Choosing an addressable fire alarm sounder is not only about the decibel figure on the box. Every device on the loop draws current from the panel and batteries, sound falls with distance, and a beacon’s EN 54-23 rating decides the area it covers.
This article walks through the addressable sounders and beacons in the Context Plus datasheet on the AZEIDK Egypt Context Plus page, with a worked loop-load example and device selection for factories, warehouses and car parks on Egyptian projects.
Key takeaways
- The CON-series sounders in the datasheet come in three output classes: 91 dB(A) (compact), 96 dB(A) (base sounder under a detector) and 103 dB(A) (high-output wall unit), all measured at 1 m.
- All listed CON models draw 550 µA in quiescent mode. In alarm, a sounder draws 5 mA, a sounder with beacon 14 mA and a beacon only 10 mA, all at 24 VDC.
- An EN 54-23 code such as C-3-8 or W-2.4-8.2 sets mounting type, height and coverage volume.
- A beacon raises a device’s alarm current almost threefold, which affects loop device count and battery size.
- BS 5839-1 and NFPA 72 sound levels are design references, not Egyptian law.
In this article
- Addressable fire alarm sounders: what the Context Plus range offers
- Model table: sound output, current and size
- What the EN 54-23 coverage code means
- Loop current load: a worked example
- How many decibels do you need? Design references
- Which sounder for which space on Egyptian projects?
- IP rating for outdoor installation
- Common mistakes when choosing sounders and beacons
- Frequently asked questions
- Conclusion
Addressable fire alarm sounders: what the Context Plus range offers
On Egyptian sites a sounder is often called a fire alarm siren, and a beacon a flasher or visual alarm device (VAD). An addressable device takes power and commands from the panel loop, with no separate sounder circuit.
The addressable CON models in the datasheet share two features: a built-in short-circuit isolator that protects the rest of the loop if one section shorts, and group addressing to trigger many devices with one command. For the base, compact and high-output models the datasheet also states third-party certification to EN 54-3 (sounder) and EN 54-17 (isolator), plus EN 54-23 for models with a beacon. They sit within AZEIDK Egypt’s fire detection and alarm solutions. Confirm the exact model with our team before it goes into the BOQ.
Model table: sound output, current and size
Values from the datasheet; currents at 24 VDC.
| Model | Type | Output at 1 m | Alarm current | Quiescent current | Size and protection |
|---|---|---|---|---|---|
| CON431A/CX/W | Base sounder under a detector | 96 dB(A) | 5 mA | 550 µA | 112 mm dia., 46 mm deep (base), IP21C |
| CON456A/CX/W | Base sounder with C-3-8 beacon | 96 dB(A) | 14 mA | 550 µA | 112 mm dia., 46 mm deep, IP21C |
| CON450A/CX/SR | Compact wall/ceiling sounder | 91 dB(A) | 5 mA | 550 µA | 102 mm dia., 63 mm deep, IP21C |
| CON451A/CX/SR | Compact sounder with beacon (C-3-8 ceiling, W-3-2.1 wall) | 91 dB(A) | 14 mA | 550 µA | 102 mm dia., 63 mm deep, IP21C |
| CON458A/CX/SR | Beacon only (C-3-8 ceiling, W-3-2.1 wall) | No sounder | 10 mA | 550 µA | 102 mm dia., 63 mm deep, IP21C |
| CON430A/CX/DR | High-output wall sounder, deep base | 103 dB(A) | 5 mA | 550 µA | IP33C |
| CON433A/CX/DR | High-output sounder with W-2.4-8.2 beacon | 103 dB(A) | 14 mA | 550 µA | IP33C |
| CON430A/CX/DR/65 and CON433A/CX/DR/65 | IP65 versions of the two models above | 103 dB(A) | 5 mA and 14 mA | 550 µA | 114 mm dia., 132 mm deep, IP65 |
| 55000-001 | Open-area sounder | 100 dB(A) | Not stated | Not stated | IP65, isolating base, EN54-3 (2001) |
The two high-output models have 7 volume levels and up to 15 tone pairs. The 55000-001 output is stated at 90 degrees with no current values, so confirm its electrical data before using it in a loop calculation.
What the EN 54-23 coverage code means
EN 54-23 classifies a beacon by how it is mounted and the volume in which it reaches a minimum illuminance. The rating is a letter followed by two numbers:
- C (ceiling): C-x-y means a maximum mounting height of x metres and a cylindrical coverage volume y metres in diameter. C-3-8 on the CON456A, CON451A and CON458A means a ceiling up to 3 m high and an 8 m diameter cylinder.
- W (wall): W-x-y means a maximum wall mounting height of x metres and a cuboid coverage volume on a square base y metres a side. W-2.4-8.2 on the CON433A covers a volume on an 8.2 × 8.2 m base when mounted at 2.4 m; the datasheet states a minimum of 0.4 lux there.
- O (open): no restriction on shape or position; not used by these models.
Note that the CON451A gives C-3-8 on a ceiling but only W-3-2.1 on a wall, a square 2.1 m a side. On a wall it suits a small room, not a long corridor. Height is part of the code, so a C-3-8 device in a 6 m warehouse ceiling is outside its rating.
Loop current load: a worked example
On an addressable loop, detectors, call points, I/O modules and sounders share the same cable. Each panel has a maximum loop current in its datasheet, and more current means more voltage drop to the last device. Loop capacity, isolators and device layout are covered in addressable fire alarm loop design.
Example: a warehouse loop in an industrial zone
Assume these notification devices on one loop. Detectors and modules are added later from their own datasheets.
| Device | Qty | Quiescent (mA) | Alarm (mA) |
|---|---|---|---|
| CON430A/CX/DR (103 dB sounder) | 20 | 20 × 0.55 = 11.0 | 20 × 5 = 100 |
| CON433A/CX/DR (sounder with beacon) | 10 | 10 × 0.55 = 5.5 | 10 × 14 = 140 |
| CON456A/CX/W (base sounder with beacon, offices) | 8 | 8 × 0.55 = 4.4 | 8 × 14 = 112 |
| Total | 38 | 20.9 | 352 |
Adding quiescent to alarm current for safety gives about 373 mA of notification load on this loop alone. Swapping the ten CON433A units for CON430A sounders without beacons cuts 90 mA.
Effect on the batteries
If the project adopts 24 hours of standby and 30 minutes of alarm, these devices take about 24 × 0.0209 = 0.50 Ah in standby and 0.5 × 0.373 = 0.19 Ah in alarm, before panel, detector and ageing allowances. The full method with the safety factor is in fire alarm battery calculation.
How many decibels do you need? Design references
The figure on a sounder is measured at 1 m. In a free field, sound level falls by about 6 dB each time the distance doubles. A 103 dB sounder gives in theory about 91 dB at 4 m and about 79 dB at 16 m, and a 91 dB sounder about 67 dB at 16 m. Doors, racking and machinery reduce it further, so measure at acceptance.
Common references:
- BS 5839-1: in the 2017 edition, the general minimum is 65 dB(A). 60 dB(A) may be accepted in small spaces and stairwells, the level should be 5 dB(A) above persistent background noise in noisy areas such as factories, and 75 dB(A) at the bed head in sleeping areas. The 2025 edition replaced the 2017 edition on 30 April 2025, so check its text at design stage.
- NFPA 72 (2025 edition): in public mode the signal must be at least 15 dBA above the average ambient sound level in all occupied areas, ambient plus all appliances must not exceed 110 dBA at the minimum hearing distance, and above 105 dBA average ambient visual notification is required.
The legally binding reference in Egypt is the Egyptian Code for the Design and Implementation of Fire Protection for Buildings, 2026 edition, together with the requirements of the General Directorate of Civil Protection (Ministry of Interior). Its third part covers detection and alarm. The figures above are design references, not Egyptian legal requirements.
Which sounder for which space on Egyptian projects?
Offices, corridors, hotels and hospitals
The CON431A base sounder fits under a detector, using the same ceiling point with no separate mounting position. The datasheet describes it as suited to corridors, stairwells and open spaces. Where a visual alarm is also needed, use the CON456A with its built-in beacon.
Factories and warehouses
Production halls in zones such as 10th of Ramadan, 6th of October and Sadat City combine high noise and long distances. Measure noise during real operation, then use the CON430A 103 dB wall sounder, with the CON433A beacon version where sound may not be heard. In warehouses, high racking blocks sound and light, so spread more devices along the aisles.
Car parks, loading bays and roofs
An underground car park is exposed to humidity and dust, and open ramps, loading bays and roofs face rain and dust directly. Use IP65 versions such as the CON430A/CX/DR/65 and CON433A/CX/DR/65, or the 55000-001 open-area sounder.
IP rating for outdoor installation
An IP rating has two digits: the first for solids and dust, the second for water. IP21C (objects over 12.5 mm, vertically dripping water) suits dry indoor ceilings. IP33C adds protection against small objects and sprayed water. IP65 (dust-tight, water jets) is what outdoor locations need.
The datasheet classes the CON430A/CX/DR as Type A and the CON433A/CX/DR as Type B. In EN 54-3, Type A refers to indoor use and Type B to outdoor use. Sealed cable entries remain essential for any outdoor device.
Common mistakes when choosing sounders and beacons
- Counting loop devices by addresses only, ignoring alarm current.
- Adding a beacon to every sounder without need.
- Installing a C-3-8 beacon in a ceiling higher than 3 m, or relying on W-3-2.1 to cover a long corridor.
- Picking sound output without measuring actual hall noise.
- Using IP21C devices in open car parks or loading bays.
For sounders alongside manual call points, see manual call points and sounders.
Frequently asked questions
What is the difference between a sounder and a beacon?
A sounder is an audible alarm device. A beacon is a visual alarm device rated to EN 54-23. Some models combine both, such as the CON456A and CON433A.
How much current does a Context Plus addressable sounder draw?
Per the datasheet: 550 µA quiescent for the listed CON models; in alarm 5 mA (sounder), 14 mA (sounder with beacon) or 10 mA (beacon only), at 24 VDC.
Is a 103 dB sounder enough for a large factory?
Not necessarily. The figure is measured at 1 m and sound falls with distance and obstacles, so the device count comes from noise measurements and distances.
What does C-3-8 on a beacon mean?
A ceiling device mounted up to 3 m high, covering a cylinder 8 m in diameter under EN 54-23.
Which model suits car parks and open areas?
The IP65 versions, such as the CON430A/CX/DR/65 and CON433A/CX/DR/65, or the 55000-001 open-area sounder, with sealed cable entries.
Does Egyptian law require 65 dB?
The 65 dB(A) value comes from BS 5839-1 as a design reference. The binding reference is the Egyptian fire code with civil protection requirements.
Conclusion
Three checks decide the choice: sound level for the real noise and distance, an EN 54-23 rating that matches height and space, and a current load the loop and batteries can carry. Base it on calculation and measurement, not the decibel figure alone.
Selecting notification devices for a factory, warehouse or car park? Send us layouts, ceiling heights and noise conditions, and we will review suitable models and loop load with you. Talk to the AZEIDK Egypt team