A grooved flange adapter turns the grooved end of a pipe into a flange, so it bolts directly to a flanged valve, pump or other equipment without welding a flange onto the pipe. In Saudi Arabia AZEIDK supplies the Shurjoint Model 7041 flange adapter for ANSI Class 125/150 flanges, in sizes 2 to 24 inch, rated at 300 psi (20 bar) maximum working pressure according to the Shurjoint catalogue.
This article covers where flange adapters are used in pump rooms and risers, the sealing surface rules, when a sandwich plate is needed, and the correct tightening sequence.
Key takeaways
- Shurjoint 7041: 2 to 12 inch supplied hinged as one assembly; 14 to 24 inch (7041N) as two segments with a draw kit.
- 300 psi maximum working pressure for every size in the ANSI 125/150 table, based on roll grooved standard wall carbon steel pipe.
- The catalogue also lists PN10/16 and BS 10 Table E drillings, and Model 7043 for Class 300.
- It needs a hard, flat mating face. With serrated faces or rubber-faced valves, use a Model 49 sandwich plate with a flange gasket.
- It must not be used as an anchor for tie-rods across non-restrained joints.
Why flange adapters are used in fire protection
Many modern fire networks in Saudi Arabia are built with grooved joints, while much of the equipment comes with flanged ends: fire pumps, flanged OS&Y gate valves, flanged check valves, some alarm valves and tank connections. The traditional answer is to weld a flange on site, which is hot work needing a permit, a qualified welder and painting afterwards.
A flange adapter avoids that. The pipe end is grooved as usual and the adapter clamps around it to create a flange face that bolts to the equipment. This is especially useful in pump rooms, where valves and spools are removed for maintenance. See our guide to fire pump suction and discharge accessories.
Where you need a flange adapter
The Shurjoint catalogue describes the flange adapter as the transition from a flanged system to a grooved one. On fire projects the typical points are:
- Fire pump suction and discharge flanges and the flanged valves and check valves after them.
- Flanged control valves such as OS&Y or NRS gate valves on the main.
- Extending an existing network built with flanges using new grooved pipe.
- Equipment removed for maintenance, such as strainers, flow meters and test spools in the pump room.
At each point, confirm the drilling standard of the mating flange before ordering: an ANSI 125/150 adapter will not fit a PN16 or Class 300 flange.
Shurjoint 7041 sizes and ratings
| Size | Pipe OD | Max working pressure | Flange bolts | Supplied as |
|---|---|---|---|---|
| 2 in (50 mm) | 60.3 mm | 300 psi (20 bar) | 4 x ⅝ in | Hinged |
| 4 in (100 mm) | 114.3 mm | 300 psi (20 bar) | 8 x ⅝ in | Hinged |
| 6 in (150 mm) | 168.3 mm | 300 psi (20 bar) | 8 x ¾ in | Hinged |
| 8 in (200 mm) | 219.1 mm | 300 psi (20 bar) | 8 x ¾ in | Hinged |
| 12 in (300 mm) | 323.9 mm | 300 psi (20 bar) | 12 x ⅞ in | Hinged |
| 14 to 24 in (7041N) | 355.6 to 609.6 mm | 300 psi (20 bar) | Per size | Two segments with draw kit |
Figures from the Model 7041 ANSI Class 125/150 table in the Shurjoint full line catalogue (AZEIDK brand page), which notes that working pressure is based on roll grooved standard wall carbon steel pipe. For PN10/16, BS 10 Table E or Class 300, use the dedicated tables in the same catalogue.
Sealing surface and the sandwich plate
A flange adapter does not behave like a welded flange with an ordinary gasket. It seals with its own gasket against the mating flange face, so the catalogue requires a hard, flat face. The table gives two sealing dimensions: D, the maximum inside face, and E, the minimum outside face of the mating flange.
If the mating face falls outside these dimensions, is serrated as on some valves, or belongs to a wafer valve with a rubber face or lining, the catalogue requires a regular flange gasket plus a Model 49 sandwich plate. The plate is electro-zinc plated mild steel, with stainless 304 or 316 available on request. The Model 49 sandwich plate and the 7043 are catalogue items, so confirm their availability with AZEIDK before specifying them.
This matters most with wafer butterfly valves. If your project uses them, see AFC grooved and wafer butterfly valves.
Installation and tightening per the catalogue
- Bolts: always use factory-supplied bolts and nuts to assemble the segments. The catalogue warns that other bolts may cause joint failure.
- Internal teeth: the 7041 has small triangular teeth inside the key shoulder to stop the pipe rotating. Remove them when connecting to schedule 5 pipe, plastic pipe or any surface the teeth could damage.
- Actuated valves: with butterfly or ball valves, check that the adapter OD does not clash with the actuator or its mounting pad.
- Tightening: as with any flange, tighten in diagonally opposite pairs until the faces meet metal to metal, keeping them parallel.
- Two adapters together: when two adapters mate a pipe or a wafer or lug valve between them, stagger the hinge points 90° to each other, use a sandwich plate where appropriate, and keep the segment housings parallel while tightening.
One firm limit: a flange adapter must not be used as an anchor point for tie-rods across non-restrained joints. Thrust restraint is solved another way, as the designer specifies.
Mistakes that show up at the hydrostatic test
- Bolting the adapter to a serrated or rubber face without a sandwich plate, so leaks appear as pressure rises.
- Tightening bolts in a circle instead of opposite pairs, tilting the face and damaging the gasket.
- Grooves outside catalogue dimensions, or pipe thinner than the wall the rating is based on.
- Leaving the internal teeth in place on thin-wall pipe.
These checks are part of AZEIDK’s shop drawings and coordination review and the pre-test inspection in testing and commissioning.
Listings and binding references
In Saudi Arabia the binding requirements are the Saudi Fire Code SBC 801 and Civil Defense rules; specifications usually adopt NFPA 13 and NFPA 20 as technical references for networks and pump rooms. The submittal should show the model and size as listed or approved for fire service at the working pressure. Verify this in the official UL and FM directories, not from the catalogue alone.
FAQ
What is a grooved flange adapter?
A fitting that turns a grooved pipe end into a flange so it can bolt to flanged valves or pumps without welding.
What is the pressure rating of the Shurjoint 7041?
300 psi (20 bar) for all sizes from 2 to 24 inch in the ANSI 125/150 table, on standard wall carbon steel pipe.
When do I need a sandwich plate?
When the mating face is outside the sealing dimensions, is serrated, or belongs to a wafer valve with a rubber face or lining.
What is the difference between 7041 and 7041N?
7041 covers 2 to 12 inch as one hinged piece; 7041N covers 14 to 24 inch as two segments with a draw kit.
Is there a flange adapter for PN16 flanges?
Yes, the Shurjoint catalogue lists PN10/16 and BS 10 Table E drillings, and Model 7043 for Class 300.
Can a flange adapter anchor tie-rods?
No. The catalogue prohibits using it as an anchor point for tie-rods across non-restrained joints.
Summary
A flange adapter saves site welding and simplifies maintenance, as long as its rules are respected: a suitable mating face or a sandwich plate, factory bolts, opposite-pair tightening and no use as an anchor. For other Shurjoint grooved products see our Shurjoint grooved piping guide, and for the full scope AZEIDK fire fighting systems.
Need flange adapters for your project? Send the sizes, the flange drilling standard and the equipment they connect to, and we will send the matching Shurjoint models with catalogue pages. Contact the AZEIDK team
Related guides
- Context Plus Reflective Beam Detectors: Installation, Alignment and Testing
- Low Current Systems for Hospitals: Network, CCTV, Access Control, PA and Fire Alarm as One Package
- Fire Protection Systems in Saudi Hospitals: Risks and Technical Solutions
- NAQUA Saudi Arabia: Seafood Plant and Warehouse Fire Safety