UL 864 11th Edition Effective 9 October 2026 per Intertek: What It Means for Fire Alarm Panel Approvals on Saudi Projects

  • News
  • 5 min read
UL 864 11th Edition Effective 9 October 2026 per Intertek: What It Means for Fire Alarm Panel Approvals on Saudi Projects
AZEIDK IntelligenceWe track the change before it reaches your site
Certifications & ApprovalsUL / Intertek

The 11th edition of UL 864, the standard for control units and accessories for fire alarm systems, reached its effective date on 9 October 2026. That date was set by Intertek, the certification body behind the ETL mark, in a Standards Update Notice dated 4 June 2025. The new edition (UL 864:2023 Ed.11) replaces the 10th edition (UL 864:2014 Ed.10, revised 7 May 2020), and Intertek requires manufacturers to recertify their fire alarm control panels to it.

The change matters to anyone who prepares or reviews a material approval for a UL-listed panel as part of fire alarm systems on Saudi projects: the edition cited in the listing is now a line item worth checking in every submittal.

Key Points

  • UL 864 is the standard used to test fire alarm control units (FACPs), their accessories, amplifiers and commercial power supplies for these systems.
  • Per Intertek’s notice, the 11th edition took effect on 9 October 2026.
  • Products certified to the 10th edition need a full evaluation and recertification to the 11th edition, because the changes are significant.
  • The 11th edition adds Functional Safety requirements and is harmonized with the 5th edition of the Canadian standard ULC-S527.
  • Intertek stated that reports not updated by the effective date will be withdrawn.

What Changed in UL 864 11th Edition?

According to its description on the ANSI Webstore, the standard covers discrete control units and accessories for fire alarm systems, electronic amplifiers for speech and distinctive sounds, and commercial fixed power supplies up to 600 V. UL Standards & Engagement published Edition 11 on 9 October 2023, and its latest revision is dated 25 October 2024, the same date it received ANSI approval.

Intertek’s notice gives manufacturers three practical points:

  • Full evaluation: updating paperwork is not enough. The product is re-evaluated to the 11th edition before the effective date.
  • Functional safety: the 11th edition brings Functional Safety requirements into the panel evaluation.
  • Canadian harmonization: UL 864 Ed.11 is harmonized with ULC-S527 5th edition, and a listing that references the Canadian standard needs caution and warning markings in English and French.

After the effective date, Intertek said, certification reports not updated to the new edition are withdrawn. This is Intertek’s policy for ETL listings; other certification bodies apply their own procedures.

Where Do NFPA 72 and Proposed TIA 1898 Fit In?

NFPA 72, 2025 edition, references the 11th edition of UL 864 in its list of referenced publications (section 2.3.11). NFPA published a Proposed Tentative Interim Amendment, Log No. 1898, submitted by the National Electrical Manufacturers Association (NEMA), asking to revert that reference to the 10th edition (2014, revised 2020). The submitter cited errors in the 11th edition that inhibit testing and certification, conflicts between US and Canadian requirements, and stated that UL had paused testing to the 11th edition until corrections are published. The comment closing date was 2 June 2026.

As of this report we have not verified a final decision on TIA 1898, so we treat it as a proposal only. For the edition itself, see our report on NFPA 72 2025 edition cybersecurity requirements.

What Does This Mean for the Saudi Market?

On Saudi projects whose specifications call for UL-listed fire alarm panels, the consultant reviews the listing as part of the material approval. Three situations come up:

  • Specification says “UL 864” with no edition: the contractor should ask the consultant which edition is acceptable before submitting, rather than face a rejection afterwards.
  • Specification requires the current edition: the supplier must show that the listing for that exact panel model cites the 11th edition.
  • Existing systems and extensions: adding cards or accessories to an installed panel requires confirming that the accessory is listed for use with that panel and that its directory status is still active.

The deciding record is the listing in the certification body’s official directory, such as UL Product iQ for UL listings, not a line in a catalog or datasheet. The difference between UL marks is covered in UL Listed vs UL Recognized vs UL Classified, and UL versus EN 54 approvals in UL or EN 54 for fire alarm devices.

AZEIDK Expert Take

Before submitting any fire alarm panel for material approval, ask the supplier for the listing file number and the model name exactly as shown in the certifier’s directory, then check the UL 864 edition cited and the listing status on the submission date. If the specification does not name an edition, get the accepted edition from the consultant in writing. Do not assume any panel, including those covered in our articles such as the Context Plus FirePlus addressable panel, has been updated to the 11th edition until its official record confirms it. The AZEIDK GROUP team can support technical selection of systems and equipment and review panel documents before submission. Contact AZEIDK GROUP with your project specification.

Sources

  1. Standards Update Notice: UL 864 Control Units and Accessories for Fire Alarm Systems, Intertek, 4 June 2025
  2. UL 864 Edition 11, UL Standards & Engagement (ShopUL Standards), published 9 October 2023, last revised 25 October 2024
  3. UL 864 Ed. 11-2023 Control Units and Accessories for Fire Alarm Systems, ANSI Webstore
  4. NFPA 72-2025 Proposed TIA Log No. 1898, NFPA, comment closing date 2 June 2026
  5. UL Product iQ, UL Solutions
Share this article

Back to Media Center

This site is registered on wpml.org as a development site. Switch to a production site key to remove this banner.