Checking for Recalled Sprinklers in Fire Network Maintenance in Egypt: What TIA 1944 Proposes for NFPA 25

Checking for Recalled Sprinklers in Fire Network Maintenance in Egypt: What TIA 1944 Proposes for NFPA 25

On 20 November 2026, the National Fire Protection Association (NFPA) closed comments on proposed Tentative Interim Amendment TIA 1944 to NFPA 25, 2026 edition, the standard for inspection, testing and maintenance of water-based fire protection systems. The proposal adds an annual check of the building’s sprinkler list for recalled fire sprinklers, requires any recalled sprinkler to be replaced, and treats the system or portion containing it as impaired until replacement.

The proposal is American, but NFPA 25 is a common reference for sprinkler maintenance in projects that follow NFPA standards, including projects in Egypt. Below we explain what the amendment proposes and how a facility owner in Egypt can apply the same idea in routine maintenance now.

Key takeaways

  • TIA 1944 is a proposed tentative interim amendment to NFPA 25-2026, submitted by Joshua Hetzler of the Fall River Fire Department, Massachusetts; comments closed on 20 November 2026.
  • Proposed section 5.2.1.6: an annual inspection of the sprinkler list required by 5.4.1.6.6 for sprinklers under recall by the manufacturer or the US Consumer Product Safety Commission (CPSC).
  • Recalled sprinklers are replaced, and the system or portion containing them is treated as impaired until then.
  • A new Annex J gives examples of recalled sprinklers, most of them O-ring seal designs.
  • Maintenance contracts in Egypt can include this review without waiting for a final decision.
In this article
  1. What does TIA 1944 propose?
  2. Why was it proposed?
  3. What does this mean for sprinkler maintenance in Egypt?
  4. What this means for your facility

What does TIA 1944 propose?

  • 5.2.1.6.1: the sprinkler list required by 5.4.1.6.6 is inspected annually for sprinklers under a CPSC or manufacturer recall.
  • 5.2.1.6.2: recalled sprinklers shall be replaced.
  • 5.2.1.6.3: systems or portions of systems containing recalled sprinklers shall be considered impaired.
  • 5.4.1.1: sprinklers identified by this inspection are added to the mandatory replacement cases.
  • Annex J: a table of mandatory and voluntary recall examples, including Central (dry, wet and Omega series), Gem, Globe (Model J) and Star, with models, years and reasons.

Why was it proposed?

According to the proposal, O-ring sealed sprinklers can fail to operate because of seal degradation, sticking and material transfer; UL identified these defects and the designs were barred from new manufacture after 9 January 2003. The submitter cites a July 2025 fire at an assisted living facility in Fall River where recalled Central sprinklers were found afterwards, noting that the proposal does not assign causation. The proposal states that NFPA 25 has no explicit recall verification requirement today, and that it relies on existing recall records without mandating new testing or blanket replacement.

What does this mean for sprinkler maintenance in Egypt?

Older buildings in Egypt, such as hotels and factories whose networks were installed many years ago, may contain sprinklers from different sources and generations, and owners often do not know the models. Looking at a sprinkler from floor level is not enough to read its model, so the review starts with a written list:

  1. Sprinkler record: manufacturer, model, identification number (SIN), K-factor, temperature rating and year of manufacture where marked, for each type installed and its location.
  2. Comparison: check the record against manufacturer notices, the CPSC recall list and the Annex J examples.
  3. If a recalled sprinkler is found: treat the affected portion as impaired and replace the sprinkler with a listed one matching the original design in K-factor, temperature rating and response type.
  4. Contract: write this review into the maintenance contract as an annual item, and update the record after every replacement.

For background on NFPA references in fire projects, see NFPA standards in fire fighting systems.

What this means for your facility

If your facility has no record of its sprinklers, the first step is to survey and document them. At AZEIDK Egypt we provide preventive, periodic and corrective maintenance for fire systems as part of our fire fighting systems work, and a maintenance visit can include listing sprinkler types and checking them against recall lists.

Older building and unsure of its sprinkler models? We survey, document and review the sprinklers with you under a clear maintenance contract. Contact the AZEIDK Egypt team

Sources: NFPA 25 Proposed TIA 1944, NFPA, comments closed 20 November 2026; From Recall to Resolution: Proposed Changes to Improve Fire Sprinkler Safety, NFSA, 23 July 2026