Proposed NFPA 25 Amendment TIA 1944: Annual Check of the Sprinkler List for Recalled Models, Impairment Until Replaced
- News
- 5 min read

NFPA has published proposed Tentative Interim Amendment TIA 1944 to NFPA 25, 2026 edition, and the public comment period closed on 20 November 2026. The proposal covers recalled sprinkler inspection: an annual check of the installed sprinkler list for recalled models, replacement of any recalled sprinkler, and treating the system or portion that contains them as impaired. It is still a proposal, not an issued amendment, so it is not yet part of the standard. AZEIDK GROUP’s annual and preventive maintenance contracts cover sprinkler inspection to NFPA 25 for fire systems.
Key points
- TIA 1944 is a proposed amendment to NFPA 25-2026, submitted by Joshua Hetzler of the Fall River Fire Department, Massachusetts.
- New section 5.2.1.6: the sprinkler list required by 5.4.1.6.6 is inspected annually for sprinklers under a CPSC or manufacturer recall.
- Recalled sprinklers shall be replaced, and the systems or portions containing them are considered impaired.
- A new Annex J lists recalled sprinklers, mostly dynamic O-ring seal designs.
- Comments closed on 20 November 2026; no final decision had been published at the time of this report.
Recalled sprinkler inspection: what TIA 1944 would change in NFPA 25
The proposal adds no new testing and no blanket replacement. It uses a record that already exists, the list of installed sprinklers required by 5.4.1.6.6, and has it compared with recall lists once a year. Proposed section 5.2.1.6 says:
- The sprinkler list is inspected annually for sprinklers subject to a recall by the US Consumer Product Safety Commission (CPSC) or the manufacturer.
- Sprinklers identified as recalled shall be replaced.
- Systems or portions of systems containing them are considered impaired, so the standard’s impairment procedures apply until they are corrected.
A new item (5) in 5.4.1.1 adds recalled sprinklers found in this inspection to the replacement criteria. For current replacement rules, service life and sample testing, see When to Replace Fire Sprinklers.
Recalled fire sprinklers listed in proposed Annex J
Proposed Annex J, “Recalled Fire Sprinklers”, includes Table J.1.1:
| Manufacturer and type | Example models | Years | Reason |
|---|---|---|---|
| Central (dry) | A-1, GB, GB4-EC, H-1, K | 1970s to 2001 | O-ring seal degradation |
| Central (Omega series) | C1, C1A, R-1, EC-12 RES, EC-20, AC | All | Defective sealing design |
| Central (wet) | GB, BB2, ELOC, SD1 and others | 1989 to 2000 | O-ring seal degradation |
| Gem (wet) | F927 | 1995 to 2001 | O-ring seal degradation |
| Globe (dry) | Model J | All | O-ring deterioration may stop discharge |
| Star (dry) | ME-1, SG, SG-QR, Q, QQR | 1996 to 1998 | O-ring seal degradation |
The Central Sprinkler recall itself and the September 2026 CPSC release are covered in our earlier report, Recalled Central Sprinkler Heads.
Why it was submitted
The substantiation states that recalled O-ring sprinklers remain installed in many existing buildings and that UL field data show lower normal operation rates for O-ring designs than for non-O-ring designs. It cites the July 2025 Gabriel House fire in Fall River, where recalled Central GB-series sprinklers were found, as evidence that current NFPA 25 text does not reliably identify them. On 23 July 2026 NFSA reported that it and the Fall River Fire Department had submitted TIAs and Public Inputs to NFPA 25 that build on the 5.4.1.6.6 sprinkler inventory.
What it means for Saudi Arabia
NFPA 25 is a technical reference for inspecting and maintaining water-based systems; the edition applied to a Saudi building depends on SBC 801, Civil Defense requirements and the authority having jurisdiction. As the TIA has not been issued, it should not be presented to owners as a requirement. The idea is still practical: older buildings, and those with imported sprinklers and weak records, benefit from checking the sprinkler list against recall data. For the current edition, see NFPA 25 2026 Edition: What Changes for Building Owners.
AZEIDK Expert Take
There is no need to wait for the amendment. Ask your maintenance contractor for an up-to-date list of installed sprinklers: manufacturer, model, sprinkler identification number (SIN) and year where marked. Compare it with Annex J and manufacturer notices. If a recalled sprinkler is found, treat that portion as impaired, notify the authority having jurisdiction and replace it with a listed sprinkler matching the original K-factor, temperature rating and response type. This check can be built into the annual inspection under an AZEIDK GROUP maintenance contract.
What your facility should do now
- Keep a record of the sprinklers installed in the building (manufacturer, model, K-factor, year of manufacture) in the documentation and handover file; that is what would be checked against the recall table every year if the amendment is adopted.
- If the facility has no such record, start with an assessment of existing systems, then replace any recalled head with a listed sprinkler that matches the design, such as Tyco Series TY-B sprinklers where they match.
No record of the sprinklers in your building? We survey and document the sprinklers and check them against recall lists as part of routine maintenance. Contact AZEIDK
Sources
- NFPA 25 Proposed TIA 1944, NFPA, comment closing date 20 November 2026
- From Recall to Resolution: Proposed Changes to Improve Fire Sprinkler Safety, NFSA, 23 July 2026
Related guides
- Intersec Europe 2027: New Security and Fire Safety Fair in Frankfurt, 14 to 16 September
- EU PFAS Foam Restrictions: The 23 October 2026 Stage and What It Means for Saudi Facilities
- Dahua Vulnerabilities June 2026 (DHCC-SA-202606-001): CVE-2026-29116 Reaches Cameras, Recorders and Intercoms
- AZEIDK General Contracting Registered as a Service Provider in the Saudi Aramco Supplier Management System