The 3PUMP sets AZEIDK Egypt supplies at the listed duty points, including 1500 GPM at 10 bar, are Non-Listed. If the owner, insurer or consultant requires a listed set, UL/FM versions are manufactured and supplied on request. On large projects this requirement often sits in the insurance documents, so settle it before pricing and write it clearly into the specification and BOQ.

Common mistakes on 1500 GPM projects

  • Selecting the set on rated flow without reading the curve pressure at the actual design flow.
  • Designing the test line for 1500 GPM and forgetting that the test reaches about 2250 GPM.
  • Leaving electrical coordination for the 250 HP motor until installation.
  • Sizing the fuel tank on the electric motor rating instead of the diesel engine rating.
  • A long suction pipe with many bends that cuts inlet pressure.
  • Writing UL/FM in the BOQ, then accepting a Non-Listed set without changing the specification.

Frequently asked questions

Which pump model is used in the 3PUMP 1500 GPM set?

The 3P 6×5-12.4 end suction model for both the electric and diesel pumps, per the datasheet.

Why is the diesel engine 240 HP and the motor 250 HP?

Each driver is chosen on its rated power at its own speed and the pump curve at that speed. The manufacturer’s data governs in both cases.

What is the shutoff pressure of this set?

10.88 bar per the datasheet, about 109% of rated pressure and below the NFPA 20 limit of 140%.

At what flow is peak performance tested?

At 150% of rated flow, about 2250 GPM, where pressure must not fall below 65% of rated pressure.

Is a 1500 GPM set available above 10 bar?

Yes. A 1500 GPM at 12 bar duty point is available, and its datasheet has not been published yet. Ask the AZEIDK Egypt team for its data.

Is the set UL listed or FM approved?

No. The set supplied in Egypt is Non-Listed. UL/FM versions are manufactured and supplied on request.

Conclusion

The 3PUMP 1500 GPM at 10 bar set pairs a 250 HP electric pump and a 240 HP diesel pump of the same 3P 6×5-12.4 model, and its curve sits inside the NFPA 20 limits. It suits factories, warehouses and projects whose calculated demand goes above 1000 GPM, provided the curve covers the pressure needed at the design flow. At this size the key is to prepare the pump room with it: power, fuel, test line and suction.

Does your factory or warehouse demand go above 1000 GPM? Send us the duty point and the pump room drawings. We will check them against the datasheet curve and confirm whether 1500 GPM at 10 bar is enough. Talk to the AZEIDK Egypt team

Share this article