A stainless steel grooved coupling joins grooved stainless pipe without welding, where the water or the environment needs more corrosion resistance than carbon steel offers. In Saudi Arabia AZEIDK supplies the Shurjoint stainless steel grooved series, including the SS-5 angle-pad rigid coupling for Sch. 5S, 10S and 40S pipe, plus the rest of the series’ couplings and fittings.
This guide explains how the SS-5 works, its pressure ratings by pipe schedule, what the Shurjoint catalogue says about grooving stainless pipe, and the key point for fire systems: which models in the series appear in the UL and FM approval table and which do not.
Key points
- SS-5: angle-pad rigid coupling with two identical CF8 (304) or CF8M (316) housings, EPDM gasket and stainless bolts.
- Sizes 1¼ to 8 in, 600 psi on roll grooved Sch. 40S pipe.
- On Sch. 10S the rating drops to 300 psi and on Sch. 5S to 200 psi per the performance table.
- The catalogue’s UL and FM table includes SS-7, SS-8, SS-41, SS-723 and the series fittings, but not SS-5.
- SS-5 is listed by IAPMO to CSA B242 at 300 psi.
In this article
- What is the SS-5 stainless steel grooved coupling?
- Stainless steel grooved coupling SS-5 pressure ratings
- Grooving stainless pipe: catalogue cautions
- What the Shurjoint stainless series includes
- Stainless grooved couplings in fire systems: check the listing
- When to choose stainless pipe and couplings
- How AZEIDK helps
- FAQ
- Summary
What is the SS-5 stainless steel grooved coupling?
Shurjoint describes the SS-5 as an angle-pad stainless coupling for Sch. 5S, 10S or 40S pipe where a rigid joint is needed. The housings slide along the bolt pads as they are tightened, giving an offset clamping action that makes the joint rigid and resists snaking of long straight runs.
The SS-5 can be fitted by removing only one bolt and swinging the coupling over the pipe, which saves time. It consists of two identical CF8 (304) or CF8M (316) housings, an EPDM gasket, and stainless track bolts with heavy duty nuts, with a standard C-shaped gasket or a GapSeal gasket in several grades.
Stainless steel grooved coupling SS-5 pressure ratings
A grooved joint’s rating depends on pipe wall and grooving method, because the groove takes part of the wall. The SS-5 performance table in the catalogue shows, for 1¼ to 8 in:
| Pipe and grooving | Max cold working pressure (CWP) |
|---|---|
| Sch. 40S cut grooved | 600 psi (42 bar) |
| Sch. 40S roll grooved | 600 psi (42 bar) |
| Sch. 10S roll grooved | 300 psi (20 bar) |
| Sch. 5S roll grooved | 200 psi (14 bar) |
The SS-5 dimension table gives 600 psi for all sizes from 1¼ to 8 in on Sch. 40S, with two bolts per coupling: 3/8 x 2⅛ in for 1¼ and 1½ in, 3/8 x 2¾ for 2 to 4 in, 1/2 x 3 for 5 and 6 in, and 5/8 x 4¾ for 8 in. When ordering, state the actual pipe schedule, because “4 in stainless coupling” alone does not define the allowable pressure.
Grooving stainless pipe: catalogue cautions
- Separate roll set: using the roll set used on carbon steel can transfer rust and scale to stainless pipe, so Shurjoint recommends a dedicated stainless roll set.
- Groove corners: stainless is harder to groove; grooves without defined corners and with too much radius can cause joint failure.
- Correct roll set: matched to the pipe material and wall thickness.
- Keep dry: keep roll grooved stainless pipe dry before installation.
The catalogue also notes that ductile iron couplings can be used on stainless pipe depending on the application, since the medium contacts only the gasket, not the housing. That is a design decision based on the external environment and the water. For grooved basics see Shurjoint grooved couplings for fire systems.
What the Shurjoint stainless series includes
- Rigid couplings: SS-5, SS-7, SS-7X.
- Flexible couplings: SS-8, SS-8X, the SS-1200 high pressure coupling and the SS-28 hinged lever coupling.
- Fittings: SS-10, SS-11, SS-20 and SS-60 elbows, tee and cap; SS-21 and SS-50 reducing tee and concentric reducer.
- Others: SS-41 and SS-80 flange adapters, SS-723 mechanical tee, SS-726 Y-strainer.
The series is made in CF8 (304) and CF8M (316) for general service and in specialty alloys for uses such as reverse osmosis and desalination, with fittings from 1 to 24 in per the catalogue.
Stainless grooved couplings in fire systems: check the listing
In its fire protection section the Shurjoint catalogue gives a table of UL and FM approved pressure ratings for the stainless series on Sch. 40S and 10S pipe. It lists the SS-7 and SS-8 couplings, SS-41 flange adapter, SS-723 mechanical tee, and fittings SS-10, SS-11, SS-20, SS-21, SS-21F, SS-50, SS-50F, SS-60 and the SS-80 flange adapter, mostly at 300 psi. The SS-5 is not in that table; it appears in a separate IAPMO listing table to CSA B242 at 300 psi for 1¼ to 8 in.
In practice: where stainless pipe forms part of a sprinkler or standpipe system that requires UL listed or FM approved components, choose models from the UL and FM table such as SS-7 or SS-8 and include that page in the submittal. The SS-5 remains suitable for general water, HVAC and other services that do not require that listing. The project specification, SBC 801 and Civil Defense requirements are the final reference.
The AZEIDK product page covers the whole stainless series, so the sprinkler and standpipe uses it lists apply to the UL and FM listed models in the series, not to the SS-5 itself.
When to choose stainless pipe and couplings
Stainless costs more than carbon steel, so it is usually chosen where water or the environment is corrosive, or where the specification requires water cleanliness or chemical resistance. These cases are more common in industrial plants, water facilities and coastal sites. The choice between 304, 316 and higher alloys depends on chloride level, temperature and medium, as Shurjoint notes in its materials data, and the designer decides. For carbon steel pipe types and schedules see fire pipes: types and schedules. See our industrial facilities page.
How AZEIDK helps
AZEIDK supplies the Shurjoint stainless series with catalogue pages, pressure tables and listing data for the submittal, checks pipe schedules and the right model for each service, separates the models needed for fire systems from general service lines, and can extend the work to installation and testing. The full network is under fire fighting systems.
FAQ
What is a stainless steel grooved coupling?
A grooved coupling with a stainless housing that joins grooved stainless pipe without welding, such as the Shurjoint SS-5 angle-pad rigid coupling.
What is the pressure rating of the Shurjoint SS-5?
600 psi on Sch. 40S, 300 psi on Sch. 10S and 200 psi on Sch. 5S roll grooved pipe, per the catalogue performance table.
Is the SS-5 UL listed and FM approved for fire systems?
The SS-5 does not appear in the UL and FM table of the Shurjoint catalogue; it appears in the IAPMO listing. For listed fire systems choose table models such as SS-7 or SS-8.
What is the SS-5 housing made of?
CF8 (304 equivalent) or CF8M (316 equivalent), with an EPDM gasket and stainless bolts and nuts.
Can the same grooving machine be used for carbon and stainless pipe?
The machine yes, but Shurjoint recommends a separate roll set for stainless so rust is not transferred to the pipe.
What sizes does the SS-5 come in?
1¼ to 8 in per the catalogue dimension table.
Summary
A stainless steel grooved coupling such as the Shurjoint SS-5 gives a rigid, quick to install joint on stainless pipe, with a rating set by pipe schedule. For fire systems check the UL and FM table before writing the specification, since the model listed there (SS-7 or SS-8, for example) is what the consultant will expect in the submittal.
Working with stainless pipe on your project? Send sizes, schedules and service type, and we will send suitable Shurjoint models with catalogue and listing pages. Contact the AZEIDK team
Related guides
- Car Park Carbon Monoxide Detection and Extraction Fan Control: Komttech VCO800 and VSO-800
- Sidewall Sprinklers: When to Use Them in Hotel Rooms and Corridors, K-Factor and Coverage with Victaulic FireLock FL-QR/SW
- Fire Pump Parts: Mechanical Seals, Bearings, Diesel Batteries and Filters, and Why Genuine Parts Matter
- Fitting Out a New Fuel Station with Safety Systems: From Drawing Review to Installation, Handover and Salamah