Victaulic FireLock V27 K5.6 Fire Sprinklers – V2703, V2704, V2707 and V2708
Brand
Victaulic
View Product
←
Victaulic FireLock Series FL-SR/ST sprinklers are standard-response storage sprinklers with a nominal K11.2 discharge coefficient, designed for warehouse and storage fire-protection applications.
This product page combines the two models supplied within the same product catalogue:
• V3403: Upright storage sprinkler.
• V3407: Pendent storage sprinkler, also available in a recessed-pendent installation configuration.
Both models belong to the same FireLock FL-SR/ST product family and share the same K-factor, response classification, working pressure, connection options and primary construction materials. Their main difference is installation orientation and deflector configuration.
The sprinklers use a CMDA, or Control Mode Density Area, approach. The fire-protection system is designed to deliver a calculated water density over a defined hydraulic operating area according to the stored commodity, storage arrangement and ceiling height.
Key Features:
• Storage fire-sprinkler family.
• Victaulic FireLock Series FL-SR/ST.
• Models V3403 and V3407.
• Standard Response.
• CMDA sprinkler type.
• Nominal K-factor of 11.2.
• Nominal metric K-factor of 16.1.
• Upright configuration.
• Pendent configuration.
• V3407 available as recessed pendent with a compatible arrangement.
• Maximum working pressure of 175 PSI.
• 100% factory hydrostatically tested at 500 PSI.
• Minimum UL/FM operating pressure of 7 PSI.
• NPT, BSPT and IGS connection options.
• Multiple temperature ratings.
• Multiple frame finishes.
• Corrosion-resistant finish options according to listing.
• cULus Listed.
• FM Approved.
• Intended for systems designed to NFPA, FM Data Sheets or applicable local standards.
Available Models:
V3403 Upright:
Installed above the branch line with the deflector directed upward.
When activated, water strikes the upright deflector and is distributed upward, outward and into the protected area below.
This model is suitable for storage-system layouts requiring an upright sprinkler orientation.
V3407 Pendent:
Installed below the branch line with the deflector directed downward over the protected storage area.
It can be installed as an exposed pendent sprinkler or as a recessed pendent using a compatible escutcheon and installation arrangement.
Model Differences:
• V3403: Upright orientation.
• V3407: Pendent or recessed-pendent orientation.
• Both models use K11.2.
• Both are Standard Response.
• Both are CMDA sprinklers.
• Both have a maximum working pressure of 175 PSI.
• Both are available with the connection options shown in the catalogue.
Operation:
Each sprinkler uses a 3 mm nominal-diameter heat-sensitive glass bulb.
When the ambient temperature reaches the rated operating temperature:
• Fluid inside the glass bulb expands.
• The bulb breaks.
• The sealing assembly releases.
• Water discharges through the sprinkler orifice.
• The deflector distributes water according to the selected sprinkler orientation.
• Fire control is provided according to the calculated design density and operating area.
Discharge Coefficient:
• K-factor: 11.2 GPM/psi½.
• Nominal metric K-factor: 16.1.
Maximum Working Pressure:
• 175 PSI.
• 1200 kPa.
• Approximately 12 bar.
Factory Hydrostatic Test:
• 100% factory tested.
• Test pressure: 500 PSI.
• 3447 kPa.
• 34 bar.
Minimum Operating Pressure Shown:
• 7 PSI.
• 48 kPa.
• Approximately 0.5 bar.
Available Connections:
• 3/4-inch NPT.
• 20 mm BSPT.
• IGS grooved connection.
The IGS option supports installation using the compatible Victaulic Installation-Ready Grooved Sprinkler Connection arrangement.
Available Temperature Ratings:
• 135°F / 57°C.
• 155°F / 68°C.
• 175°F / 79°C.
• 200°F / 93°C.
• 286°F / 141°C.
Verify the approved temperature rating for the selected model, connection and configuration.
Main Construction Materials:
• Deflector: Bronze.
• Bulb: Glass, 3 mm nominal diameter.
• Load screw: Bronze.
• Pip cap: Bronze.
• Spring seal: PTFE-coated beryllium nickel alloy.
• Frame: Brass.
• Lodgement spring: Stainless steel.
• Installation wrench: Ductile iron.
Available Finishes:
• Plain brass.
• Chrome plated.
• White polyester painted.
• Flat black polyester painted.
• Custom polyester painted.
• VC-250.
Selected polyester finishes are UL Listed for corrosion resistance. VC-250 is shown as UL Listed and FM Approved for corrosion resistance.
Compatible Sprinkler Guard:
• V34/V36 Sprinkler Guard.
Available Installation Tools:
• V34 Recessed Wrench.
• V34 Open-End Wrench.
• 3/16-inch Hex-Bit V9.
Select the tool according to the connection and installation arrangement. Do not apply installation force to the glass bulb or deflector.
V3403 Main Dimensions:
Threaded arrangement:
• Overall height: approximately 2.5 inches.
• Metric height: 63 mm.
• Frame and deflector height: approximately 1.75 inches.
• Metric height: 44 mm.
• Deflector width: approximately 1.875 inches.
• Metric width: 47 mm.
• Nominal make-in: 1/2 inch.
• Metric make-in: 13 mm.
V3407 Main Dimensions:
Threaded arrangement:
• Overall height: approximately 2.5 inches.
• Metric height: 63 mm.
• Lower frame-to-deflector dimension: approximately 15/16 inch.
• Metric dimension: 33 mm.
• Frame and deflector width: approximately 1.875 inches.
• Metric width: 47 mm.
• Nominal make-in: 1/2 inch.
• Metric make-in: 13 mm.
IGS grooved connection arrangements are also illustrated in the supplied catalogue.
Applications:
• Warehouses.
• Distribution centers.
• Open-frame rack storage.
• Single-row rack storage.
• Double-row rack storage.
• Multiple-row rack storage.
• Portable rack storage.
• Solid-pile storage.
• Palletized storage.
• Class I through Class IV commodities.
• Selected Group A and Group B plastic storage.
• Idle pallet storage.
• Rubber-tire storage.
• Rolled-paper storage.
• Flammable-liquid storage where permitted by the design.
• Aerosol storage according to the applicable standard.
• Selected automotive-component storage applications.
Referenced Design Standards:
• NFPA 13.
• NFPA 30.
• NFPA 30B.
• FM Data Sheet 2-0.
• FM Data Sheet 8-24.
• FM Data Sheet 8-3.
• FM Data Sheet 8-21.
• FM Data Sheet 7-29.
• FM Data Sheet 7-31.
Final model and system selection must consider:
• Stored commodity type.
• Commodity classification.
• Storage height.
• Ceiling height.
• Rack arrangement.
• Open or solid shelves.
• Obstructions around the sprinklers.
• Required sprinkler orientation.
• Sprinkler spacing.
• Design density.
• Hydraulic operating area.
• Available water flow and pressure.
• NFPA or FM requirements.
• Project, consultant and authority requirements.
Installation and Safety Notes:
• Design and install the sprinklers according to NFPA, FM Data Sheets or applicable local standards.
• Fully depressurize and drain the piping before installation, removal or maintenance.
• Use appropriate personal protective equipment.
• Do not install a damaged sprinkler or one with a cracked bulb.
• Do not field paint or modify the sprinkler.
• Use the compatible connection and installation tool.
• Use a compatible escutcheon when installing V3407 as a recessed pendent.
• Refer to the latest Victaulic documentation before final approval.
Important Note:
Models V3403 and V3407 are combined under one product because Victaulic supplies them together as the FireLock FL-SR/ST K11.2 family within one catalogue.
Select the final orientation, model, connection, temperature and finish according to hydraulic calculations, storage conditions, project specifications and required approvals.