{"id":29636,"date":"2026-11-23T13:01:01","date_gmt":"2026-11-23T10:01:01","guid":{"rendered":"https:\/\/azeidkgroup.com\/sa\/media-center\/"},"modified":"2026-11-23T13:01:01","modified_gmt":"2026-11-23T10:01:01","slug":"deluge-valve-firetech-fx-vs-cla-val-134-05","status":"publish","type":"post","link":"https:\/\/azeidkgroup.com\/en\/sa\/media-center\/deluge-valve-firetech-fx-vs-cla-val-134-05\/","title":{"rendered":"Deluge Valve Comparison: FIRETECH FX vs Cla-Val 134-05 by Release Method, Size and Approval"},"content":{"rendered":"\t\t<div data-elementor-type=\"wp-post\" data-elementor-id=\"29636\" class=\"elementor elementor-29636 elementor-29635 elementor-bc-flex-widget\" data-elementor-post-type=\"post\">\n\t\t\t\t<div class=\"elementor-element elementor-element-c8770cc e-con-full az-el-article e-flex e-con e-parent\" data-id=\"c8770cc\" data-element_type=\"container\" data-e-type=\"container\">\n\t\t\t\t<div class=\"elementor-element elementor-element-f7adcf8 elementor-widget elementor-widget-text-editor\" data-id=\"f7adcf8\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<p class=\"az-intro\">A <strong>deluge valve<\/strong> is the part of a deluge system that releases water to every open nozzle at once. AZEIDK supplies two different approaches in Saudi Arabia: the FIRETECH FX, a diaphragm deluge valve with several release trims, and the Cla-Val 134-05, a solenoid-operated valve built on the Hytrol main valve. This comparison sets out what the two product pages publish, so the choice follows the release method, size and approval the project needs.<\/p>\n<p>For the system itself (detection, open nozzles and how the valve fits in), see our article on the <a href=\"\/en\/sa\/media-center\/deluge-sprinkler-system-valve-nozzles\/\">deluge sprinkler system<\/a>. Both valves are part of AZEIDK&#8217;s <a href=\"\/en\/sa\/solutions\/fire-fighting-systems\/\">fire fighting systems<\/a> scope.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-d1b983a elementor-widget elementor-widget-text-editor\" data-id=\"d1b983a\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<div class=\"az-keybox\"><h2>Key points<\/h2><ul><li>FIRETECH FX: line-pressure-operated diaphragm globe valve, UL listed as a deluge-type special system water control valve (file EX27978), 2 to 10 in, up to 250 psi.<\/li><li>The FX releases four ways: wet (hydraulic) pilot, dry (pneumatic) pilot, electric solenoid or manual, with factory test, alarm and drain trim.<\/li><li>Cla-Val 134-05: on-off solenoid control valve built on the UL\/ULC listed Hytrol 100G\/2100G main valve, 3 to 12 in.<\/li><li>The 134-05 is supplied normally open or normally closed, with a seawater version on the 100GS\/2100GS main valve.<\/li><li>Choose by the release method in the design, the line size, the water type and the approval written into the specification.<\/li><\/ul><\/div>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-0f499c4 elementor-widget elementor-widget-text-editor\" data-id=\"0f499c4\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>Deluge valve comparison table<\/h2>\n<div class=\"az-table-wrap\"><table><thead><tr><th>Item<\/th><th>FIRETECH FX<\/th><th>Cla-Val 134-05<\/th><\/tr><\/thead><tbody>\n<tr><td>Operating principle<\/td><td>Diaphragm valve held closed by water pressure in the cover chamber; opens fully when the chamber is vented<\/td><td>Diaphragm main valve opened or closed by an electrical signal to a three-way solenoid with an auxiliary pilot<\/td><\/tr>\n<tr><td>Published approval<\/td><td>UL, deluge-type water control valve, file EX27978<\/td><td>Main valve 100G\/2100G UL and ULC listed<\/td><\/tr>\n<tr><td>Sizes<\/td><td>2, 2\u00bd, 3, 4, 6, 8 and 10 in<\/td><td>3 to 12 in<\/td><\/tr>\n<tr><td>Working pressure<\/td><td>20 to 250 psi (1.4 to 17.5 kg\/cm\u00b2)<\/td><td>Not stated on the product page<\/td><\/tr>\n<tr><td>Hydrostatic test<\/td><td>500 psi<\/td><td>Not stated<\/td><\/tr>\n<tr><td>Release methods<\/td><td>Wet pilot, dry pilot, electric solenoid, manual<\/td><td>Electric solenoid<\/td><\/tr>\n<tr><td>Normal position<\/td><td>Closed<\/td><td>Normally open or normally closed, as ordered<\/td><\/tr>\n<tr><td>Body and ends<\/td><td>ASTM A216 Gr. WCB, ANSI B16.5 Class 150 RF flanges<\/td><td>Not stated<\/td><\/tr>\n<tr><td>Seawater<\/td><td>Not stated<\/td><td>100GS\/2100GS version<\/td><\/tr>\n<\/tbody><\/table><\/div>\n<p>The data comes from AZEIDK&#8217;s two product pages. &#8220;Not stated&#8221; means the page does not give the item; ask for it from the datasheet with the technical offer.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-c83b62b elementor-widget elementor-widget-text-editor\" data-id=\"c83b62b\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>FIRETECH FX: a deluge valve with several release trims<\/h2>\n<p>The <a href=\"\/en\/sa\/products\/firetech-fx-ul-listed-deluge-valve\/\">FIRETECH FX deluge valve<\/a> page describes a diaphragm-operated, line-fluid-actuated globe valve. It stays closed while pressure is held in the cover chamber above the diaphragm; on fire detection the chamber is vented through the release devices, the valve opens fully and water flows to the open nozzles or sprinklers. The diaphragm is nylon-reinforced Buna-N, with a soft-seat quad-ring for tight closure.<\/p>\n<p>Its clearest advantage is the choice of release: wet or dry pilot trim, an electric trim with a normally closed 2\/2-way solenoid (energised to open) wired to the releasing panel, or a manual release station. The UL listing states it is for hydraulically calculated systems, installed horizontally or vertically. Listed applications include transformers, fuel storage and loading, conveyors and aircraft hangars.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-5a83666 elementor-widget elementor-widget-text-editor\" data-id=\"5a83666\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>Cla-Val 134-05: a solenoid-operated deluge valve<\/h2>\n<p>The <a href=\"\/en\/sa\/products\/cla-val-134-05-solenoid-operated-deluge-valve\/\">Cla-Val 134-05<\/a> page describes an on-off valve that opens or closes when its solenoid pilot receives an electrical signal. It is built on the UL\/ULC listed Hytrol 100G\/2100G main valve, with a three-way solenoid and an auxiliary pilot that apply or relieve pressure on the main valve diaphragm. It is supplied normally open or normally closed, and the 100GS\/2100GS main valve is used for seawater. Listed applications are deluge and pre-action systems released by a detection or suppression panel, water spray for transformers and tank farms, foam systems, and marine and offshore protection. Other Cla-Val valves are covered in our article on <a href=\"\/en\/sa\/media-center\/cla-val-fire-pump-relief-deluge-valves-saudi\/\">Cla-Val fire pump valves<\/a>.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-cf2dc4e elementor-widget elementor-widget-text-editor\" data-id=\"cf2dc4e\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>How to choose<\/h2>\n<ol><li><strong>Release method in the design.<\/strong> If release is by hydraulic or pneumatic pilot line or a manual station, the FX offers it in its trims. If release is electric from the detection panel, both valves fit.<\/li><li><strong>Size.<\/strong> FX runs from 2 to 10 in and the 134-05 from 3 to 12 in, so a 2 or 2\u00bd in line points to the FX and a 12 in line to the 134-05.<\/li><li><strong>Water type.<\/strong> For marine and offshore sites, Cla-Val lists a dedicated seawater version.<\/li><li><strong>Approval.<\/strong> Read exactly what the specification asks for (a listed deluge valve, or a listed main valve) and match it to the document.<\/li><li><strong>Normal position.<\/strong> Some applications need a normally open valve, which the 134-05 offers.<\/li><\/ol>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-36b62a7 elementor-widget elementor-widget-text-editor\" data-id=\"36b62a7\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>Common mistakes<\/h2>\n<ul><li>Choosing the valve before the release method is fixed, then finding the required trim is not offered on that model.<\/li><li>Comparing nominal size without checking the site water pressure against the valve&#8217;s limits.<\/li><li>Overlooking the test, alarm and drain trim, which matters at handover and in maintenance.<\/li><li>Confusing deluge with pre-action; the difference is explained in our article on the <a href=\"\/en\/sa\/media-center\/pre-action-sprinkler-system\/\">pre-action sprinkler system<\/a>.<\/li><\/ul>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-f2c9b7b elementor-widget elementor-widget-text-editor\" data-id=\"f2c9b7b\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<div class=\"az-faq\"><h2>Frequently asked questions<\/h2>\n<details class=\"az-faq__item\"><summary><h3>What is a deluge valve?<\/h3><\/summary><p>A valve that stays closed until it receives a release command from the detection system or by hand, then opens fully so water flows to all open nozzles in the zone at once.<\/p><\/details>\n<details class=\"az-faq__item\"><summary><h3>What is the difference between the FIRETECH FX and the Cla-Val 134-05?<\/h3><\/summary><p>The FX is a diaphragm deluge valve with wet, dry, electric and manual release; the 134-05 is a solenoid-operated valve on the Hytrol main valve, supplied normally open or normally closed.<\/p><\/details>\n<details class=\"az-faq__item\"><summary><h3>What deluge valve sizes does AZEIDK supply?<\/h3><\/summary><p>FIRETECH FX from 2 to 10 in and Cla-Val 134-05 from 3 to 12 in.<\/p><\/details>\n<details class=\"az-faq__item\"><summary><h3>Are these deluge valves UL listed?<\/h3><\/summary><p>The FIRETECH FX is UL listed as a deluge valve (file EX27978); the Cla-Val 134-05 main valve is UL and ULC listed.<\/p><\/details>\n<details class=\"az-faq__item\"><summary><h3>Where are deluge systems used?<\/h3><\/summary><p>Transformers, fuel storage and loading facilities, conveyors, aircraft hangars and other high-hazard areas that need discharge from all nozzles at the same time.<\/p><\/details>\n<\/div>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-2b55d61 elementor-widget elementor-widget-text-editor\" data-id=\"2b55d61\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<h2>Summary<\/h2>\n<p>Both valves do the same job in different ways: the FIRETECH FX is a deluge valve with several release trims from 2 in, and the Cla-Val 134-05 is a solenoid-operated valve up to 12 in with a seawater version. Fix the release method, size and approval first, then choose. AZEIDK handles supply, installation, testing and maintenance under its <a href=\"\/en\/sa\/services\/annual-maintenance-contracts\/\">preventive maintenance contracts<\/a>.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-6615815 elementor-widget elementor-widget-text-editor\" data-id=\"6615815\" data-element_type=\"widget\" data-e-type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<p class=\"az-cta\"><strong>Need a deluge valve for a project?<\/strong> Send the system drawing, release method, size and site water pressure, and the AZEIDK team will recommend the valve and trim. <a href=\"\/en\/sa\/contact\/\">Contact AZEIDK<\/a><\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t","protected":false},"excerpt":{"rendered":"<p>Deluge valve comparison from the product pages: FIRETECH FX diaphragm valve versus Cla-Val 134-05 solenoid valve by release method, size, pressure and UL.<\/p>\n","protected":false},"author":0,"featured_media":29633,"comment_status":"closed","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"_acf_changed":false,"footnotes":""},"categories":[221,321,323,322],"tags":[],"azeidk_region":[223],"class_list":["post-29636","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-azeidk-articles","category-codes-certifications-en","category-systems-guides-en","category-systems-guides-ar"],"acf":[],"_links":{"self":[{"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/posts\/29636","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/types\/post"}],"replies":[{"embeddable":true,"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/comments?post=29636"}],"version-history":[{"count":0,"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/posts\/29636\/revisions"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/media\/29633"}],"wp:attachment":[{"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/media?parent=29636"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/categories?post=29636"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/tags?post=29636"},{"taxonomy":"azeidk_region","embeddable":true,"href":"https:\/\/azeidkgroup.com\/en\/wp-json\/wp\/v2\/azeidk_region?post=29636"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}