UL 2196 Third Edition: Signal Integrity Now Required for Fire-Resistive Data Cables

  • News
  • 3 min read
UL 2196 Third Edition: Signal Integrity Now Required for Fire-Resistive Data Cables
AZEIDK RadarWe track the update before it reaches your site
CertificationsUL

UL Solutions used its 30 October 2026 issue of The Code Authority, its newsletter for code officials, to explain a significant change in the third edition of UL 2196, the fire test standard for circuit integrity of fire-resistive cables. Data and communication cables used to be tested for electrical continuity only. The third edition also requires them to maintain signal integrity through both the fire endurance test and the hose stream test that follows it.

Key points

  • A data or communication cable can stay electrically connected in a fire while its signal degrades past the point of usefulness. The third edition addresses that gap.
  • The signal must stay within the manufacturer’s stated performance specifications, which may be based on standards such as TIA or IEC.
  • Measurements are taken every five minutes during the fire test; after the hose stream they start within five minutes and continue at five-minute intervals for at least 30 minutes.
  • A fire-resistive cable system is certified as a complete assembly: cable, connectors, clamps, supports, raceway, pull boxes and splices. Any change after certification requires the whole assembly to be retested.

How to check a cable in UL listings

UL explains that Product iQ lists these products in separate categories: FHIT for complete systems, FHJR for fire-resistive cable and FHJW for fire-resistive data and communication cable. FHJW cables are marked for use in electrical circuit integrity systems and come with a manufacturer’s performance data sheet. The standard also adds an appendix for testing coaxial cable used in distributed antenna systems for emergency responder communication enhancement (ERCES), covering insertion loss, return loss and voltage standing wave ratio.

What it means for projects in Saudi Arabia

On projects in the Kingdom, fire-resistive cables show up in voice evacuation circuits, in links between networked fire alarm panels and in in-building communication systems in high-rise towers. When a specification calls for a cable certified to UL 2196, the question is no longer only “is it rated for two hours?”. It is also: is it a power cable or a data cable, does the certification cover signal integrity, and does the certified design number match how the cable is installed on site, supports and splices included?

Many projects follow the British and European route instead of the American one. The Belden Safe-T-Line 79001FS that AZEIDK supplies is LPCB certified and complies with BS 6387 CWZ, EN 50200 PH120 and IEC 60331-2. It suits specifications that call for those standards; it is not a UL 2196 certified product. Read the specification first to confirm which route applies before any cable is approved.

AZEIDK view

A common reason for a cable submittal to be rejected is a certificate to a different standard from the one the specification asks for, even when the cable itself is good. For the technical background, see our guide to fire alarm cables and circuit integrity and our earlier update on fire-resistant cable standards. AZEIDK supplies alarm cables as part of its fire alarm systems and reviews the specification with you to pick a compliant cable through our technical selection service. Send your project specification to the AZEIDK team.

Sources

  1. Fire-Resistive Cable Systems and UL 2196: Signal Integrity and Circuit Continuity, UL Solutions Knowledge Center
  2. UL Solutions, The Code Authority newsletter: Fire-Resistive Cables Just Got Smarter, 30 October 2026