A single-door fire hose cabinet in the BOQ is more than a red steel box. It is a set: body, hose reel, hose, nozzle and inlet valve, and each part shows up again at site receiving, testing and pricing.
This article covers the Falcon Gold FG-1001S cabinet supplied by AZEIDK Egypt: its contents, the hose and reel data in the submittal, site installation and testing, and price drivers. Cabinet locations and spacing have their own article.
Key takeaways
- FG-1001S is the model shown on the AZEIDK Egypt Falcon Gold page: a red single-door fire hose cabinet, manufactured locally in Egypt and fitted with genuine Falcon Gold components.
- The submittal lists a manual swinging-arm reel, a 25 mm x 30 m semi-rigid hose, a 12 bar maximum working pressure, a jet/spray nozzle and a 1.5 x 1 inch angle valve.
- EN 671-1:2012 sets a maximum working pressure of 1.2 MPa (12 bar) for 25 mm hose and requires the cabinet door to open to at least 170 degrees.
- Correct installation starts from the approved drawing, then wall fixing, the supply connection, pipe flushing, pressure testing and a functional test of every cabinet.
- The fire hose cabinet price depends on the specified body requirements, components, quantity and scope, not the model number alone.
What is the FG-1001S fire hose cabinet from AZEIDK Egypt?
The Falcon Gold page at AZEIDK Egypt shows one cabinet model, FG-1001S. In Egypt we supply red single-door Falcon Gold cabinets, manufactured locally and fitted with genuine Falcon Gold components from Dubai: hose reel, hose, nozzle and valve.
Note one point when reviewing documents. The submittal on the brand page is the manufacturer’s file for Falcon Gold cabinets and components, while the cabinet supplied in Egypt is made locally. So confirm the body material, sheet thickness, finish and dimensions of the supplied unit in the project submittal rather than copying the factory drawing. The reel, hose, nozzle and valve data in the file apply to the genuine components fitted in the cabinet.
The cabinet is part of the water-based network described on the AZEIDK Egypt fire fighting systems page. The legal reference in Egypt is the Egyptian Code for the Design and Implementation of Fire Protection for Buildings, 2026 edition (Ministerial Decree No. 355 of 2026), plus the drawings approved by the General Directorate of Civil Protection. EN 671-1 is a technical product standard, not a legal requirement in itself.
FG-1001S components
The submittal for the swinging manual hose reel assembly lists the reel disc and hub, swinging arm, waterway, inlet joint and hose, angle valve, nozzle, hose and an outlet protective spring. The table groups them for site receiving.
| Component | What the Falcon Gold file says | What to check at receiving |
|---|---|---|
| Cabinet body | AZEIDK Egypt page: red, single door, made locally | Material, thickness, finish, size and door swing per the project submittal; no scratches or rust |
| Hose reel | Manual, swinging arm; reel diameter 600 mm, width 150 mm, bracket length 290 mm | Reel turns and swings out freely |
| Hose | Semi-rigid, 25 mm x 30 m, maximum working pressure 12 bar | Printed length and bore; no cracks or kinks |
| Nozzle | Model N-04-2, adjustable jet/spray | Opens, closes and changes pattern easily |
| Inlet valve | 1.5 x 1 inch angle valve, model A-4 | Opening direction marked; size matches the branch |
| Waterway | Full brass waterway; hose fixed with threaded nipples instead of clamps | No leaks at hub or hose joint in testing |
The file also states the manufacturer’s reel tests: over 3,000 rotations with no visible leakage and 1,000 swings to at least 170 degrees with no leakage or damage. These are the manufacturer’s own figures.
Hose and reel: what matters when you select
The reel, hose and conformity certificate are covered in Falcon Gold Fire Hose Reels and Hoses in Egypt. Here we link three points to EN 671-1:2012, the European standard for semi-rigid hose reels permanently connected to a water supply in buildings for occupant use.
Diameter and length
The standard gives hose bores of 19, 25 and 33 mm and one continuous length that should not exceed 30 m. The FG-1001S hose is 25 mm x 30 m, at the top of that range.
Working pressure
For 19 and 25 mm hose the standard sets a maximum working pressure of 1.2 MPa (12 bar), a test pressure of 1.8 MPa and a minimum burst pressure of 3.0 MPa. The Falcon Gold 12 bar figure matches this limit. The designer checks the pressure at each cabinet in the hydraulic calculation, especially on lower floors of tall buildings, so it stays within the hose rating.
Nozzle and inlet valve
For a manual inlet valve, the standard requires closing in the clockwise direction, a marked opening direction and, for a screw-down valve, full opening in no more than 3.5 turns. It also sets minimum throw at 0.2 MPa: 10 m for a jet, 6 m for a flat spray and 3 m for a conical spray.
How to install an FG-1001S fire hose cabinet, step by step
These steps combine the manufacturer’s file, the standard’s product requirements and good site practice. The final reference is the approved drawing and the manufacturer’s instructions.
- Confirm the location on the approved drawing. Positions come from the approved fire drawings, as explained in Fire Hose Cabinet Locations. Do not move a cabinet without the designer.
- Match the cabinet to its location. Check the supplied cabinet’s size and door swing against the location on the drawing before delivery, so the door does not hit a wall or column and can open fully.
- Prepare the wall and fix the cabinet. Check the fixing holes in the back panel and the drain holes in the base of the supplied cabinet. Choose anchors for the wall type and the weight with a full hose, and level the cabinet so the door moves freely.
- Connect the supply branch. Run the branch from the riser or floor main to the inlet valve, matching its connection size, with room to turn the valve by hand.
- Flush the pipework. Remove swarf, welding debris and dust before water reaches the reel, or it can block the nozzle.
- Pressure test the network. Test the installed section hydrostatically as per the project documents before handover.
- Functional test of every cabinet. Check the door opens fully, open the valve, pull out the hose, run the nozzle in both patterns and check joints and hub for leaks.
- Signage and handover. Fit signage, give the owner the operating instructions and record each cabinet by number and location.
The manufacturer’s operating instructions are six steps: open the valve, pull the hose towards the fire, open the nozzle to jet or spray and aim at the base of the fire. After use, close the valve, drain the hose, then rewind it and close the nozzle.
What drives the fire hose cabinet price
Price questions often reach the AZEIDK Egypt team with little detail. The model number alone does not set the price; the quotation rests on the decisions below. We give no figures, because a correct price comes from the project specification and quantities.
| Factor | How it affects the price | What to send for an accurate quote |
|---|---|---|
| Body specification | Specified sheet thickness and dimensions change weight, material and cost | The body requirements in the BOQ |
| Finish and door wording | Any special wording or marking on the door adds a fabrication step | Wording required on the door, if any |
| Reel and hose components | Genuine Falcon Gold reel, hose, nozzle and valve are the largest share of value | Hose length and diameter, and nozzle type if specified |
| Quantity and delivery schedule | Volume and phased deliveries change fabrication and transport | Number of cabinets and delivery phases |
| Scope of work | Supply only differs from supply, install, connection and testing | Supply only, or with installation and testing |
| Documents | Some consultants require a full submittal before delivery | The consultant’s document requirements |
| Project location | Distance, access and lifting affect transport and installation | City and number of floors |
Compare quotations only when these items match. A lower offer may mean thinner sheet, a shorter hose or no installation, so describe the components in full in the BOQ line.
Common mistakes
- Copying the factory drawing into the project file without review, although the cabinet supplied in Egypt is made locally and its material and dimensions must be confirmed for the supplied unit.
- Not checking the door swing against the location, so the door hits a wall or column and cannot open fully.
- Ignoring network pressure on lower floors, so the cabinet sees more than the hose’s rated working pressure.
- Opening water to the reel before flushing, so construction debris blocks the nozzle.
- Placing furniture or goods in front of the cabinet after handover, so the door cannot open fully.
- Rewinding the hose full of water after testing, against the manufacturer’s instruction to drain it first.
After handover the cabinet enters the periodic inspection programme; see Fire Hose Maintenance in Egypt.
Frequently asked questions
What is inside the FG-1001S fire hose cabinet?
A single-door body, a manual swinging-arm reel, a 25 mm x 30 m semi-rigid hose, a jet/spray nozzle and a 1.5 x 1 inch angle inlet valve, as listed in the Falcon Gold component submittal.
Is the FG-1001S made in Egypt?
Yes. The AZEIDK Egypt Falcon Gold page states the cabinets are made locally under the Falcon Gold brand with genuine Falcon Gold components from Dubai.
Is a double-door cabinet available?
AZEIDK Egypt offers the single-door Falcon Gold cabinet. For a different arrangement, review the drawing with our team before writing the BOQ line.
What is the maximum working pressure of the cabinet hose?
The Falcon Gold file gives 12 bar maximum working pressure for the hose, the same limit EN 671-1:2012 sets for 25 mm hose. The pressure reaching each cabinet is checked in the hydraulic design.
How much does a fire hose cabinet cost?
It depends on the specified body requirements, components, quantity and scope of work. Send the BOQ and specification to the AZEIDK Egypt team for a project quotation.
Conclusion
The FG-1001S is a set: a locally made single-door body with a Falcon Gold reel, hose, nozzle and valve. Confirm the supplied unit’s specification in the submittal, install and test it to the drawing and manufacturer’s instructions, and compare quotations item by item.
Preparing the fire hose cabinet line for your project? Send us the number of cabinets, their locations and scope of work, and we will send the submittal and a detailed quotation for Falcon Gold cabinets. Talk to the AZEIDK Egypt team