Victaulic FireLock FL-QR/ST/ESFR K16.8 Pendent Storage Sprinkler – V4702

Victaulic FireLock FL-QR/ST/ESFR V4702 quick-response pendent storage sprinkler with a K16.8 discharge coefficient and a maximum working pressure of 175 PSI.
العلامة التجارية
ESFR Pendent Sprinklers V4702 - Victaulic

تفاصيل المنتج

نظرة عامة على المنتج

The Victaulic FireLock Series FL-QR/ST/ESFR V4702 is a quick-response ESFR pendent sprinkler designed for warehouse and storage fire-protection applications.

ESFR stands for Early Suppression Fast Response. This sprinkler type is intended to attack a developing storage fire at an early stage by delivering a high water flow with droplets capable of penetrating the fire plume and reaching the burning commodity.

Model V4702 has a nominal K16.8 discharge coefficient and is intended for storage sprinkler systems designed in accordance with NFPA, FM Data Sheets and applicable local requirements.

Key Features:

• ESFR storage fire sprinkler.
• Victaulic FireLock Series FL-QR/ST/ESFR.
• Model V4702.
• Pendent installation.
• Quick Response.
• Early Suppression Fast Response protection.
• Nominal K-factor of 16.8.
• Nominal metric K-factor of 24.25.
• 3/4-inch NPT connection.
• 20 mm BSPT connection.
• IGS grooved connection option.
• Maximum working pressure of 175 PSI.
• 100% factory hydrostatically tested at 500 PSI.
• Minimum UL/FM operating pressure of 7 PSI.
• Two available temperature ratings.
• cULus Listed.
• FM Approved.
• Intended for wet-pipe sprinkler systems under the listed criteria.
• Designed for storage applications according to NFPA 13 and FM Data Sheets.

Operation:

The sprinkler uses a 3 mm nominal-diameter heat-sensitive glass bulb.

When the ambient temperature reaches the rated operating temperature:

• Fluid inside the glass bulb expands.
• The bulb breaks.
• The sealing assembly releases.
• Water begins to discharge through the sprinkler.
• The pendent deflector directs water downward over the protected storage area.
• The high discharge coefficient provides the flow required for early suppression applications.
• The system operates according to the hydraulically designed pressure, flow and number of operating sprinklers.

Discharge Coefficient:

• K-factor: 16.8 GPM/psi½.
• Nominal metric K-factor: 24.25.

Maximum Working Pressure:

• 175 PSI.
• Approximately 1200 kPa.
• Approximately 12 bar.

Factory Hydrostatic Test:

• 100% factory tested.
• Test pressure: 500 PSI.
• 3447 kPa.
• 34 bar.

Minimum Operating Pressure Shown:

• 7 PSI.
• 48 kPa.
• Approximately 0.5 bar.

Available Connections:

• 3/4-inch NPT.
• 20 mm BSPT.
• IGS grooved connection.

Available Temperature Ratings:

• 155°F / 68°C.
• 200°F / 93°C.

Coverage Criteria:

• Maximum coverage area: 100 ft².
• Approximately 9.1 m².

• Minimum coverage area: 64 ft².
• Approximately 6 m².

Sprinkler Spacing:

• Maximum spacing: 12 ft for ceiling heights up to 30 ft.
• Approximately 3.6 m for ceilings up to 9.1 m.

• Maximum spacing: 10 ft for ceiling heights above 30 ft.
• Approximately 3.1 m.

• Minimum spacing: 8 ft.
• Approximately 2.4 m.

Maximum Ceiling Slope:

• 2 in 12.
• Approximately 10.5 degrees.

Deflector-to-Ceiling Distance:

Under NFPA/cULus:

• 6 to 14 inches.
• Approximately 150 to 355 mm.

Under FM:

• 4 to 13 inches.
• Approximately 100 to 330 mm.

Minimum Deflector Distance Above Storage:

• 3 ft.
• Approximately 0.9 m.

Minimum Distance from Walls:

• 4 inches.
• Approximately 100 mm.

System Design:

The catalogue shows:

• A design based on 12 operating sprinklers at the approved pressures.
• Wet-pipe system applications.
• Design according to NFPA 13 or the applicable FM Data Sheets.

Main Construction Materials:

• Deflector: Bronze.
• Bulb: 3 mm nominal glass.
• Load screw: Bronze.
• Pip cap: Bronze.
• Spring seal: PTFE-coated beryllium nickel alloy.
• Frame: Brass.
• Coupling: According to the applicable Victaulic publication.
• Installation wrench: Ductile iron.

Sprinkler Finish:

• Plain brass.

Installation Tools:

• V47 Open-End Wrench.
• 3/16-inch Hex-Bit V9 for the compatible connection arrangement.

Main Dimensions:

Threaded V4702:

• Overall height: approximately 3 inches.
• Metric height: 76 mm.
• Frame-to-deflector height: approximately 1.75 inches.
• Metric dimension: 45 mm.
• Nominal make-in: 1/2 inch.
• Metric make-in: 13 mm.

IGS Grooved V4702:

• Overall height with coupling: approximately 3 inches.
• Metric height: 76 mm.
• Frame-to-deflector dimension: approximately 1.75 inches.
• Metric dimension: 45 mm.

Storage Applications:

Subject to approved design criteria, the sprinkler may be used for:

• Open-frame rack storage.
• Single-row racks.
• Double-row racks.
• Multiple-row racks.
• Portable rack storage.
• Class I through Class IV commodities.
• Selected Group A and Group B plastics.
• Solid-pile storage.
• Palletized storage.
• Idle pallet storage.
• Rubber-tire storage.
• Rolled-paper storage.
• Flammable-liquid storage where permitted.
• Aerosol storage according to the applicable standard.

Referenced Design Standards:

• NFPA 13.
• NFPA 30.
• NFPA 30B.
• FM Data Sheet 8-9.
• FM Data Sheet 8-24.
• FM Data Sheet 8-3.
• FM Data Sheet 8-21.
• FM Data Sheet 7-29.
• FM Data Sheet 7-31.

Final selection depends on:

• Commodity type.
• Commodity classification.
• Storage arrangement.
• Storage height.
• Ceiling height.
• Rack arrangement.
• Clearance above storage.
• Available water pressure and flow.
• Required number of operating sprinklers.
• NFPA or FM criteria.
• Project, consultant and authority requirements.

Installation Notes:

• Install only in the pendent orientation.
• Maintain the approved deflector position and spacing.
• Use only the specified installation wrench.
• Do not apply installation force to the bulb or deflector.
• Fully depressurize and drain the system before installation or maintenance.
• Do not install a damaged sprinkler or one with a cracked bulb.
• Do not field paint or modify the sprinkler.
• Refer to the latest Victaulic documentation before final approval.
• The system must be hydraulically designed by a qualified fire-protection professional.

Important Note:

The V4702 ESFR sprinkler is not a direct replacement for another storage sprinkler without a complete design review.

Verify commodity type, storage and ceiling height, spacing, available flow and pressure, and NFPA or FM requirements before procurement and installation.