In a water-based fire fighting network, water travels from the tank to the fire pumps, then through control valves, check valves and the alarm check valve, before it reaches the sprinklers, hose reel cabinets and outdoor hydrants. Each fire valve on that path affects how easy the system is to operate and maintain, and whether the submittal is accepted by the consultant and Civil Protection.
This guide puts the American Fire Control (AFC) products offered by AZEIDK Egypt in one place: what each product is, where it sits in the network, the key figures in its datasheet, and which detailed article covers it. All of them are part of the fire fighting systems AZEIDK Egypt supplies.
Key takeaways
- American Fire Control is a US brand based in Orlando. AZEIDK Egypt offers its network valves, fire hydrants and the AFC-227 / P227 clean agent system.
- Control valves: OS&Y gate valves A-3000 (flanged) and AG-3000 (grooved), and butterfly valves BFW-300 and BFG-300/301.
- Check valves A-3150 (flanged) and A-3500 (grooved), and the ACV-300 wet alarm check valve at the base of the sprinkler riser.
- The FW-9000 wet barrel hydrant has one 4.5 in pumper outlet, two 2.5 in hose outlets and a 250 psi working pressure per its datasheet.
- UL or FM approval applies to each model as its datasheet states. It is not a blanket approval for the whole brand.
An AFC fire valve for every point in the network
The easiest way to understand the AFC range is to follow the water. The table places each product at its usual location and links to the article that covers the model in detail. The locations are common design examples; the actual positions come from the approved project drawings.
| Product | Model | Usual location | Key datasheet figure | Detailed article |
|---|---|---|---|---|
| OS&Y gate valve | A-3000 (flanged), AG-3000 (grooved) | Pump suction and discharge, main lines, riser inlets | 300 psi working pressure, 2.5 to 12 in | AFC OS&Y gate valves |
| Butterfly valve | BFW-300 (wafer), BFG-300/301 (grooved) | Risers, floor branches, pump rooms | 300 psi working pressure, 2 to 12 in | AFC butterfly valves |
| Check valve | A-3150 (flanged), A-3500 (grooved) | Pump discharge, fire department (Siamese) connection, supply points | 300 psi for A-3150, 350 psi for A-3500 | AFC check valves |
| Wet alarm check valve | ACV-300 | Base of the wet sprinkler riser | 300 psi, vertical installation only | ACV-300 alarm check valves |
| Wet barrel hydrant | FW-9000 | Outdoor underground network around the building | 250 psi, one 4.5 in pumper and two 2.5 in outlets | FW-9000 hydrants |
| Clean agent suppression | AFC-227 / P227 | Enclosed electrical and control rooms | HFC-227ea pressurised to 24.8 bar at 21 °C | AFC-227 / P227 system |
The AFC brand page on the AZEIDK Egypt site also lists dry barrel hydrants. We have not yet published a detailed article on them, so ask for the datasheet of the exact model before you put it in the BOQ.
Control valves: OS&Y or butterfly
Control valves isolate part of the network for maintenance or repair. AFC offers two types, and each has its place.
A-3000 and AG-3000 OS&Y gate valves
On an OS&Y (outside screw and yoke) valve the stem rises out of the bonnet when the valve is open, so anyone can see its position. The datasheet gives sizes from 2.5 to 12 in, a maximum working pressure of 300 psi (21 bar), a test pressure of 600 psi and compliance with AWWA C515. The difference is the end connection: the flanged A-3000 suits pump rooms and flanged mains, while the grooved AG-3000 is lighter. At 6 in the datasheet gives 62 kg for the A-3000 and 48 kg for the AG-3000.
BFW-300 and BFG-300/301 butterfly valves
A butterfly valve opens and closes with a quarter turn through a gearbox. It is shorter than a gate valve, so it fits risers and tight spaces. The BFW-300 is a wafer valve clamped between two flanges; the BFG-300/301 has grooved ends to AWWA C606. The datasheet gives 300 psi working pressure and 0 to 80 °C. In the FM Approvals guide the model number changes with size: 300 covers 2.5 to 8 in, and 301 covers 2, 10 and 12 in. Check this when you write the BOQ item.
Both types are normally supervised with a tamper switch that signals the fire alarm panel when someone starts to close the valve. The connection to the alarm system is covered in connecting sprinklers to the fire alarm.
Check valves and the alarm check valve
A-3150 and A-3500: stopping backflow
A check valve lets water flow one way only. Its most common positions are after the pump discharge and on the fire department (Siamese) connection line, so network water cannot flow out through it. The A-3150 is a flanged swing check valve rated 300 psi. The A-3500 is a grooved swing check valve with a stainless steel disc that returns to the seat with spring assistance, rated 350 psi. Both come in 2 to 12 in according to the submittal. Remember that the weakest component sets the rating of a line: a 350 psi check valve does not upgrade a line that has 300 psi valves on it.
ACV-300 wet alarm check valve
The ACV-300 sits at the base of a wet sprinkler riser. It prevents water from flowing back to the supply and triggers the water motor gong and pressure switch when a sprinkler starts to discharge. The datasheet gives a 300 psi working pressure and 4 to 70 °C, and states that the valve is installed vertically only, with a retard chamber. The retard chamber prevents false alarms from pressure surges, with a delay of 5 to 60 seconds according to the manufacturer’s manual.
FW-9000 outdoor fire hydrants
The outdoor hydrant is where the fire engine connects to the underground network. The FW-9000 is a wet barrel hydrant: its body stays full of water, and each outlet has its own valve, as AWWA C503 requires. The datasheet lists one 4.5 in pumper outlet, two 2.5 in hose outlets, a 6 in Class 150 flanged inlet, 250 psi working pressure, a 500 psi factory test on every unit, and UL listing and FM approval.
That factory test applies to the hydrant itself. The hydrostatic test of the underground network on site follows the project documents and the design standard, such as NFPA 24. Make sure the chosen test pressure does not exceed what every component on the line can take.
AFC-227 / P227 clean agent system
Water is not suitable everywhere. Electrical switchgear and control rooms are usually protected by total flooding with a clean agent, which is where the AFC-227 / P227 system comes in, as part of our special fire suppression solutions. The system uses HFC-227ea, widely known by the trade name FM-200, stored as a liquid and pressurised with nitrogen to 24.8 bar at 21 °C, in cylinders from 26.8 to 175 L water capacity. The P227 version adds a separate nitrogen cylinder to push the agent through long or complex pipe networks. The datasheet limits the protected height to 0.3 to 4.5 m per nozzle limits, and the room must be tight.
How to read an AFC submittal
The American Fire Control page on the AZEIDK Egypt site carries separate submittals for fire valves, alarm check valves and fire hydrants, plus the AFC-227 / P227 datasheet. When you review any of them, check four points:
- The full model number: one letter or digit can mean a different end connection or size range, as with A-3000 and AG-3000 or BFG-300 and BFG-301. Match the BOQ text to the approval guide page.
- Approval per model: the brand page itself says UL and FM approvals apply to specific models as stated in each datasheet. Do not write “UL/FM approved” for the whole brand without checking.
- End type and flange class: match the flange class (Class 125, Class 150 or PN16) to the pipes and pumps on both sides.
- Rated pressure against the highest actual pressure: compare the valve rating with the highest pressure at its location, including fire pump churn pressure plus suction pressure.
The legally binding reference in Egypt is the Egyptian Code for the Design and Implementation of Fire Protection for Buildings, 2026 edition (Ministerial Decree No. 355 of 2026), together with approval of drawings and systems by the General Directorate of Civil Protection (Ministry of Interior). The NFPA and AWWA standards mentioned here are technical design and manufacturing references, not a substitute for the Egyptian code.
Common mistakes when ordering AFC products
- Writing a generic item such as “UL/FM butterfly valve 4 in” without the model number and end type, then receiving a valve that does not fit the line.
- Mixing flanged and grooved ends in the pump room without allowing for adaptors and supports, although the weight difference is large in big sizes.
- Installing the ACV-300 horizontally, or without the retard chamber approved with it.
- Fitting a check valve the wrong way round, or leaving it off the fire department (Siamese) connection line.
- Choosing a network test pressure above what the weakest hydrant or valve on the line can take.
- Proposing AFC-227 for a room that is not tight, or one taller than the datasheet height limit.
Frequently asked questions
Which American Fire Control products does AZEIDK Egypt offer?
OS&Y gate valves A-3000 and AG-3000, butterfly valves BFW-300 and BFG-300/301, check valves A-3150 and A-3500, the ACV-300 wet alarm check valve, FW-9000 wet barrel hydrants and the AFC-227 / P227 clean agent system. The brand page also lists dry barrel hydrants.
What is the difference between an OS&Y fire valve and a butterfly valve?
An OS&Y valve shows its position by the rising stem and has lower friction loss when open. A butterfly valve is shorter and operates with a quarter turn, so it suits risers and tight spaces. Both are supervised with a tamper switch.
Are all AFC products UL and FM approved?
Approval applies per model, as stated in the datasheet and the approval guide pages in the submittal. Check the approval for the exact model and size before you write it into the specification.
Where is a check valve installed in a fire network?
Most often after the fire pump discharge, on the fire department (Siamese) connection line, and at supply points where water must not flow back. The actual positions come from the project drawings.
Is the FW-9000 a wet or dry barrel hydrant?
The FW-9000 is a wet barrel hydrant whose body stays full of water, with a separate valve for each outlet to AWWA C503. Dry barrel hydrants are listed on the brand page; ask for the datasheet of the model you need.
How do I get AFC submittals?
The valve, alarm check valve and hydrant submittals and the AFC-227 datasheet are published on the brand page on the AZEIDK Egypt site, and our team can prepare a project-specific submittal.
Summary
The American Fire Control range at AZEIDK Egypt covers most points of a water network: control and check valves, the alarm check valve at the riser base and outdoor hydrants, plus the AFC-227 / P227 system for rooms where water is not suitable. A good selection starts with the component’s position in the network, then the model number, end type and pressure, and then the approval of that exact model in its datasheet.
Do you have a BOQ with fire valves and hydrants? Send us the items, sizes and network pressure, and we will match them to AFC models and send the submittals. Talk to the AZEIDK Egypt team
Related guides
- Fire Safety in Nurseries and Kindergartens in Egypt: Detectors, Extinguishers, Evacuation
- Context Plus Fire Alarm Panels in Egypt: Choosing ZFP, CFP or FP
- Fire Safety in Wedding Halls in Egypt: Alarms, Extinguishers, Exits and Decor
- Fire Alarm System Cost in Egypt: What Drives the Price and How to Get an Accurate Quote