TYCO Series TY-B Upright, Pendent and Recessed Pendent Fire Sprinklers

TYCO Series TY-B standard-response fire sprinklers available in upright, pendent and recessed-pendent configurations with K2.8, K5.6 and K8.0 discharge coefficients.
العلامة التجارية
TYCO Series TY-B Upright, Pendent and Recessed Pendent Fire Sprinklers

تفاصيل المنتج

نظرة عامة على المنتج

TYCO Series TY-B Fire Sprinklers are standard-response, standard-coverage automatic sprinklers available in upright, pendent and recessed-pendent configurations.

This product page combines all Series TY-B models because the catalogue presents them as one sprinkler family using the same basic construction and operating principle. The primary differences are K-factor, installation orientation, connection size, available finishes and model-specific approvals.

The series is designed for light, ordinary and selected extra-hazard commercial and industrial occupancies, including banks, hotels, shopping malls, factories, refineries and chemical plants, subject to the applicable hydraulic design and approval criteria.

Key Features:

• TYCO Series TY-B fire sprinklers.
• Standard Response.
• Standard Coverage.
• 5 mm heat-sensitive glass bulb.
• Available with K2.8, K5.6 and K8.0 discharge coefficients.
• Upright configurations.
• Pendent configurations.
• Selected models available as recessed pendent.
• Suitable for light-hazard applications.
• Suitable for ordinary-hazard applications.
• Suitable for selected extra-hazard applications according to design.
• 1/2-inch NPT or 3/4-inch NPT connections.
• ISO 7-1 threaded connections available upon special request.
• Multiple temperature ratings.
• Corrosion-resistant finishes available according to model and approval.
• Poly-Stainless options available for selected models.
• UL Listed according to model.
• C-UL Listed according to model.
• FM Approved according to model and finish.
• LPCB Approved for selected models.
• VdS Approved for selected models.
• NYC Approved for selected models.
• Intended for systems designed in accordance with NFPA 13.
• Pendent models can be combined with a Model S2 Shield for intermediate-level applications.

Available Models:

K2.8 Models:

TY1151:

• Orientation: Upright.
• K-factor: 2.8.
• Connection: 1/2-inch NPT.
• Response: Standard Response.
• Coverage: Standard Coverage.

TY1251:

• Orientation: Pendent.
• K-factor: 2.8.
• Connection: 1/2-inch NPT.
• Response: Standard Response.
• Coverage: Standard Coverage.

K5.6 Models:

TY3151:

• Orientation: Upright.
• K-factor: 5.6.
• Connection: 1/2-inch NPT.
• Response: Standard Response.
• Coverage: Standard Coverage.

TY3251:

• Orientation: Pendent or Recessed Pendent.
• K-factor: 5.6.
• Connection: 1/2-inch NPT.
• Response: Standard Response.
• Coverage: Standard Coverage.
• Uses the Style 10 Recessed Escutcheon.

K8.0 Models:

TY4151:

• Orientation: Upright.
• K-factor: 8.0.
• Connection: 3/4-inch NPT.
• Response: Standard Response.
• Coverage: Standard Coverage.

TY4251:

• Orientation: Pendent or Recessed Pendent.
• K-factor: 8.0.
• Connection: 3/4-inch NPT.
• Response: Standard Response.
• Coverage: Standard Coverage.
• Uses the Style 40 Recessed Escutcheon.

TY4851:

• Orientation: Upright.
• K-factor: 8.0.
• Connection: 1/2-inch NPT.
• Primarily intended for retrofit applications in existing sprinkler systems.
• Response: Standard Response.
• Coverage: Standard Coverage.

TY4951:

• Orientation: Pendent.
• K-factor: 8.0.
• Connection: 1/2-inch NPT.
• Primarily intended for retrofit applications in existing sprinkler systems.
• Response: Standard Response.
• Coverage: Standard Coverage.

Important Note for 1/2-inch K8.0 Models:

The catalogue states that NFPA 13 prohibits the installation of 1/2-inch NPT sprinklers with K-factors greater than 5.6 in new construction.

Models TY4851 and TY4951 are therefore primarily intended for retrofit or replacement in existing sprinkler systems rather than as default selections for new systems.

Operation:

The sprinkler contains a glass bulb filled with heat-sensitive fluid.

When the rated operating temperature is reached:

• The fluid inside the bulb expands.
• The glass bulb shatters.
• The sealing assembly releases.
• Water begins to discharge.
• The deflector distributes water according to the selected sprinkler orientation and spray pattern.

Discharge Coefficients:

K2.8:

• 2.8 GPM/psi½.
• 40.3 LPM/bar½.

K5.6:

• 5.6 GPM/psi½.
• 80.6 LPM/bar½.

K8.0:

• 8.0 GPM/psi½.
• 115.2 LPM/bar½.

Installation Orientations:

Upright:

Installed above the branch line with the deflector directed upward.

Pendent:

Installed below the branch line with the deflector directed downward.

Recessed Pendent:

Installed partially within the finished ceiling using an approved recessed escutcheon to reduce the visible profile.

Recessed-Pendent Options:

Style 10:

• For model TY3251.
• 1/2-inch NPT.
• 1/2-inch recessed adjustment.
• Up to 3/4-inch total adjustment.
• Escutcheon diameter approximately 2.875 inches.
• Metric diameter: 73 mm.

Style 40:

• For model TY4251.
• 3/4-inch NPT.
• 1/2-inch recessed adjustment.
• Up to 3/4-inch total adjustment.
• Escutcheon diameter approximately 2.875 inches.
• Metric diameter: 73 mm.

Available Temperature Ratings:

• 135°F / 57°C – Orange bulb.
• 155°F / 68°C – Red bulb.
• 175°F / 79°C – Yellow bulb.
• 200°F / 93°C – Green bulb.
• 286°F / 141°C – Blue bulb.
• 360°F / 182°C – Mauve bulb.

Available ratings and approvals vary by model and finish.

Main Construction Materials:

• Frame: Bronze.
• Button: Brass or copper.
• Sealing assembly: Beryllium nickel with PTFE.
• Bulb: Glass.
• Compression screw: Bronze.
• Deflector: Copper.
• Bushing on K2.8 models: Bronze.

Poly-Stainless Construction:

Selected Poly-Stainless models include:

• Button: L316 stainless steel.
• Compression screw: L316 stainless steel.
• Deflector: Copper or bronze.
• Sealing assembly: Gold-plated beryllium nickel with PTFE.
• Frame: Bronze.

Available Sprinkler Finishes:

• Natural brass.
• Chrome plated.
• Polyester coated.
• Poly-Stainless.
• Lead coated.
• Wax coated.
• Wax-over-lead coated.

Not all finishes are available for every model or temperature rating.

Recessed-Escutcheon Finishes:

• Signal White.
• Pure White.
• Grey Aluminum.
• Jet Black.
• Chrome plated.
• Natural brass.

Corrosion Protection:

Corrosion-resistant finishes can extend sprinkler service life in selected aggressive environments.

The final finish should be evaluated according to:

• Ambient temperature.
• Chemical concentration.
• Gas or vapor velocity.
• Type of corrosive exposure.
• Indoor or outdoor environmental conditions.

Passing standard corrosion tests does not mean that a finish is suitable for every corrosive atmosphere.

Working Pressure:

Maximum working pressure varies according to the model and applicable listing shown in Table D of the catalogue.

The selected model, connection and finish must be checked against the catalogue pressure table before final approval.

Installation Requirements:

• Do not install a sprinkler with a cracked glass bulb.
• Replace sprinklers that have lost bulb liquid.
• Apply suitable pipe-thread sealant.
• Tightening torque for 1/2-inch NPT models is 7 to 14 lb-ft.
• Equivalent torque is 9.5 to 19 N·m.
• Use the W-Type 6 sprinkler wrench for exposed sprinklers.
• Use the W-Type 7 recessed sprinkler wrench for recessed models.
• Do not apply installation force to the bulb or deflector.
• Do not over-tighten the sprinkler inlet.
• Use only the applicable Style 10 or Style 40 escutcheon.
• Install the escutcheon closure after ceiling completion without lifting the ceiling panel.

Care and Maintenance:

• Do not hang objects from sprinklers.
• Clean sprinklers only by gentle dusting.
• Do not field paint or coat the sprinkler.
• Replace leaking sprinklers.
• Replace sprinklers showing corrosion.
• Replace sprinklers damaged by impact or dropping.
• Replace sprinklers damaged by wrench slippage or twisting.
• Maintain the escutcheon in place for recessed installations.
• Inspect, test and maintain the system in accordance with NFPA 25 and authority requirements.

Applications:

• Banks.
• Hotels.
• Shopping malls.
• Office buildings.
• Factories.
• Warehouses.
• Refineries.
• Chemical plants.
• Light-hazard occupancies.
• Ordinary-hazard occupancies.
• Selected extra-hazard applications.
• Open ceilings.
• Suspended ceilings.
• Architecturally finished ceilings.
• Corrosive environments requiring approved protective finishes.

Standards and Approvals Shown in the Catalogue:

• UL Listed.
• C-UL Listed.
• FM Approved.
• LPCB Approved according to model.
• VdS Approved according to model.
• NYC Approved according to model.
• NFPA 13.
• FM Global Loss Prevention Data Sheets.
• NFPA 25 for inspection, testing and maintenance.

Important Note:

All Series TY-B models are combined under one product because they share the same product family and basic operating construction. Their primary differences are K-factor, orientation, connection size and finish.

The final model must be selected according to installation orientation, hazard classification, hydraulic calculations, pipe-connection size, temperature rating, required finish and project approval requirements.

الوثائق الفنية

كتالوج المنتج

اطّلع على البيانات والمعلومات الفنية الكاملة للمنتج من خلال الكتالوج الرسمي.

This site is registered on wpml.org as a development site. Switch to a production site key to remove this banner.