Victaulic FireLock FL-QR/SW Horizontal Sidewall Sprinklers – V2826, V4226, V2710 and V3410

Victaulic FireLock FL-QR/SW quick-response horizontal-sidewall sprinklers with K2.8, K4.2, K5.6 and K8.0 options, available in standard or recessed arrangements.
العلامة التجارية
Victaulic FireLock FL-QR/SW Horizontal Sidewall Sprinklers – V2826, V4226, V2710 and V3410

تفاصيل المنتج

نظرة عامة على المنتج

Victaulic FireLock Series FL-QR/SW sprinklers are quick-response, standard-coverage horizontal-sidewall fire sprinklers designed for installation through walls.

This product page combines all models supplied in the same catalogue:

• V2826 with a K2.8 discharge coefficient.
• V4226 with a K4.2 discharge coefficient.
• V2710 with a K5.6 discharge coefficient.
• V3410 with a K8.0 discharge coefficient.

All models are horizontal-sidewall sprinklers and are available in standard or recessed-horizontal-sidewall arrangements according to the approved configuration and escutcheon.

The models are grouped under one product because they belong to the same FL-QR/SW family and share the same basic construction and operating principle. Their primary differences are K-factor, connection size, dimensions and selected approvals.

Key Features:

• Horizontal-sidewall fire sprinklers.
• Victaulic FireLock Series FL-QR/SW.
• Quick Response.
• Standard Coverage.
• Standard horizontal-sidewall installation.
• Recessed horizontal-sidewall installation.
• K2.8, K4.2, K5.6 and K8.0 options.
• Maximum working pressure of 175 PSI.
• 100% factory hydrostatically tested at 500 PSI.
• Minimum UL/FM operating pressure of 7 PSI.
• NPT and BSPT connection options.
• IGS options for V2710 and V3410.
• 3 mm nominal glass bulb.
• Multiple temperature ratings.
• Multiple frame finishes.
• Corrosion-resistant finish options.
• Compatible guards and installation tools by model.
• cULus Listed according to model.
• FM Approved for selected models and arrangements.
• LPCB Approved for V2710 as shown.
• CE Approved for V2710 as shown.
• Intended for systems designed according to NFPA and applicable local standards.

Available Models:

V2826:

• Orientation: Horizontal Sidewall.
• Response: Quick Response.
• K-factor: 2.8.
• Nominal metric K-factor: 4.0.
• Connection: 1/2-inch NPT or 15 mm BSPT.
• Maximum working pressure: 175 PSI.
• Available as standard or recessed.
• Globe re-designation shown: GL2826.
• Globe equivalent shown: GL5626.

V4226:

• Orientation: Horizontal Sidewall.
• Response: Quick Response.
• K-factor: 4.2.
• Nominal metric K-factor: 6.1.
• Connection: 1/2-inch NPT or 15 mm BSPT.
• Maximum working pressure: 175 PSI.
• Available as standard or recessed.
• Globe re-designation shown: GL4226.
• Globe equivalent shown: GL8127.

V2710:

• Orientation: Horizontal Sidewall.
• Response: Quick Response.
• K-factor: 5.6.
• Nominal metric K-factor: 8.1.
• Connection: 1/2-inch NPT or 15 mm BSPT.
• IGS option available for the standard arrangement.
• Maximum working pressure: 175 PSI.
• Available as standard or recessed.
• Carries broader approval options according to the catalogue tables.

V3410:

• Orientation: Horizontal Sidewall.
• Response: Quick Response.
• K-factor: 8.0.
• Nominal metric K-factor: 11.5.
• Connection: 3/4-inch NPT or 20 mm BSPT.
• IGS option available for the standard arrangement.
• Maximum working pressure: 175 PSI.
• Available as standard or recessed.

Standard and Recessed Arrangements:

Horizontal Sidewall:

The sprinkler is installed horizontally through the wall, with the sprinkler body visible and a flush or extended escutcheon according to the selected arrangement.

Recessed Horizontal Sidewall:

The sprinkler is installed partially within the wall using a recessed escutcheon to reduce the visible profile.

The recessed arrangement does not change the model number or K-factor. It changes the mounting arrangement and finished appearance.

Operation:

The sprinkler uses a heat-sensitive 3 mm nominal glass bulb.

When the ambient temperature reaches the rated temperature:

• The fluid inside the bulb expands.
• The glass bulb breaks.
• The sealing assembly releases.
• Water discharges through the sprinkler orifice.
• The sidewall deflector directs water outward, downward and away from the wall.
• Water is distributed across the protected area according to the approved sidewall spray pattern.

Discharge Coefficients:

V2826:

• K-factor: 2.8 GPM/psi½.
• Nominal metric value: 4.0.

V4226:

• K-factor: 4.2 GPM/psi½.
• Nominal metric value: 6.1.

V2710:

• K-factor: 5.6 GPM/psi½.
• Nominal metric value: 8.1.

V3410:

• K-factor: 8.0 GPM/psi½.
• Nominal metric value: 11.5.

Maximum Working Pressure:

• 175 PSI.
• Approximately 1200 kPa.
• Approximately 12 bar.

Factory Hydrostatic Test:

• 100% factory tested.
• Test pressure: 500 PSI.
• 3447 kPa.
• 34 bar.

Minimum Operating Pressure Shown:

• 7 PSI.
• 48 kPa.
• Approximately 0.5 bar.

Available Connections:

V2826 and V4226:

• 1/2-inch NPT.
• 15 mm BSPT.

V2710:

• 1/2-inch NPT.
• 15 mm BSPT.
• IGS grooved connection in the compatible arrangement.

V3410:

• 3/4-inch NPT.
• 20 mm BSPT.
• IGS grooved connection in the compatible arrangement.

Available Temperature Ratings:

• 135°F / 57°C.
• 155°F / 68°C.
• 175°F / 79°C.
• 200°F / 93°C.
• 286°F / 141°C.

Approved temperature ratings vary by model, installation arrangement, escutcheon and approval agency.

Deflector-to-Ceiling Distance:

The approval tables show typical deflector-to-ceiling distances of:

• 4 inches to 12 inches.
• Approximately 102 mm to 305 mm.

The installed distance must comply with the applicable listing and design standard.

Escutcheon Options:

Standard arrangement:

• Flush escutcheon.
• Extended escutcheon.

Recessed arrangement:

• Recessed escutcheon.
• 1/2-inch or 3/4-inch adjustment according to model and arrangement.

Main Construction Materials:

• Deflector: Bronze.
• Bulb: 3 mm nominal glass.
• Load screw: Bronze.
• Pip cap: Bronze.
• Spring seal: PTFE-coated beryllium nickel alloy.
• Frame: Brass.
• Lodgement spring: Stainless steel.
• Installation wrench: Ductile iron.

Available Finishes:

• Plain brass.
• Chrome plated.
• White polyester painted.
• Flat black polyester painted.
• Custom polyester painted.
• VC-250.

Selected polyester finishes are UL Listed for corrosion resistance. VC-250 is shown as UL Listed and FM Approved for corrosion resistance.

Approvals Shown:

V2826:

• cULus Listed according to the catalogue table.
• Standard and recessed arrangements listed at the shown temperatures.

V4226:

• cULus Listed.
• FM Approved for selected configurations.
• Standard and recessed arrangements available.

V2710:

• cULus Listed.
• FM Approved.
• LPCB Approved.
• CE Approved.
• Standard and recessed arrangements.

V3410:

• cULus Listed.
• Approval status varies according to configuration.
• Standard and recessed arrangements.

The final approval status depends on:

• Model.
• K-factor.
• Temperature rating.
• Installation arrangement.
• Escutcheon type.
• Finish.
• Connection type.

Main Dimensions:

V2826 and V4226:

• Approximate overall length: 2.5625 inches.
• Metric length: 64 mm.
• Approximate body height: 1.25 inches.
• Metric height: 31 mm.
• Nominal make-in: 7/16 inch.
• Metric make-in: 11 mm.

V2710:

• Approximate overall length: 3 inches.
• Metric length: 76 mm.
• Approximate body height: 1.25 inches.
• Metric height: 32 mm.
• Nominal make-in: 7/16 inch.
• Metric make-in: 11 mm.

V3410:

• Approximate overall length: 2.9375 inches.
• Metric length: 75 mm.
• Approximate body height: 15/16 inch.
• Metric height: 33 mm.
• Nominal make-in: 1/2 inch.
• Metric make-in: 13 mm.

Recessed Installation Dimensions:

Dimensions vary according to the selected model and escutcheon.

The catalogue shows adjustment options including:

• 1/2-inch adjustment.
• 3/4-inch adjustment.

Installation Tools:

V2826 and V4226:

• V56-2 Recessed Wrench.
• V56 Open-End Wrench.

V2710:

• V27-2 Recessed Wrench.
• V27 Open-End Wrench.

V3410:

• V34-2 Recessed Wrench.
• V34 Open-End Wrench.
• 3/16-inch Hex-Bit for compatible arrangements.

Compatible Guards:

• V28 for V2826.
• V42 for V4226.
• V27 for V2710.
• V34 for V3410.

Applications:

• Hotel rooms.
• Hospitals.
• Residential and commercial buildings.
• Offices.
• Corridors.
• Finished-ceiling rooms.
• Locations where pendent installation is difficult.
• Wall-perimeter protection.
• Architecturally finished interiors.
• Light-hazard applications.
• Ordinary-hazard applications according to model and design.
• Projects requiring multiple K-factor options.

Installation Requirements:

• Install only in the horizontal-sidewall orientation.
• The sprinkler waterway must be perpendicular to the wall.
• The word TOP on the deflector must face upward.
• Maintain the required deflector-to-ceiling distance.
• Use only the compatible escutcheon.
• Use the specified installation wrench.
• Do not apply installation force to the bulb or deflector.
• Do not field paint the sprinkler.
• Do not modify the frame or deflector.
• Depressurize and drain the system before installation or maintenance.
• Verify the approval status of the selected model and configuration.

Important Note:

Models V2826, V4226, V2710 and V3410 are grouped under one product because Victaulic supplies them together as the FireLock FL-QR/SW family in one catalogue.

The primary differences are K-factor, connection size, dimensions and selected approvals.